| Literature DB >> 31601042 |
Manuel Pinto1, João Lanzinha2, João Viegas3, Catarina Infante4, Tiago Freire5.
Abstract
Assessments of Indoor Environment Quality (IEQ) present a very significant challenge when analyses are undertaken mainly in buildings that include a particularly sensitive and vulnerable population, such as elderly people. In order to maintain an indoor environment that is adequate for occupants, it is necessary to comply with a set of requirements (for TVOC, the Portuguese threshold values) regarding concentrations of airborne pollutants and hygrothermal comfort conditions. This paper studies IEQ in compartments in 3 buildings in two cities in central Portugal, Viseu and Covilhã, which hold elderly care centers. The following environmental parameters were continuously recorded: air temperature, relative humidity, concentration of carbon dioxide, formaldehyde, and total volatile organic compounds and ventilation rates. An analysis of the obtained results was performed, taking recommended guidelines and threshold values into account, thus making it possible to evaluate the IEQ conditions and hygrothermal comfort in the selected indoor spaces. On the basis of the conclusions reached and the observed problems of hygrothermal comfort and indoor pollutants in the indoor spaces, a number of recommendations are proposed, specifically in terms of climate control, ventilation, and maintenance, in order to obtain an overall improvement of IEQ.Entities:
Keywords: Elderly Care Centers (ECC); Indoor Air Quality (IAQ); Indoor Environment Quality (IEQ)
Mesh:
Substances:
Year: 2019 PMID: 31601042 PMCID: PMC6843510 DOI: 10.3390/ijerph16203801
Source DB: PubMed Journal: Int J Environ Res Public Health ISSN: 1660-4601 Impact factor: 3.390
Figure 1Map of Portugal showing the location of Viseu and Covilhã.
Viseu: physical characterization of the buildings and some of the studied compartments.
| Buildings | Rooms | ||||||
|---|---|---|---|---|---|---|---|
| Year of Construction | Climate Control/Heating System | Ventilation System | Designation | Predominant Orientation | Area [m2] | Usual Maximum Occupancy/No. of Residents | |
| ECC 1 a | 1994 | Intermittent heating with water radiators | NV | Room 1 | NW | 20.58 | 1 |
| Room 2 | SE | 20.58 | 2 | ||||
| Room 3 | NW | 20.58 | 2 | ||||
| Living room | SE and SW | 257.32 | 25 | ||||
| ECC 2 b | 1869 | Intermittent heating with water radiators | NV | Room 1 | E and NE | 24.61 | 3 |
| Room 2 | W | 22.79 | 3 | ||||
| Living room 1 | W | 39.76 | 25 | ||||
| Living room 2 c | W | 39.76 | 25 | ||||
Notes: a Cleaning method: daily with aqueous solution; opening of windows during cleaning (unsystematic); b Cleaning method: daily with aqueous solution; opening of windows during cleaning (unsystematic), outer walls uninsulated; c Also serves as dining hall; the natural ventilation system (NV) is due to the natural air permeability of the envelope. There is not a properly designed, natural ventilation system.
Viseu: interior cladding, windows, and solar protection of the various compartments.
| Buildings | Compartments | Flooring | Walls | Ceiling | Solar Protection | Windows | |
|---|---|---|---|---|---|---|---|
| Interior | Exterior | ||||||
| ECC 1 | Room 1 | Wooden parquet | Plastered | Plastered | Blackout curtains | Blinds | Aluminum without thermal brake; side hung windows; double glazing |
| Room 2 | |||||||
| Room 3 | |||||||
| Living room | Ceramic tile | Vertical blinds with fabric slats | None | Aluminum without thermal brake; sliding windows; double glazing | |||
| ECC 2 | Room 1 | Vinyl | Plastered | Plastered | Blackout curtains + semi-opaque curtains | None | Aluminum without thermal brake; side hung windows; double glazing |
| Room 2 | |||||||
| Living room 1 | |||||||
| Living room 2 | Blackout fabric roller blinds | ||||||
Covilhã: physical characterization of the studied compartments.
| Building | Compartments | ||||||
|---|---|---|---|---|---|---|---|
| Year of Construction | Climate Control/Heating System | Ventilation System | Designation | Predominant Orientation | Area [m2] | Usual Maximum Occupancy/No. of Residents | |
| ECC 3 | 2002 | Intermittent heating with water radiators; HVAC in living room and dining hall | RR in the living room and dining hall: MV-intermittent extraction | Living room | E | 134.00 | 25 |
| Dining hall | E | 134.00 | 50 | ||||
| RR of the rooms: NV-opening of windows | Triple room | SE | 33.92 | 3 | |||
Note: Cleaning method—daily with aqueous solution; opening window while cleaning.
Covilhã: interior cladding, windows, and solar protection in the various compartments.
| Solar Protection | |||||||
|---|---|---|---|---|---|---|---|
| Building | Compartments | Flooring | Walls | Ceiling | Interior | Exterior | Windows |
| ECC 3 | Room | Vinyl and ceramic tile | Ceramic tile | Plasterboard | Slightly transparent curtains | Blinds | Aluminum without thermal brake; sliding windows; double glazing |
| Living room/dining hall | Vinyl | Semi-opaque fabric roller blinds | None | ||||
Parameters measured and reference concentrations.
| Parameters | Protection Threshold in New Buildings | Margin of Tolerance b ( | Protection Threshold b | |||
|---|---|---|---|---|---|---|
| [mg/m3] | [ppmv] | [%] | [mg/m3] | [ppmv] | ||
| Physico-chemical pollutants | TVOC [ | 0.6 | 0.26 a | 100 | 1.2 | 0.52 a |
| CH2O [ | 0.1 | 0.08 | ||||
| CO2 [ | 2250 | 1250 | 30 | 2925 | 1625 | |
| Recommended/regulated level | ||||||
| Hygrothermal comfort | 20–25 °C | |||||
| 30–70% | ||||||
Notes: a Value obtained for the molar mass of isobutylene [24]; b Margin of tolerance and protection threshold in existing buildings and new buildings without mechanical ventilation systems; for a mean of 8 h; c MT is the value added to “Protection threshold in new buildings” to get “Protection threshold in existing buildings and new buildings without mechanical ventilation”, e.g., for TVOC: 0.6 mg/m3 × 100% = 1.2 mg/m3.
Viseu: parameters, technical characteristics of the equipment used, and conditions of measurement.
| Parameters | Instrument | Accuracy | Measurement Range | Duration of Measurement | Maximum Measurement Period a |
|---|---|---|---|---|---|
| Telaire 7001 with data logger U12-013 coupled to record data | ±0.35 °C (0 to 50 °C); | −20 to70 °C; | 1 min | 4 days | |
|
| Data logger U12-012 | ±0.35 °C (0 to 50 °C); | −20 to 70 °C; | 1 min | 4 days |
| Fluke 975 AirMeter | ±0.9 °C (40 to 60 °C); | −20 to 60 °C; | 1 min | 4 days | |
| TVOC | PhoCheck Tiger (PID) | ±5% of the display reading ± one digit | 1 ppb to 20,000 ppm | 30 s | 10 h |
Note: a: During an experimental campaign, there are several measurement periods (e.g., depending on the equipment’s memory capacity or the experimental conditions); the “Maximum measurement period” is the longest measurement period.
Minimum number of measurement points per compartment.
| Building | Compartment | Area | Volume | Minimum Number of Measuring Points | Number of Measured Points |
|---|---|---|---|---|---|
| ECC 3 | Living room | 134.00 | 375.2 | 2 | 3 |
| Canteen | 134.00 | 375.2 | 2 | 3 | |
| Triple room | 33.92 | 95.0 | 1 | 1 |
Covilhã: parameters, technical characteristics of the equipment used, and conditions of measurement.
| Parameters | Instruments | Accuracy | Measuring Range | Measuring Interval a | Measuring Period b |
|---|---|---|---|---|---|
| CH2O | Formaldemeter htV-M | ±10% | 0–10 ppm | Punctual a | 3 measurements spaced every 5 min |
| CO2 | TSI Velocicalc 9565-P | ±3% or 50 ppm, | 0–5000 ppm | 15 s | 3 measurements 5 min each |
| TVOC | TSI Velocicalc 9565-P | ±20% | 0.01–20 ppm, isobutylene | 15 s | 3 measurements 5 min each |
|
| Extech RH520 | ±1.0 °C; | –28–60 °C; | 1 min | 15 to 30 days |
Notes: a “Measuring interval” is the time between two successive measurements. The formaldehyde measuring interval spot (punctual) is an isolated (instantaneous) measurement; b “Measuring period” is the set of all “Measuring intervals”.
Statistical analysis of the pollutants recorded in ECC 1 compartments: 2nd trial (21 to 25 March).
| CO2 | TVOC | |||||
|---|---|---|---|---|---|---|
| Compartment | Max | Maximum of 8 h Means | Max | Maximum of 8 h Means ( | ||
| Room 1 | 1272 | 78 ± 83 | 888 | 0.86 | 0.05 ± 0.06 | 0.05 |
| Room 2 | 1343 | 710 ± 101 | 840 | 2.60 | 0.20 ± 0.25 | 0.24 |
| Room 3 | 1324 | 705 ± 245 | 850 | 0.32 | 0.07 ± 0.06 | 0.08 |
| Living room | 2538 | 1562 ± 335 | 1861 | 0.08 | 0.04 ± 0.02 | 0.04 |
Notes: (1) The measurements were continuous in the rooms, while in the living room, the measurement refers to the normal period of occupancy: from 7.30 a.m. to 7.30 p.m.; (2) The mean concentration of CO2 and TVOC were calculated without taking into account any errors (e.g., external or equipment); (3) “Maximum of 8 h means” is the maximum value that occurs in sequentially-calculated 8 h means. “Maximum of 8 h means” occurs during “Maximum measurement period” (See Table 6). Approximately 5500 arithmetic means were calculated.
Figure 2Recording of CO2 in room 1 and the living room of ECC 1: 2nd trial (21 to 25 March).
Statistical analysis of the hygrothermal parameters recorded in compartments of ECC 2: 1st trial (4 to 8 January).
| Δ | ||||||||
|---|---|---|---|---|---|---|---|---|
| Compartment | Perc ≤ 20 °C | Perc ≥ 25 °C | Perc ≤ 30% | Perc ≥ 70% | ||||
| Room 1 | 19.6 ± 0.9 | 64 | 0 | 73 ± 1 | 0 | 99 | 9.9 ± 2.6 | 9.7 |
| Room 2 | 19.9 ± 0.8 | 55 | 0 | 70 ± 2 | 0 | 51 | 10.0 | |
| Room 3 | 20.4 ± 0.8 | 31 | 0 | 68 ± 2 | 0 | 21 | 10.5 | |
| Room 4 | 19.5 ± 0.8 | 74 | 0 | 69 ± 3 | 0 | 49 | 9.6 | |
| Room 5 | 19.7 ± 0.7 | 63 | 0 | 69 ± 3 | 0 | 46 | 9.8 | |
| Living room 1 | 24.4 ± 0.3 | 0 | 3 | 52 ± 4 | 0 | 0 | 10.1 ± 2.5 | 14.3 |
| Living room 2 | 23.1 ± 0.8 | 0 | 0 | 59 ± 2 | 0 | 0 | 13.0 | |
| Living room 3 | 22.4 ± 0.5 | 0 | 0 | 57 ± 5 | 0 | 0 | 12.3 | |
Notes: (1) The measurements were continuous in the rooms, while in the living room, the measurement refers to the normal period of occupancy: from 7.30 a.m. to 7.30 p.m.; (2) ΔT is the difference between the means of Tint and Text; (3) Perc is “Percentage of time that exceeds a certain value”; see Nomenclature.
Figure 3Assessment of thermal comfort by the adaptive method of the LNEC in ECC 2: 1st trial.
Ventilation rates of living rooms 1 and 2 in ECC 2: 1st trial.
| Compartment | ACHav | Volume | Maximum Usual Occupancy—Number of Residents | ACHRECS | |
|---|---|---|---|---|---|
| Living room 1 | 0.48 | 24 | 117.69 | 25 | 5.10 |
| Living room 2 | 0.39 | 24 | 71.97 | 20 | 6.67 |
Notes: a To determine mean ACH by the CO2 decay method, a total of 5 trials were used for living room 1 and 4 for living room 2; b Air flow rates were obtained in [19]; qRECS means “Air flow rate”, obtained in accordance with “Ordinance 353-A/2013” (see Nomenclature); c ACHRECS means “Air change rate“, obtained in accordance with “Ordinance 353-A/2013” (see Nomenclature).
Statistical data of the pollutants recorded in ECC 3 compartments: 1st trial (March).
| Compartment | CO2 | TVOC | CH2O | |
|---|---|---|---|---|
| ECC 3 | Living room | 889 | 0.25 | 0.07 |
| Dining hall | 694 a | 0.19 | 0.06 | |
| Triple room | 684 a | 0.33 | 0.13 |
Notes: a measurement obtained outside hours of use; b maximum value of 3 means of 5 min each.
Figure 4Interior temperature in ECC 3: 1st trial (10 to 16 February).
Statistical analysis of hygrothermal parameters recorded in compartments of ECC 3: 1st trial (February–March).
| Δ | |||||||||
|---|---|---|---|---|---|---|---|---|---|
| Compartment | Perc ≤ 20 °C | Perc ≥ 25 °C | Perc ≤ 30% | Perc ≥ 70% | |||||
| ECC 3 | Living room | 23.8 ± 1.2 | 7 | 16 | 44 ± 5 | 0 | 0 | 10.4 ± 4.9 | 13.4 |
| Dining hall | 22.7 ± 1.3 | 2 | 1 | 46 ± 5 | 0 | 0 | 7.4 ± 3.3 | 15.3 | |
| Triple room | 22.0 ± 2.3 | 26 | 11 | 47 ± 7 | 1 | 0 | 7.4 ± 3.3 | 14.6 | |
Statistical analysis of the pollutants recorded in ECC 3 compartments and calculation of ACH: 2nd trial (April–May).
| CO2 | ACHav | ACHRECS | TVOC | CH2O | ||||
|---|---|---|---|---|---|---|---|---|
| Compartment | Perc ≥ 1625 | Perc ≥ 0.52 |
| |||||
| ECC 3 | Living room | 723 ± 253 | 0.8 | 0.22 | 1.6 | 0.04 ± 0.09 | 6.7 | 0.09 |
| Triple room | 890 ± 335 | 0.0 | 0.81 | 0.5 | 0.17 ± 0.15 | 7.3 | 0.04 | |
Notes: (1) The measurements in the living room refer to the usual period of occupancy: 6.30 a.m. to 6.30 p.m.; (2) A total of 8 trials were conducted in the living room, and 5 in the triple room, to determine the mean ACH by the CO2 decay method.
Figure 5CO2 and TVOC in the triple room in ECC 3: 2nd trial (30 April to 7 May).
Figure 6CO2 and TVOC in the living room in ECC 3: 2nd trial (24 to 30 April).