Literature DB >> 31546981

Dissolved Gas Analysis Equipment for Online Monitoring of Transformer Oil: A Review.

Sergio Bustamante1, Mario Manana2, Alberto Arroyo3, Pablo Castro4, Alberto Laso5, Raquel Martinez6.   

Abstract

Power transformers are the most important assets of electric power substations. The reliability in the operation of electric power transmission and distribution is due to the correct operation and maintenance of power transformers. The parameters that are most used to assess the health status of power transformers are dissolved gas analysis (DGA), oil quality analysis (OQA) and content of furfuraldehydes (FFA) in oil. The parameter that currently allows for simple online monitoring in an energized transformer is the DGA. Although most of the DGA continues to be done in the laboratory, the trend is online DGA monitoring, since it allows for detection or diagnosis of the faults throughout the life of the power transformers. This study presents a review of the main DGA monitors, single- or multi-gas, their most important specifications, accuracy, repeatability and measurement range, the types of installation, valve or closed loop, and number of analogue inputs and outputs. This review shows the differences between the main existing DGA monitors and aims to help in the selection of the most suitable DGA monitoring approach according to the needs of each case.

Entities:  

Keywords:  dissolved gas analysis; power transformer; transformer maintenance; transformer oil

Year:  2019        PMID: 31546981      PMCID: PMC6806153          DOI: 10.3390/s19194057

Source DB:  PubMed          Journal:  Sensors (Basel)        ISSN: 1424-8220            Impact factor:   3.576


1. Introduction

The most important and expensive asset in power transmission and distribution networks is the power transformer, so there must have a well-defined maintenance strategy from commissioning to withdrawal to ensure an appropriate level of reliability throughout the operational life of the transformer. According to [1,2,3], different asset maintenance strategies coexist depending on the condition and available information of the components and subcomponents of the substation equipment, as seen in Figure 1. The current trend in maintenance strategies for substation assets is to maintain a predictive maintenance approach based on prognostics, understanding that the prognostic tools do not strictly assess the remaining operating time but can be used to assess the future degradation of an asset [1].
Figure 1

Interrelation of maintenance strategies [1].

In predictive maintenance strategies, the lifetime management of high-voltage substation equipment is pursued [1], with the aim to manage the risks of the assets of a substation. To perform lifetime management of the transformers, it is necessary to have all the possible data throughout the lifetime of the transformer, which can be obtained through condition-based maintenance and through online continuous monitoring technologies [1,4,5,6,7,8,9,10,11,12]. According to [13], the risk is defined as the “effect of the uncertainty in the objectives,” so risk management of the assets has the purpose to evaluate, create and protect the correct operation of assets throughout the lifetime. The risk of an asset is represented by the risk index. The risk index is a function of the probability of failure and the consequences of failure [1,5,6,14]. The probability of failure refers to the health index of an asset, while the failure consequence evaluates and defines the consequences of a failure event.

2. Health Index of the Power Transformer

The GB Distribution Network Operators (DNO) created a Network Asset Indices Methodology [14] that aims to create a common framework of definitions, principles and methodologies for calculating the health index (HI). This report is adopted by all GB DNO. From [14], it was observed that more parameters are used in calculating the transformer HI than for the HI calculation of any other asset; for this reason, it was necessary to establish an order of importance for the parameters that are used. All condition criteria that can be used to calculate the transformer HI [15] are shown in Table 1. Figure 2 aims to show the location of the parameters, which are measured for the HI calculation of the transformer.
Table 1

Parameters of the transformer health index [15].

ItemCondition CriteriaItemCondition Criteria
1DGA13Main Tank Corrosion
2Load History14Cooling Equipment
3Power Factor15Oil Tank Corrosion
4Infra-Red16Foundation
5Oil Quality17Grounding
6Overall Condition18Gaskets, Seals
7Furan or Age19Connectors
8Turns Ratio20Oil Leaks
9Leakage Reactance21Oil Level
10Winding Resistance22DGA of LTC
11Core-to-Ground23LTC Oil Quality
12Bushing Condition24Overall LTC Condition
Figure 2

Location of the parameters measured for the HI calculation of the transformer.

In a previous study [15,16,17,18,19,20,21,22,23,24,25,26,27,28,29,30,31], the parameters that were used in their equations or algorithms have different weights. These weight differences, equations and algorithms between studies are discussed in [32], and this review assumes that the subjective judgement of the weighting factor leads to different values of the final HI. Power transformers, mainly above 30–40 MVA, are custom designed machines [33], so for the HI calculation, it is necessary to take into account the differences of the transformers in the limits and weights that are applied in the equations and algorithms. Thus, the best way to calculate the transformer HI is to always know as many parameters as possible (Table 1); however, although all the parameters are important, they are often partially unknown, difficult to collect or difficult to automatically incorporate into computer programs. For example, the thermal images of the transformer cannot be included easily in computer programs for the calculation of the transformer HI. Because an expert is necessary to interpret the thermal images which makes the calculation of the transformer HI slower. Therefore, the most used and most important parameters for calculating the transformer HI are dissolved gas analysis (DGA), oil quality analysis (OQA) and the content of furfuraldehydes (FFA) in the oil. DGA: The DGA method measures the gas concentrations in oil that are formed by the insulation decomposition processes, which occur when the transformer has faults. Depending on the type of fault, different types of decomposition processes can occur. When electrical and thermal defects occur in the transformer oil, they degrade generating combustible gases, such as hydrogen (), ethylene (CH), acetylene (CH), methane (CH) and ethane (CH). When decomposition occurs in cellulosic insulation, the generated gases are carbon monoxide (CO) and carbon dioxide (CO), and these gases indicate a thermal fault. Depending on the gas concentration that is measured, the type of fault can be identified by using the interpretation method that was collected in [34,35]. OQA: The OQA consists of a combination of electrical, physical and chemical tests. The list of all the tests that can be performed on the transformer oil is shown in IEEE Std C57.106 [4]. The most important and common are the dielectric breakdown voltage (BDV), the water content, the power factor, the interfacial tension (IFT), acidity and colour. The results of these tests are used to prevent incipient failures and to evaluate the preventive maintenance processes, such as the replacement or recovery of transformer oil [36]. Even the use of these tests are different and have different weights when calculating the HI, depending on the study [15,16,17,18,19,20,21,22,23,24,25,26,27,28,29,30,31]. FFA: The content of FFA in the transformer oil indicates the decomposition processes of the cellulosic material that constitute the transformer solid insulation [37]. The furanic components remain adsorbed by the paper, while a small part is dissolved in the oil. Its presence in the oil is used to diagnose the equipment in service as a complementary information to the DGA. Although the content of FFA in the transformer oil is a very important parameter in the calculation of HI, there are no recommendations for the interpretation of the results in the standards, as indicated by [24,28,38,39], so in each of the studies [15,16,17,19,20,22,23,26,30] a different limit value is taken in the HI calculation.

3. Dissolved Gas-In-Oil Analysis

Given the most important parameters in calculating the transformer HI defined above, the parameter that currently allows simple online monitoring of an energized transformer is the DGA [5,6,7,8,40]. DGA can be applied to various types of insulation oil used to fill the transformer [34,35,41,42,43,44]. Aging, thermal properties of each oil as well as the methods for the faults identification in the transformer oil are different depending on the oil used to fill the transformer. This review focuses on transformers filled with mineral oil and DGA equipment for online monitoring that measure the gas concentration in this type of oil. Accurate online DGA monitoring makes it possible to detect or diagnose, almost instantaneously, any incipient failure that occurs in the liquid or solid insulation of the transformer, avoiding a major failure. The use of gas concentrations limits and the methods for faults identification defined in the standards [34,35] allow for the detection and identification of early failures. The gases that best detect an incipient fault are hydrogen and carbon monoxide. According to the gas generation based on temperature [45] and the key gas method (KGM) [34], as seen in Figure 3 and Figure 4.
Figure 3

Gas generation based on temperature (Not to scale) [45].

Figure 4

Fault type by the key gas method [34].

Hydrogen is present, in higher or lesser amounts, in all the electrical faults and thermal faults that occur in the oil. Figure 3 shows the approximate generation of combustible gases based on temperature. The band on the left shows the approximate proportions of gases that are generated under partial discharge conditions; as shown, the amount of hydrogen is much greater than the rest of the gases. From the gas generation chart, it can be observed how hydrogen is present in all temperatures, from 150 to >800 , while the rest of the gases, such as ethylene or acetylene, need high temperatures, such as from 350 to 500 , respectively, to be generated; or in very high temperatures, gases such as methane and ethane are not generated. Carbon monoxide is produced when the solid insulation is decomposed due to thermal faults according to KGM (Figure 4). Therefore, a monitoring process aimed at detecting incipient faults in the transformer should at least measure the concentrations of hydrogen and carbon monoxide. As seen below, all DGA monitors measure oil moisture, so the measurement of the carbon monoxide concentration is not essential, since the degradation of the solid insulation is indicated by the increase of oil moisture. The measurement of these three concentrations (hydrogen, carbon monoxide and moisture) would allow a basic initial diagnosis, by differentiating between thermal and electrical faults or leaks into oil, according to Table 2.
Table 2

Initial fault identification chart [46].

FaultGas Generated
COH2H2O
Cellulose agingx x
Mineral oil decomposition x
Leaks into oil x
Thermal decomposition of cellulosexx
Overheated transformer corexx
Thermal faults in oil (150 to 300 C) x
Thermal faults in oil 300 to 700 C) x
Thermal faults in oil (> 700 C) x
Partial discharge x
Arcing x
There are many methods for the faults identification in the transformer insulation [34,35,47], in Table 3 the main characteristics of the most used methods are summarized.
Table 3

Comparison between fault identification methods [34,35,47].

MethodDescriptionFault Identification and Normal AgingGas Used
Key Gas Method(KGM)Uses individual gasconcentrations toidentify the faultPD, arcing, overheated oil,overheated celluloseCO, H2,C2H2, C2H4
Doernenburg RatioMethod (DRM)Uses four gasconcentration ratios:CH4H2,C2H2C2H4,C2H2CH4,C2H6C2H2Thermal decomposition,PD, arcingH2, C2H2, CH4,C2H6, C2H4
Rogers RatioMethod (RRM)Uses three gasconcentration ratios:CH4H2,C2H2C2H4,C2H4C2H6Normal aging, PD, arcing,low temperature fault,thermal fault <700 C,thermal fault >700 CH2, C2H2, CH4,C2H6, C2H4
IEC RatioMethod (IRM)Uses three gasconcentration ratios:CH4H2,C2H2C2H4,C2H4C2H6PD, low energy discharge,high energy discharge,thermal faults <300 C,between 300 and 700 C,and >700 CH2, C2H2, CH4,C2H6, C2H4
Duval TriangleMethod (DTM)Uses three gasescorresponding to theincreasing energycontent or temperatureof the faultsPD, low energy discharge,high energy discharge,thermal faults <300 C,between 300 and 700 C,and >700 CC2H2, CH4,C2H4
Duval PentagonMethod (DPM)Uses five gasescorresponding to theincreasing energycontent or temperatureof the faultsNormal aging, PD,low energy discharge,high energy discharge,thermal faults <300 C,between 300 and 700 C,and >700 CH2, C2H2, CH4,C2H6, C2H4
Several studies [48,49,50,51,52,53,54,55,56] indicate that the best method for the faults identification in the transformer insulation is the Duval triangle method (DTM).The Duval pentagon method (DPM) was created to improve DTM results. Several recent studies [48,49] indicate that the DPM success rate improves those of the DTM, since the DPM allows to identify the normal aging of the transformer insulation. Although the DPM is shown as the best method of identifying faults, it should be noted that it is a fairly new method that should be studied further to improve its validity. So the DTM is the method considered as the best and most established to diagnose faults in the transformer insulation. The DTM, as seen in Figure 5, uses the concentration ratio of three combustible gases (acetylene, ethylene and methane) to identify the fault. The concentration ratios of the three gases are calculated as where x, y and z are gas concentrations in ppm of acetylene, ethylene and methane, respectively.
Figure 5

Duval Triangle and list of faults detectable by DGA [37].

4. DGA Monitors

Online gas-in-oil monitors measure the gas concentrations in the transformer oil and detect or identify transformer faults. CIGRE made a report on gas monitors for oil-filled electrical equipment [57] in which a list of the main monitors available in 2007 and the most important specifications were shown. Table 4 shows the list of online gas-in-oil monitors and the main specifications that were analysed in this study. These monitors measure up to nine gas concentrations (hydrogen, ethylene, acetylene, methane, ethane, carbon monoxide, carbon dioxide, oxygen, nitrogen, propane or propene) from a single gas concentration (hydrogen). The amount of gas concentrations that this equipment can measure determines their functionality.
Table 4

List of manufacturers and gas-in-oil monitors.

ManufacturerEquipmentMeasurement TechnologyGas ExtractionConsumablesAutomatic CalibrationInstallation
Morgan SchafferCalisto 2 [58]TCDPTFE 2 V
Calisto 5 [59]GCPTFECalibration andcarrier gasesEvery24 hours2 V
Calisto 9 [60]GCPTFECalibration andcarrier gasesEvery24 hours2 V
LumaSenseSmartDGAGuard [61]NDIR + FCMembraneH2 sensorAfter sensorreplacement1 V or 2 V
SmartDGAGuide [62]NDIR + FCMembraneH2 and O2sensorAfter sensorreplacement1 V or 2 V
GEMinitrans [63]PASHeadspace 2 V
Hydran 201Ti [64]FCMembrane 1 V
Hydran M2-X [65]FCMembraneH2 sensor 1 V
Taptrans [66]PASHeadspace 2 V
Transfix [67]PASHeadspace 2 V
Multitrans [68]PASHeadspace 2 V
DGA 900 [69]PASHeadspace 2 V
VaisalaMHT 410 [70]ICHeadspace 1 V
OPT 100 [71]IRHeadspace 2 V
ABBCoreSense [72]ICHeadspace 1 V
CoreSense M10 [73]IC + FTIRHeadspace 1 V
QualitrolDGA 150 [74]ICHeadspace 1 V
TM1 [75]ICHeadspace 1 V
TM3 [76]GCMembraneCalibration andcarrier gasesEvery3 days2 V
TM8 [77]GCMembraneCalibration andcarrier gasesEvery3 days2 V
MTEHydrocal 1003 [78]Micro-electronicsensor +ElectrochemicalcellMembrane 1 V
Hydrocal1004 GenX [79]Micro-electronicsensor + NIRMembrane 1 V
Hydrocal 1005 [78]Micro-electronicsensor + NIRMembrane 1 V
Hydrocal 1008 [80]Micro-electronicsensor + NIRMembrane 1 V
Hydrocal 1009 [80]Micro-electronicsensor + NIRMembrane 1 V
SIEMENSSITRAM H2Guard [81]ICHeadspace 1 V
SITRAMMultisense 5 [82]Micro-electronicsensor + NIRHeadspace 1 V
SITRAMMultisense 9 [83]Micro-electronicsensor + NIRHeadspace 1 V
CAMLINTOTUS G5 [84]IR 2 V
TOTUS G9 [85]PAS 2 V

TCD = Thermal conductivity detector; GC = Gas chromatography; NDIR = Non dispersive infrared; FC = Fuel cell; PAS = Photoacoustic Spectroscopy; IC = Solid-state sensor; NIR = Near infrared; IR = Infrared; FTIR = Fourier-transform infrared; 1 V = Single valve installation; 2 V = Close loop installation; –: Not indicated by the manufacturer; Blank spaces indicate that monitors do not need consumables or calibration owing to the use or replacement of consumables.

The equipment that measures from one to two gas concentrations is a fault detection monitor, known as single-gas DGA. Normally, these monitors measure hydrogen and carbon monoxide concentrations, which are the gases that indicate thermal and electrical faults in the transformer oil and thermal faults in the solid insulation [34]. There are equipment that also measure acetylene, ethylene or carbon dioxide, in addition to measuring hydrogen and carbon monoxide; although these monitors measure more gas concentrations, they do not identify faults. The fault detection monitor is used to monitor abnormal gassing in the transformer oil. The equipment that measures nine gas concentrations is the fault diagnosis monitor, known as a multi-gas DGA. Using the values of gas concentrations and the methods defined in the standards [34,35], these monitors identify transformer faults. The fault diagnosis monitor is used to monitor the abnormal gassing in the transformer oil and diagnose faults. As shown in Table 4, each manufacturer of DGA monitors uses a different technology for the detection and diagnosis of dissolved gases in the online monitoring transformer oil. The main manufacturers use predominantly gas chromatography (GC), photoacoustic spectroscopy (PAS), solid-state (IC), thermal conductivity detector (TCD), non-dispersive infrared (NDIR), infrared (IR), near infrared (NIR), Fourier transform infrared (FTIR), fuel cell (FC), micro-electronic sensor or electrochemical cell [58,59,60,61,62,63,64,65,66,67,68,69,70,71,72,73,74,75,76,77,78,79,80,81,82,83,84,85]. Several studies [86,87,88,89,90,91] present a review of these gas sensor technologies for the detection of different gases.Table 5 shows the advantages and disadvantages collected in [86,87,88,89,90,91] of the gas detection methods of the DGA online monitoring equipment presented in Table 4.
Table 5

Advantages and disadvantages of gas detection technologies [86,87,88,89,90,91].

TechnologyAdvantagesDisadvantages
GCWide range of fault gasesHighest accuracy and repeatabilityLong time required to complete a testExpensiveFrequent calibrations neededAuxiliary (carrier) gas neededMaintenance cost
PASWide range of fault gasesCan detect/measure verylow (ppm and ppb) gasconcentrationsLow maintenanceResults are sensitive to the wavenumber range of the opticalfilters and their absorptioncharacteristicsAccuracy influencedby temperature,pressure, and vibrationLimited ability to measurehigh gas concentrationsInterfering gases can effectaccuracy
ICOperate under extremetemperatures,vibration, or incorrosive atmospheresLimited ability to detect verylow gas concentrations
TCDFast responseStableWide measuring rangeSimple constructionRobustSensitive to interfering gasesReaction due to heating wireHeating element reacts with gas
NDIRSimultaneous multi-gasmeasurementNo required calibrationsLow maintenanceFast gas measurement timeLimited ability to detect very lowgas concentrationsInterfering gases can effectaccuracy
IRUses only physical techniqueCan be used in inert atmospheresNot all gases have IR absorptionSequential monitoring is slower onmulti point analyzers and alsomore user expertise required
NIRSimultaneous multi-gasmeasurementNon-frequent calibrationsLow maintenanceLimited ability to measure highgas concentrationsInterfering gases can effectaccuracy
FTIRSimultaneous multi-gas measurementAccuracy influenced by moisture
FCSmall sizePeriodic replacementSingle gas measurement
Micro-electronic sensorSmall sizeSingle gas measurement
Electrochemical cellSmall sizeWorking at high temperature is possibleFrequent calibrations neededShort/limited life timeSingle gas measurementCross sensitivity to other gases
According to the report on gas-in-oil monitors published by CIGRE [57], most manufacturers use the gas extraction method based on the headspace principle [92,93,94]. In this study, all monitors use the gas extraction method based on the headspace principle by direct contact between the oil and a small gas phase above or through a membrane separating the two phases (membrane of semipermeable PTFE or another polymer), as shown in Table 4. The extraction of gases is performed under different conditions of pressure (atmospheric or under partial vacuum) and temperature (at oil temperature, at ambient temperature, or at a fixed temperature), with or without pumping the oil continuously on the monitor. Once the gas extraction is performed, each gas measurement technology [86,87,88,89,90,91,92] measures the gas concentrations present in the oil sample. Monitors that use GC measurement technology need carrier and calibration gases. Helium is used as a carrier gas to transport the sample gases that are extracted from the transformer oil. Gas chromatography monitors perform automatic calibration using on-board National Institute of Standards and Technology (NIST) traceable calibration gas. Table 4 shows the elapsed time between automatic calibrations, depending on the manufacturer. Monitors that use the fuel cell as a measurement technology need to replace the sensor every several years and perform sensor calibration every time the sensor is replaced.

4.1. Installation of The Monitor

The installation of the online gas-in-oil monitors is different depending on the type of sensor and transformer [95]. According to the manufacturers [58,59,60,61,62,63,64,65,66,67,68,69,70,71,72,73,74,75,76,77,78,79,80,81,82,83,84,85], the installation of the monitors is performed using one or two different valves of the transformer. Table 4 shows the type of installation used by each sensor that is analysed in this study, and Figure 6a shows the possible valve locations on a power transformer.
Figure 6

(a) Possible valve locations in a power transformer; and (b) installation schematic (Not to scale).

The installation of the monitor using a single valve is performed by mounting the monitor directly on the valve using a thread or a flange (Figure 6b). In this type of installation, the best place to install the monitor is the valve located in the straight section in the cooling loop outlet pipe (Figure 6a), because there is oil flow, which makes the sample representative. An alternative installation, if the previous one is not available, consists of using a valve far enough from the bottom to ensure adequate oil flow, like the fill valve (Figure 6a). The drain valve is the worst location to install the monitor because it is located in the bottom of the transformer, where there is no oil flow and there is a risk of oil sludge. The installation of the monitors using two valves consists of creating a closed loop in which the oil passes through the monitor (Figure 6b). One of the valves is the supply valve and the other is the return valve. As in the case of single valve installation, the supply valve must take oil where there is oil flow, and the valve that is located in the straight section in the radiator outlet pipe, the fill valve or a valve that is far enough from the bottom are good choices. The return valve can be the drain valve or an auxiliary valve whenever it is below the supply valve. Two types of installation (Figure 6b) have several differences, apart from the number of valves they use. In the installation of the monitor in a valve, the oil sample is taken from and returned to the same valve, and the sensor or sensors are in this area where there is only circulation of the oil inside the tank. Other monitors with the installation in a valve generate oil circulation in the valve area through the heating of a pipe inside the valve to obtain a better oil flow. Although the best and most representative oil flow is achieved by using an oil loop installation, in addition to the internal flow in the tank, new flow is added due to this loop, thus making the oil sample in the monitor as representative as possible.

4.2. Fault Detection Monitor (Single-Gas DGA)

Fault detection monitors send out warnings when the gas concentration exceeds a set limit, which is normally the limits of each gas used are those indicated by the IEEE [34] and IEC [35] standards, or are calculated using the methods or recommendations proposed in [41,96,97,98,99]. Table 6 shows the gas concentrations that were measured by the fault detection monitors; it also shows the monitors that measure the oil moisture.
Table 6

Parameters measured by fault detection monitors (as indicated by manufacturers).

EquipmentHydrogen (H2)Carbon Monoxide (CO)MoistureOther Gases
Calisto 2xxx
SmartDGA GuardxxxC2H2 and CO2
MinitransxxxC2H2
Hydran 201Tix
Hydran M2-Xx 1 x
MHT410x x
CoreSensex x
DGA 150x
Serveron TM1x optional
Hydrocal 1003xxx
Hydrocal1004 GenXxxxC2H2
Hydrocal 1005xxxC2H2 and C2H4
H2 Guardx
Multisense 5xxxC2H2 and C2H4

: Relative sensitivity (%).

Table 7, Table 8 and Table 9 show the range, accuracy and repeatability of the measurements of hydrogen, carbon monoxide and moisture concentrations by the fault detection monitors, respectively, according to the manufacturers [58,61,63,64,65,70,72,74,75,78,79,81,82].
Table 7

Hydrogen concentration measurement range, accuracy and repeatability of fault detection monitors (as indicated by manufacturers).

EquipmentMeasurement Range (ppm)AccuracyRepeatability
Calisto 22–50.000±2 ppm or ±5%±2 ppm or ±3%
SmartDGAGuard5–10.000±5 ppm or ±5%
Minitrans5–5.000±5 ppm or ±10%
Hydran 201Ti25-2.000±25 ppm or ±10%±10 ppm or ±5%
Hydran M2-X25–2.000±25 ppm or ±10%±10 ppm or ±5%
MHT4100–5.000±25 ppm or ±20%±15 ppm or ±10%
CoreSense0–5.000±25 ppm or ±20%
DGA 15050–5.000±25 ppm or ±20%±15 ppm or ±10%
Serveron TM120–10.000±20 ppm or ±15%±5 ppm or ±10%
Hydrocal 10030–2.000±25 ppm or ±15%
Hydrocal1004 GenX0–6.000±20 ppm or ±10%
Hydrocal 10050–2.000±25 ppm or ±15%
H2 Guard25–5.000±25 ppm or ±20%±15 ppm or ±10%
Multisense 50–2.000±LDL ppm or ±15%

–: Not indicated by the manufacturer.

Table 8

Carbon monoxide concentration measurement range and accuracy of fault detection monitors (as indicated by manufacturers).

EquipmentMeasurement Range (ppm)AccuracyRepeatability
Calisto 225–100.000±25 ppm or ±15%±25 ppm or ±10%
SmartDGA Guard10–10.000±10 ppm or ±5%
Minitrans10–50.000±10 ppm or ±10%
Hydran 201Ti
Hydran M2-X
MHT410
CoreSense
DGA 150
Serveron TM1
Hydrocal 10030–2.000±25 ppm or ±20%
Hydrocal 1004 GenX0–6.000±5 ppm or ±10%
Hydrocal 10050–2.000±25 ppm or ±20%
H2 Guard
Multisense 50–5.000±LDL ppm or ±5%

–: Not indicated by the manufacturer; Blank spaces indicate what the monitors do not measure.

Table 9

Moisture measurement range and accuracy of fault detection monitors (as indicated by manufacturers).

EquipmentMeasurement RangeAccuracyRepeatability
Calisto 22–100%±3 ppm or ±3%±2 ppm or ±2%
SmartDGA Guard1–99%±3 ppm or ±2%
Minitrans0–100%±2%
Hydran 201Ti
Hydran M2-X0–100%±2%±2%
MHT4100–100%±2%
CoreSense0–100%±2%
DGA 150
Serveron TM10–100%±5%
Hydrocal 10030–100%±3 ppm or ±3%
Hydrocal 1004 GenX0–100%±3 ppm or ±3%
Hydrocal 10050–100%±3 ppm or ±3%
H2 Guard
Multisense 50–100%±LDL ppm or ±3%

–: Not indicated by the manufacturer; Blank spaces indicate what the monitors do not measure.

The measurement range indicates the lower detection limit (LDL) and the upper detection limit (UDL) in parts per million (ppm) that the monitor measures. The LDL is the minimum gas concentration that the monitor is able to measure; cases in which the manufacturers indicate a lower measurement range equal to 0 ppm does not indicate that the LDL is 0 ppm, but measurements below the LDL will be considered to be 0 ppm. The LDL is the most important parameter in the measurement range, because it allows for the detection of changes at very low concentrations. The accuracy and repeatability are shown in ppm and in percentage (%); the highest value is always taken. The lower the ppm and the percentage of accuracy and repeatability and the lower the LDL ppm from Table 7, Table 8 and Table 9, improve fault detection monitoring [91]. In observing the moisture measurement values (Table 9), all fault detection monitors had similar specifications, with differences approximately 1 ppm or 1% in accuracy and 1–2% in the measurement range.

4.3. Fault Diagnosis Monitor (Multi-Gas DGA)

Fault diagnosis monitors, in addition to sending out warnings when the gas concentration exceeds a set limit, also diagnose the fault using the standards of IEEE [34] and IEC [35]. Table 10 shows the gases measured by the fault diagnosis monitors; it also shows the monitors that measure the oil moisture.
Table 10

Parameters measured by fault diagnosis monitors (as indicated by manufacturers).

Equipment5 Gases7 Gases9 GasesMoisture
Calisto 5x x
Calisto 9 xx
SmartDGA Guide xx
Taptrans xx
Transfix xx
Multitrans xx
DGA 900 xx
OPT100 x x
CoreSense M101 x
Serveron TM32 optional
Serveron TM8 xoptional
Hydrocal 1008 x x
Hydrocal 10093 x
Multisense 93 x
TOTUS G5x x
TOTUS G9 x x

5 gases: H, CO, CH, CH and CH; 7 gases: 5 gases + CH and CO; 9 gases: 7 gases + O and N; : 7 gases + CH and CH; : measures the gases used in DTM; : 8 gases (7 gases + O).

Table 11 shows the range, accuracy and repeatability of the gas concentration measurements by the fault diagnosis monitors according to the manufactures [59,60,62,66,67,68,69,71,73,76,77,80,83,84,85].
Table 11

Gas concentration and moisture measurements range, accuracy and repeatability of the fault diagnosis monitors (as indicated by the manufacturers).

EquipmentH2 Range (ppm)CO Range (ppm),CH4 Range (ppm),C2H2Range (ppm),C2H4Range (ppm),C2H6Range (ppm),CO2Range (ppm),O2 Range (ppm)N2 Range (ppm),C3H6Range (ppm),C3H8Range (ppm),Moisture Range,
Accuracy and RepeatabilityAccuracy and RepeatabilityAccuracy and RepeatabilityAccuracy and RepeatabilityAccuracy and RepeatabilityAccuracy and RepeatabilityAccuracy and RepeatabilityAccuracy and RepeatabilityAccuracy and RepeatabilityAccuracy and RepeatabilityAccuracy and RepeatabilityAccuracy and Repeatability
Calisto 50–20.000±0.5 ppm or ±5%±0.5 ppm or ±3%0–30.000±10 ppm or ±5%±10 ppm or ±3%0–100.000±0.2 ppm or ±5%±0.2 ppm or ±3%0–100.000±0.2 ppm or ±5%±0.2 ppm or ±3%0–200.000±0.2 ppm or ±5%±0.2 ppm or ±3% 2–100%±3 ppm or ±3%±2 ppm or ±2%
Calisto 90–20.000±0.5 ppm or ±5%±0.5 ppm or ±3%0–30.000±10 ppm or ±5%±10 ppm or ±3%0–100.000±0.2 ppm or ±5%±0.5 ppm or ±3%0–100.000±0.2 ppm or ±5%±0.5 ppm or ±3%0–200.000±0.2 ppm or ±5%±0.5 ppm or ±3%0–200.000±0.2 ppm or ±6%±0.5 ppm or ±4%0–100.000±15 ppm or ±5%±15 ppm or ±3%0–100.000±500 ppm or ±15%±500 ppm or ±10%0–150.000±2.000 ppm or ±15%±2.000 ppm or ±10% 2–100%±3 ppm or ±3%±2 ppm or ±2%
SmartDGA Guide5–10.000±5 ppm or ±5%10–10.000±10 ppm or ±5%2–50.000±2 ppm or ±5%0.5–10.000±0.5 ppm or ±5%2–50.000±2 ppm or ±5%2–20.000±2 ppm or ±5%10–20.000±10 ppm or ±5%500–50.000±500 ppm or ±5%5.000–100.000±5.000 ppm or ±5% 1–99%±3 ppm or ±2%
Taptrans5–5.000±5 ppm or ±5%2–50.000±2 ppm or ±5%2–50.000±2 ppm or ±5%0.5–50.000±0.5 ppm or ±5%2–50.000±2 ppm or ±5%2–50.000±2 ppm or ±5%20–50.000±20 ppm or ±5%100–50.000±10%10.000–100.000±15% 0–100%±3%
Transfix5–5.000±5 ppm or ±5%2–50.000±2 ppm or ±5%2–50.000±2 ppm or ±5%0.5–50.000±0.5 ppm or ±5%2–50.000±2 ppm or ±5%2–50.000±2 ppm or ±5%20–50.000±20 ppm or ±5%100–50.000±10%10.000–100.000±15% 0–100%±3%
Multitrans5–5.000±5 ppm or ±5%2–50.000±2 ppm or ±5%2—50.000±2 ppm or ±5%0.5-50.000±0.5 ppm or ±5%2–50.000±2 ppm or ±5%2–50.000±2 ppm or ±5%20–50.000±20 ppm or ±5%100–50.000±10%10.000–100.000±15% 0–100%±3%
DGA 9005–5.000±5 ppm or ±5%< 3%1–50.000±1 ppm or ±3%< 2%2–50.000±2 ppm or ±3%< 2%0.5–50.000±0.5 ppm or ±3%< 2%1–50.000±1 ppm or ±3%< 2%1–50.000±1 ppm or ±3%< 2%20–50.000±20 ppm or ±3%< 3%100–50.000±100 ppm or ±5%< 2%10.000–100.000±15% 0–100%±3%<3%
OPT1000–5.000±25 ppm or ±20%±15 ppm or ±10%0–10.000±10 ppm or ±10%±10 ppm or ±5%0–10.000±10 ppm or ±5%±10 ppm or ±5%0–5.000±1 ppm or ±10%±1 ppm or ±10%0–10.000±10 ppm or ±10%±10 ppm or ±5%0–10.000±10 ppm or ±10%±10 ppm or ±5%0–10.000±10 ppm or ±10%±10 ppm or ±5% 0–100%±2 ppm or ±10%
CoreSense M1025–5.000±25 ppm or ±20%2–5.000±2 ppm or ±5%1–10.000±1 ppm or ±5%0.5–10.000±0.5 ppm or ±5%2–10.000±2 ppm or ±5%2–10.000±2 ppm or ±6%5–20.000±5 ppm or ±5% 10–10.000±10 ppm or ±5%10–10.000±10 ppm or ±5%0–100%±3 ppm or ±2%
Serveron TM3 5–7.000±5 ppm or ±5%< 1%1–3.000±1 ppm or ±5%< 2%3–5.000±3 ppm or ±5%< 1% 0–100%±3%
Serveron TM83–3.000±3 ppm or ±5%< 2%5–10.000±5 ppm or ±5%< 2%5–7.000±5 ppm or ±5%< 1%1–3.000±1 ppm or ±5%< 2%3–5.000±3 ppm or ±5%< 1%5–5.000±5 ppm or ±5%< 1%5–30.000±5 ppm or ±5%< 1%30–25.000±30 ppm or ±5%< 1%5.000–100.000±5.000 ppm or ±5%< 20% 0–100%±3%
Hydrocal 10080–2.000±25 ppm or ±15%0–5.000±25 ppm or ±20%0–2.000±25 ppm or ±20%0–2.000±5 ppm or ±20%0–2.000±10 ppm or ±20%0–2.000±10 ppm or ±20%0–20.000±25 ppm or ±20% 0–100%±3 ppm or ±3%
Hydrocal 10090–10.000±25 ppm or ±15%0–10.000±25 ppm or ±20%0–5.000±25 ppm or ±20%0–10.000±5 ppm or ±20%0–10.000±10 ppm or ±20%0–10.000±15 ppm or ±20%0–20.000±25 ppm or ±20%0–50.000±1.000 ppm or ±10% 0–100%±3 ppm or ±3%
Multisense 90–10.000±LDL or ±5%0–10.000±LDL or ±5%0–5.000±LDL or ±5%0–10.000±LDL or ±5%0–10.000±LDL or ±5%0–10.000±LDL or ±5%0–20.000±LDL or ±5%0–50.000±LDL or ±10% 0–100%±LDL or ±3%
TOTUS G55–5.000±5 ppm or ±15%10–20.000±10 ppm or ±10%30–60.000±20 ppm or ±10%3–5.000±3 ppm or ±5%5–90.000±5 ppm or ±5% 0–100%
TOTUS G90–5.000±5 ppm or ±5%1–50.000±1 ppm or ±5%1-50.000±1 ppm or ±5%0.1–50.000±0.1 ppm or ±5%1–50.000±1 ppm or ±5%1–50.000±1 ppm or ±5%3–50.000±3 ppm or ±5%100–505.000±10%10.000–150.000±15% 0–100%

–: Not indicated by the manufacturer; Blank spaces indicate what the monitors do not measure.

As in the case of the fault detection monitors, accuracy and repeatability are different depending on the monitor and the manufacturer, and the accuracy and repeatability in the moisture measurement are very similar among monitors. Accuracy and repeatability are the main characteristics to be observed in the diagnosis and online monitoring of transformer oil to obtain reliable results.

4.4. Analogue Inputs and Outputs of DGA Monitors

As mentioned above, online monitoring of power transformers allows having an asset maintenance strategy oriented to predictive maintenance. Most gas-in-oil monitors have analogue inputs and outputs whereby different external sensors can be connected to monitor other asset conditions. These external sensors measure, among others, the ambient temperature, oil temperature, moisture-in-oil and loading conditions. All the monitors that have analogue outputs use DC current () in the 4–20 mA range for their analogue outputs. In the case of analogue inputs, most monitors also use the DC current in the 4–20 mA range, but there are several monitors that also use the AC current (), AC voltage () or DC voltage (), in the ranges of 4–20 mA + 20%, 0–80 V + 20% and 0–10 V + 20%, respectively. Table 12 shows the analogue inputs and outputs of the fault detection monitors and the fault diagnosis monitors.
Table 12

Analogue inputs and outputs of gas-in-oil monitors (as indicated by the manufacturers)

EquipmentAnalogue InputAnalogue Output
FaultdetectionmonitorCalisto 21(IDC) (oil temperature sensor) 3(IDC)
Smart DGA Guardxx
Minitrans1(IDC) (load sensor)x
Hydran 201Ti 1(IDC) x
Hydran M2-X 1(IDC) 1(IDC)
MHT410x 3(IDC)
CoreSense 3(IDC) 3(IDC)
DGA 150x 1(IDC)
Serveron TM1 2(IDC) 3(IDC)
Hydrocal 10034(IDC) + 4(IDC) or 4(VDC) 4(IDC)
Hydrocal 1004 GenXoptional 1optional 1
Hydrocal 1005optional: 4(IDC) + 6(IAC) or 6(VAC) 5(IDC)
H2 Guard 2(IDC) 3(IDC)
Multisense 5optional: 10(IDC) 5(IDC)
FaultdiagnosismonitorCalisto 5optional: 2(IDC)optional: 10(IDC)
Calisto 9optional: 2(IDC)optional: 10(IDC)
Smart DGA Guidexx
Taptransoptional 1 8(IDC)
Transfixoptional 1 8(IDC)
Multitransoptional 1 8(IDC)
DGA 900optional: 15(IDC)optional 1
OPT100xx
CoreSense M10 4(IDC) 8(IDC)
Serveron TM3 3(IDC) x
Serveron TM8 3(IDC) x
Hydrocal 1008optional: 4(IDC) + 6(IAC) or 6(VAC) 8(IDC)
Hydrocal 1009optional: 4(IDC) + 6(IAC) or 6(VAC) 9(IDC)
Multisense 9optional: 10(IDC) 10(IDC)
TOTUS G5 4(IDC) -
TOTUS G9--

x: The monitor does not have analogue inputs or outputs; 1: Not specified the number of analogue inputs or outputs; –: Not indicated by the manufacturer.

5. Conclusions

The dissolved gas analysis of the transformer oil is one of the most important parameters when evaluating the health status of a power transformer. Online DGA monitoring aims to support predictive maintenance of the power transformers by detecting incipient faults in the liquid or solid insulations. A review of DGA equipment for online monitoring of power transformers was performed in this study. The main monitors that were available on the date of writing of this study (2018) were presented. A classification of the types of existing DGA monitors was defined in this study of fault detection monitors and fault diagnosis monitors. Fault detection monitors measure the concentrations of hydrogen and carbon monoxide that are present in the transformer oil, so they only detect the fault, whereas fault diagnosis monitors measure the concentrations of five to nine gases, so they are able to diagnose the type of fault. Apart from the amount of gases they measure, DGA monitors have differences in accuracy, repeatability and measurement range. DGA monitors have two types of installation, in a valve or in a closed loop. Finally, each monitor has a different number of analogue inputs and outputs to connect to other sensors and to obtain better monitoring of the asset. Another point to consider in the selection of a fault diagnosis monitor is the method to be used for fault identification. Depending on the number of gases required for faults identification of the method to be used, the selection of the monitor is limited. The comparison between the main methods for the faults identification, type of faults identifiable and gas concentrations required by each method was shown in this review. This review aims to help the selection of DGA monitors, fault detection or diagnosis monitors, the required specifications depending on the importance of the transformer, the number of valves needed by the monitor and the number of valves in the transformer and the need to connect other sensors to the monitor through analogue inputs, or to connect the analogue outputs of the monitor to other equipment.
  2 in total

1.  Influence of Oil Status on Membrane-Based Gas-Oil Separation in DGA.

Authors:  Tunan Chen; Kang Li; Zhenghai Liao; Xiongjie Xie; Guoqiang Zhang
Journal:  Sensors (Basel)       Date:  2022-05-10       Impact factor: 3.847

2.  Wavelet-Like Transform to Optimize the Order of an Autoregressive Neural Network Model to Predict the Dissolved Gas Concentration in Power Transformer Oil from Sensor Data.

Authors:  Francisco Elânio Bezerra; Fernando André Zemuner Garcia; Silvio Ikuyo Nabeta; Gilberto Francisco Martha de Souza; Ivan Eduardo Chabu; Josemir Coelho Santos; Shigueru Nagao Junior; Fabio Henrique Pereira
Journal:  Sensors (Basel)       Date:  2020-05-11       Impact factor: 3.576

  2 in total

北京卡尤迪生物科技股份有限公司 © 2022-2023.