Literature DB >> 31772207

Long-term monitoring data from a naturally ventilated office building.

Marcel Schweiker1, Michael Kleber2, Andreas Wagner2.   

Abstract

Data was collected in the field, from an office building located in Frankfurt, Germany, over the period of 4 years. The building was designed as a low-energy building and featured natural ventilation for individual control of air quality as well as buoyancy-driven night ventilation in combination with a central atrium as a passive cooling strategy. The monitored data include in total 116 data points related to outdoor and indoor environmental data, energy related data, and data related to occupancy and occupant behaviour. Data points representing a state were logged with the real timestamp of the event taking place, all other data points were recorded in 10 minute intervals. Data were collected in 17 cell offices with a size of ~20 m2, facing either east or west). Each office has one fixed and two operable windows, internal top light windows between office and corridor (to allow for night ventilation into the atrium) and sun protection elements (operated both manually and automatically). Each office is occupied by one or two persons.

Entities:  

Year:  2019        PMID: 31772207      PMCID: PMC6879735          DOI: 10.1038/s41597-019-0283-3

Source DB:  PubMed          Journal:  Sci Data        ISSN: 2052-4463            Impact factor:   6.444


Background & Summary

The introduction of the European “Energy Performance of Buildings Directive” in 2001 gave a strong incentive to reduce excessive energy consumption through a holistic approach in terms of building design and integrated energy concepts. Within this context, the program SolarBau, introduced by the German Federal Ministry of Economic Affairs, funded ambitious demonstration projects within the non-residential building sector setting benchmarks in terms of low primary energy consumption. Buildings in Germany are benchmarked through their primary energy demand for heating, cooling, ventilation, lighting and domestic hot water (DHW). The monitored building described here had a projected value of 107 kWh/m²a. Within this program, a strong focus was set on various passive cooling strategies in combination with a higher insulation standard than required by German regulations in the year of construction (see Table 1 for details). Daylight factors above standard at the workspaces were achieved by proper window design and light directing devices (venetian blinds with different blind positions and ceiling panels above the desks). At the same time, occupants’ interactions with windows and blinds – essential aspects in the context of passive cooling concepts – was addressed[1-3] as well as their thermal comfort under these conditions. A two-year monitoring after commissioning of the building was compulsory for a proof of concept for all funded buildings.
Table 1

Building characteristics.

Type of buildingMulti-storey office building
Dimension17,402 m2 (8,585 m2 heated)
No. of Employee~350 employees
LocationFrankfurt, Germany
Thermal characteristics

High energy standard of building envelope

Walls: U-values 0.24 to 0.5 W/m2K)

Windows: U-values 1.5 W/m2K, solar transmittance <40%, light transmittance 70%

Structural systemReinforced concrete construction
Type of observed spacesOffice rooms
Year of construction2002
No. of floors2-level underground car park +4 office floors + 1 floor apartments on top
Window dimensions

Windows:

Top lights

Windows, orientationMostly E and W
Window opening

All windows open inwards. No obstacles prevented window opening except those potentially added by occupants (e.g. plants or papers placed in front of window)

Windows: Manual opening through window handle by occupants only, windows had hinges on one side and could be fully opened (rotated) to any degree up to 90° opening angle Top lights: automatic control + manual opening through switch next to office door by occupants, windows had hinges at the bottom and opened on top; any degree up to ° was possible at manual control; at automatic control for night-time ventilation the angle was predefined in order to balance pressure difference between floors and achieve almost the same volume flow for each floor and office.

Window control options

Automated 10 minutes flush ventilation before working hours through top lights in the façade and between office and corridor

Afterwards: Top lights: Tilt (automatic + occupant driven mode), Windows: Tilt-and turn (occupant driven)

Shading devicesExternal sun protection (automatic + occupant driven mode) with different angle of blinds in the upper part to provide daylight guidance. Sun protection consists of light metal Venetian blinds with a slats width of 80 mm and a reflectance of 60%..
Predicted annual primary energy consumption107 kWh/m²
Monitored annual primary energy consumption100 kWh/m² in third year of monitoring
Building characteristics. High energy standard of building envelope Walls: U-values 0.24 to 0.5 W/m2K) Windows: U-values 1.5 W/m2K, solar transmittance <40%, light transmittance 70% Windows: Top lights All windows open inwards. No obstacles prevented window opening except those potentially added by occupants (e.g. plants or papers placed in front of window) Windows: Manual opening through window handle by occupants only, windows had hinges on one side and could be fully opened (rotated) to any degree up to 90° opening angle Top lights: automatic control + manual opening through switch next to office door by occupants, windows had hinges at the bottom and opened on top; any degree up to ° was possible at manual control; at automatic control for night-time ventilation the angle was predefined in order to balance pressure difference between floors and achieve almost the same volume flow for each floor and office. Automated 10 minutes flush ventilation before working hours through top lights in the façade and between office and corridor Afterwards: Top lights: Tilt (automatic + occupant driven mode), Windows: Tilt-and turn (occupant driven) Influencing factors on the occupants’ behaviour with regard to the operation of windows and blinds are, among others, the indoor and outdoor environmental conditions such as temperatures, relative humidity levels, air quality levels, and lighting levels[4,5]. Due to their daily and seasonal variation, long-term monitoring data, i.e. at least a full year, is essential to capture their influence on occupants’ behavioural patterns. The monitored building is located in Frankfurt am Main, Germany. Key characteristics of the building are presented in Table 1. An important design feature to enhance natural night ventilation is a large atrium with an extended “chimney” around which the offices are located. This enables a buoyancy-driven airflow from the windows through the offices themselves, into the traffic zones, and then up into the chimney where the air leaves the building. The airflows through the offices are levelled out by the opening angle of the top lights, located above the manually operable windows. Directly exposed concrete ceilings in the offices enable the activation of thermal mass as an essential part of passive cooling by night ventilation. Furthermore, the atrium increases the usage of natural lighting for the interior traffic zones. Only the meeting rooms, the offices to the south behind the double-skin facade, offices with suspended ceilings and a number of special purpose areas are actively cooled, but are not part of this dataset. The occupant is able to open the windows manually. For operating the top–light windows (see Fig. 1) occupants have to use the control panel which is located beside the door (opposite to the façade). Through this panel, occupants can also control the exterior Venetian blinds and the artificial lighting of the office. Outdoor noise due to traffic was only present in the area of the south facing rooms, which are not part of this dataset. No other noise sources are known. Outdoor air quality was high, given outdoor CO2-levels (included in data) being mean 465 ppm ± 52 (standard deviation).
Fig. 1

Window positions and dimensions of one office.

Window positions and dimensions of one office. The dataset published consists of long-term data from January 2005 to December 2008, i.e. starting 2 years after the construction, when initial problems with controls where already solved. The data published has a 10-minute interval for continuous data and the event data with individual time stamps and consists of data from 17 offices. The data has been analysed and used by several authors. A first analysis of the indoor environmental conditions and energy revealed that indoor air quality levels were high, that the primary energy consumption was at a low level as predicted, and that the monitoring was a useful measure towards an optimized operation[6,7]. Schakib-Ekbatan et al. questioned the fit between occupant behaviour and the building concept and found several occurrences of occupants’ window opening behaviour contradicting the natural ventilation concept[8]. An additional analysis of the data applied a data mining framework for identifying occupancy patterns and found four archetypal working profiles[9].

Methods

Monitoring concept

In order to collect long-term data automatically and frequently, all sensors were connected to the building management system (BMS) of the building. Data were gathered in 10-minute intervals or as event data. Data was stored for one day locally and send at night as csv-files to the server of the researcher. Data was stored in a MySQL database. A weather station was located on the top of the building at 2 m above the roof, i.e. around 30 m above street level. The weather station is providing data regarding the outdoor conditions for all offices, such as temperature or wind speed. However, the microclimate on the façades can differ, e.g. depending on the intensity and direction of wind. The precipitation meter was not heated. However, snowfall is seldom. There are no direct obstacles close-by affecting the wind speed or direction. Still, wind speed and direction might have been affected by the buildings in the neighbourhood. All offices included in this data base have a size of ~20 m2 and are facing east or west (see also Table 2). Each office has one fixed and two operable windows with top light windows above, internal top light windows between office and corridor (to allow for night ventilation into the atrium) and external sun protection elements (operated both manually and automatically). One or two persons occupy each office.
Table 2

Orientation and variables available for each office.

Room IDRoom air temperatureOccupancyWindow controlTop window controlSun protectionElectricity demand lightingElectricity demand plugsCO2− Concen- tration
EastE01E01TairE01OccE01WE01WTE01SP
E02E02TairE02OccE02WE02WTE02SP
E03E03TairE03OccE03WE03WTE03SP
E04E04TairE04OccE04WE04WTE04SPE04CO2
E05E05TairE05OccE05WE05WTE05SP
E06E06TairE06OccE06WE06WTE06SPE06ElLE06ElP
E07E07TairE07OccE07WE07WTE07SPE07ElLE07ElPE07CO2
E08E08TairE08OccE08WE08WTE08SP
E09E09TairE09OccE09WE09WTE09SP
E10E10TairE10OccE10WE10WTE10SP
E11E11TairE11OccE11WE11WTE11SP
WestW01W01TairW01OccW01WW01WTW01SPW01ElLW01ElP
W02W02TairW02OccW02WW02WTW02SP
W03W03TairW03OccW03WW03WTW03SP
W04W04TairW04OccW04WW04WTW04SP
W05W05TairW05OccW05WW05WTaW05SPW05ELPW05CO2
W06W06TairW06OccW06WW06WTW06SP

aNote that no data file is provided for this sensor, because no event was recorded over the monitoring period.

Orientation and variables available for each office. aNote that no data file is provided for this sensor, because no event was recorded over the monitoring period. Presence of occupants was measured by an infrared sensor located in the middle of the ceiling panel, which is suspended from the ceiling above the work places. Air temperature, relative humidity and CO2-level were measured inside each office close to the office door at 1.1 m height through a device attached to the walls separating the offices from the corridor. Occupants can change the status of top-light windows, blinds, and lighting through a set of buttons close to the office door. Windows can be opened directly at the façade. Status of windows was measured through reed-contacts connected to the buildings’ BMS system. Position of the blinds was measured based on blinds’ motor run time. The data points available in the database are presented in Table 3. These data can be grouped into outdoor environmental data, indoor environmental data, energy related data, and data related to occupancy and occupant behaviour.
Table 3

Variables, their categories and subcategories according to the ontology for building monitoring[13], and intervals.

Categories of dataSubcategories of measured dataVariableIntervalSensor
RangeAccuracy
InhabitantsOtherPresence (all rooms)Event
OtherWindow state (open/closed)Event
OtherTop-light window state (open/closed)Event
OtherState of sun protection (open/closed)Event
Indoor conditionsHygro-thermalAir temperature10 minutes0–40 °C±0.1 K
Hygro-thermalRelative humidity (all rooms)10 minutes0–100%±1%
Indoor Air QualityCO2-level (3 rooms)10 minutes300–3500 ppm±3%
External conditionsHygro-thermalAir temperature10 minutes−40–+ 45 °C±0.1 K
Hygro-thermalRelative humidity10 minutes0–100%±2%
VisualIlluminance (4 orientations + horizontal)10 minutes0–100,000 lx±5%
Solar radiationHorizontal solar radiation10 minutes0–1300 W/m²±2.5%
OtherPrecipitation (Amount and event)10 minutes
OtherWind speed and direction10 minutes0–360° 0–20 m/s
EnergyHeating/coolingOverall heat quantity pellet boiler and gas boiler10 minutes±1%
LightingLighting energy (3 meters for 5 rooms)10 minutes±0.5%
EquipmentPlug loads separated by IT and other (3 rooms)10 minutes±0.5%
OtherTotal electricity use of building10 minutes±0.5%
Variables, their categories and subcategories according to the ontology for building monitoring[13], and intervals.

Data Records

All data records listed in this section are available from the project pages[10] on Open Science Framework (OSF) and can be downloaded without an OSF account. We licensed the data under a CC0 1.0 Universal license.

All datasets

File format: comma separated values file (.csv). Data is available as one file for each sensor including date and time column. All date formats are in the format day, month, year, i.e. dd.mm.yyyy. Devices in use are recorded with 1 or 100, those not in use with 0. This translates to open windows being in the data recorded as 1 and completely closed blinds with values 100.

Code book

File format: comma separated values file (.csv).

Technical Validation

Incoming datasets were analysed according to their completeness and validity. An error message was sent to the researchers in case these checks revealed problems. These analyses mainly targeted for checking availability of data and to filter implausible or missing values. Missing values in air temperature, relative humidity, and CO2 were marked by a value of “0” and filtered automatically. Implausible values, e.g. indoor air temperatures above 35 °C, were flagged by the monitoring software and manually inspected using the visualization tools of the monitoring software. The monitoring software used was MoniSoft[11]. The air temperature sensors were checked and calibrated during commissioning by the facility management and later comparison through a high-quality comfort meter equipment in sample rooms showed good conformity. All other sensors had been calibrated by the manufacturer, but could not be calibrated again during operation.

Usage Notes

By the general and open csv format the researcher is free to use whatever software s/he finds suitable for analysing or visualising the data. For comfort analysis the R-package comf is recommended[12]. For further analyses, it needs to be considered, that top window and blind states were either changed through the BMS or manually by occupants. The algorithm of automatic controls of top windows and blinds is unknown. The authors assume that it will be possible to identify automated and manual controls by means of statistical analyses. Window state and blind status changes were recorded by the BMS and are available with their original time stamp. Blind events are all changes, i.e. also changes of blind position e.g. between 20 and 80% closing. Note that the official monitoring period by the original research team ended in October 2006. After that, data was still automatically received, but the status of sensors not checked anymore. Therefore, the number of sensors having failures and not providing data continuously increases, which needs to be considered when using data points after 2006.
Measurement(s)Ventilation • Occupancy • humidity • temperature of air • carbon dioxide
Technology Type(s)Carbon Dioxide Monitor Device • sensor • Temperature Sensor Device • Electrically Open Reed Device
Factor Type(s)indoor environment
Sample Characteristic - OrganismHomo sapiens
Sample Characteristic - Environmentoffice building
Sample Characteristic - LocationGermany
  4 in total

1.  A Global Building Occupant Behavior Database.

Authors:  Bing Dong; Yapan Liu; Wei Mu; Zixin Jiang; Pratik Pandey; Tianzhen Hong; Bjarne Olesen; Thomas Lawrence; Zheng O'Neil; Clinton Andrews; Elie Azar; Karol Bandurski; Ronita Bardhan; Mateus Bavaresco; Christiane Berger; Jane Burry; Salvatore Carlucci; Karin Chvatal; Marilena De Simone; Silvia Erba; Nan Gao; Lindsay T Graham; Camila Grassi; Rishee Jain; Sanjay Kumar; Mikkel Kjærgaard; Sepideh Korsavi; Jared Langevin; Zhengrong Li; Aleksandra Lipczynska; Ardeshir Mahdavi; Jeetika Malik; Max Marschall; Zoltan Nagy; Leticia Neves; William O'Brien; Song Pan; June Young Park; Ilaria Pigliautile; Cristina Piselli; Anna Laura Pisello; Hamed Nabizadeh Rafsanjani; Ricardo Forgiarini Rupp; Flora Salim; Stefano Schiavon; Jens Schwee; Andrew Sonta; Marianne Touchie; Andreas Wagner; Sinead Walsh; Zhe Wang; David M Webber; Da Yan; Paolo Zangheri; Jingsi Zhang; Xiang Zhou; Xin Zhou
Journal:  Sci Data       Date:  2022-06-28       Impact factor: 8.501

2.  CU-BEMS, smart building electricity consumption and indoor environmental sensor datasets.

Authors:  Manisa Pipattanasomporn; Gopal Chitalia; Jitkomut Songsiri; Chaodit Aswakul; Wanchalerm Pora; Surapong Suwankawin; Kulyos Audomvongseree; Naebboon Hoonchareon
Journal:  Sci Data       Date:  2020-07-20       Impact factor: 6.444

3.  A measured energy use, solar production, and building air leakage dataset for a zero energy commercial building.

Authors:  Philip Agee; Leila Nikdel; Sydney Roberts
Journal:  Sci Data       Date:  2021-11-23       Impact factor: 6.444

4.  The Building Data Genome Project 2, energy meter data from the ASHRAE Great Energy Predictor III competition.

Authors:  Clayton Miller; Anjukan Kathirgamanathan; Bianca Picchetti; Pandarasamy Arjunan; June Young Park; Zoltan Nagy; Paul Raftery; Brodie W Hobson; Zixiao Shi; Forrest Meggers
Journal:  Sci Data       Date:  2020-10-27       Impact factor: 6.444

  4 in total

北京卡尤迪生物科技股份有限公司 © 2022-2023.