Barbara Sadowska-Buraczewska1, Danuta Barnat-Hunek2, Małgorzata Szafraniec2.
Abstract
The use of recycled concrete aggregates (RCA) in high performance concrete (HPC) was analyzed. The paper presents the experimental studies of model reinforced concrete beams with a rectangular section using high-performance recycled aggregates. Two variable contents of recycled aggregate concrete were used in this study: 50% and 100%. The experimental analyses conducted as immediate studies concerned the following issues: short time loads-deflection, load-carrying capacity of beams, deformation of concrete, cracks, and long-term loads-deflection. The comparative analysis involves the behavior of beams made of high performance concrete-high strength concrete (HPC-HSC) recycled aggregates with model control elements made of regular concrete based on natural aggregates. The deflection values for the recycled aggregate beams were 20% higher than in the case of the control beams made of HPC-HSC exclusively. Replacement of aggregate with recycled concrete aggregate resulted in a large decrease in the value of these two parameters, i.e., compression strength by about 42% and modulus of elasticity by about 33%.Entities:
Keywords: concrete beams; high performance concrete (HPC); high strength concrete (HSC); high-performance recycled aggregates; recycled aggregate concrete (RAC)
Year: 2020 PMID: 31906468 PMCID: PMC6981771 DOI: 10.3390/ma13010186
Source DB: PubMed Journal: Materials (Basel) ISSN: 1996-1944 Impact factor: 3.623
Technical parameters of CEM I 52.5R Portland cement [34].
| Parameters | Unit | Value |
|---|---|---|
| Specific surface | (cm2∙g−1) | 4530 |
| Initial setting time | (min) | 157 |
| Loss on ignition by weight cement | (%) | 3.10 |
| Compressive strength | ||
| after 2 days | (MPa) | 35.8 |
| after 28 days | 63.7 | |
| Density | (g∙cm−3) | 3.14 |
| Volume stability | (mm) | 0.20 |
| SO3 content | (%) | 2.87 |
| Cl content | (%) | 0.049 |
| Insoluble residue | (%) | 0.64 |
| Na2Oeq content | (%) | 0.65 |
Figure 1Gradation of basalt and recycled aggregates.
Composition of concrete mixtures.
| Components | Unit | HPC-HSC | REC-1 | REC-2 |
|---|---|---|---|---|
| CEM I 52.5R cement | (kg∙m−3) | 450 | 450 | 450 |
| Quartz sand (0–2 mm) | (kg∙m−3) | 630 | 630 | 630 |
| Basalt (2–8 mm) | (kg∙m−3) | 1070 | 535 | – |
| Recycled aggregate(2–8 mm) | (kg∙m−3) | – | 535 | 1070 |
| Silica fume | (kg∙m−3) | 45 | 45 | 45 |
| Superplasticizier | (kg∙m−3) | 8.1 | 8.1 | 8.1 |
| Water | (kg∙m−3) | 130.9 | 130.9 | 130.9 |
Chemical composition of the natural quartz sand.
| Compositions | SiO2 | Al2O3 | Fe2O3 | CaO |
|---|---|---|---|---|
| 95.2 | 2.0 | 0.6 | 0.45 |
Properties of basalt and recycled aggregates (own research).
| Properties | Basalt | Recycled Aggregate |
|---|---|---|
| Specific density (g∙cm−3) | 2.93 | 2.80 |
| Bulk density (g∙cm−3) | 2.92 | 2.60 |
| Absorptivity (%) | 0.31 | 0.78 |
| Abrasion resistance (mm3) | 6520 | 4520 |
| Tightness (%) | 0.996 | 0.928 |
| Thermal resistance (°) | 340 | 290 |
| Compressive strength (MPa) | 280 | 155 |
| Frost resistance (F) | F2 | F2 |
Chemical composition of the basalt and recycled aggregate (%) (own research).
| Compositions | SiO2 | Al2O3 | FeO | MgO | CaO | TiO2 | K2O | Other Alkaline Compounds |
|---|---|---|---|---|---|---|---|---|
|
| 26.60 | 23.22 | 2.40 | 2.49 | 35.25 | 0.33 | 3.21 | 6.5 |
|
| 48.5 | 13.8 | 10.5 | 12.2 | 10 | 0.9 | 0.1 | 4.0 |
Chemical composition of the silica fume [35].
| Compositions | SiO2 | Al2O3 | Fe2O3 | CaO | SO3 | Na2O | K2O | Other Alkaline Compounds |
|---|---|---|---|---|---|---|---|---|
| 90 | 0.4 | 0.4 | 1.6 | 0.4 | 0.5 | 2.2 | 1.9 |
Properties of the superplasticizer [36].
| Properties | Superplasticizer |
|---|---|
| Aspect | Light Brown liquid |
| Relative density at 25 °C (g∙cm−3) | 1.08 |
| pH | ≥ 6 |
| Chloride ion content (%) | <0.2 |
| Expected water reduction (%) | > 20 |
Figure 2The scheme of reinforcement for beams.
Properties of recycled aggregate concrete and the HSC-HPC concrete.
| Type of Concrete | Apparent Density (kg∙m−3) | Absorptivity (%) | Open Porosity (%) | Average Pore Diameter (µm) |
|---|---|---|---|---|
| HSC-HPC | 2560 | 1.26 | 5.54 | 0.041 |
| REC-1 | 2450 | 1.54 | 6.53 | 0.055 |
| REC-2 | 2390 | 2.48 | 8.98 | 0.060 |
Characteristics of the recycled aggregate concrete and the HSC-HPC concrete.
| Type of Concrete/Descriptive | Compressive Strength (MPa) | Tensile Strength in Bending (MPa) | Elastic Modulus (GPa) | |||
|---|---|---|---|---|---|---|
| after 7 days | after 14 days | after 28 days | ||||
|
| Mean | 98.92 | 102.85 | 128.65 | 9.20 | 59.07 |
| SD | 1.50 | 0.81 | 1.72 | 0.26 | 1.31 | |
| CV | 1.51 | 0.79 | 1.34 | 2.85 | 2.22 | |
|
| Mean | 79.47 | 95.6 | 102.67 | 7.00 | 51.13 |
| SD | 0.46 | 0.89 | 2.25 | 0.20 | 1.77 | |
| CV | 0.58 | 0.93 | 2.19 | 2.86 | 3.47 | |
|
| Mean | 56.43 | 67.12 | 74.03 | 5.63 | 39.92 |
| SD | 0.78 | 1.18 | 1.20 | 0.40 | 1.18 | |
| CV | 1.39 | 1.76 | 1.62 | 7.17 | 2.95 | |
Coefficient of variation—CV (%), Standard deviation—SD.
Characteristics of the recycled aggregate concrete and the HSC-HPC concrete.
| Strength Properties | HSC-HPC | REC-1 | REC-2 |
|---|---|---|---|
| Class according to PN-EN 206 standard [ | C100/115 | C90/105 | C55/67 |
Figure 3Strength of concretes after 7, 14, and 28 days.
Figure 4Correlation between compression strength and elastic modulus E of concrete.
Figure 5Crack shaping and development in the test samples: (a) HPC-HSC; (b) REC-1; (c) REC-2.
Mean experimental values of rupture force and breaking moments.
| Symbol of Beam/Descriptive | Rupture Force | Breaking Moment | |
|---|---|---|---|
| HSC-HPC | Mean | 48.00 | 8.01 |
| SD | 1.73 | 0.14 | |
| CV | 3.61 | 1.69 | |
| REC-1 | Mean | 43.03 | 7.35 |
| SD | 1.17 | 0.17 | |
| CV | 2.71 | 2.38 | |
| REC-2 | Mean | 42 | 7.08 |
| SD | 1.49 | 0.08 | |
| CV | 3.55 | 1.08 | |
Coefficient of variation—CV (%), Standard deviation—SD.
Figure 6Correlation between bending tensile strength and breaking moment Msd of analyzed concrete.
Figure 7Experimental values of ε (‰) concrete deformations along cross-section height for selected forces: (a) force 15kN; (b) force 25 kN; (c) force 35 kN.
Figure 8Correlation between force acting on the concrete samples and deflection.
Figure 9Long-time deflection values for concrete.