Małgorzata Sowiak1, Anna Kozajda2, Karolina Jeżak1, Irena Szadkowska-Stańczyk1.
Abstract
The aim of this study was to establish whether the air-conditioning system in buses constitutes an additional source of indoor air contamination with fungi, and whether or not the fungi concentration depends on the period from the last disinfection of the system, combined with replacement of the cabin dust particle filter. The air samples to fungi analysis using impact method were taken in 30 buses (20 with an air-conditioning system, ACS; 10 with a ventilation system, VS) in two series: 1 and 22 weeks after cabin filter replacement and disinfection of the air-conditioning system. During one test in each bus were taken two samples: before the air-conditioning or ventilation system switched on and 6 min after operating of these systems. The atmospheric air was the external background (EB). After 1 week of use of the system, the fungi concentrations before starting of the ACS and VS system were 527.8 and 1053.0 cfu/m3, respectively, and after 22 weeks the concentrations were 351.9 and 1069.6 cfu/m3, respectively. While in the sample after 6 min of ACS and VS system operating, the fungi concentration after 1 week of use was 127.6 and 233.7 cfu/m3, respectively, and after 22 weeks it was 113.3 and 324.9 cfu/m3, respectively. Results do not provide strong evidence that air-conditioning system is an additional source of indoor air contamination with fungi. A longer operation of the system promoted increase of fungi concentration in air-conditioned buses only.Entities:
Keywords: Air-condition system; Buses; Cars; Drivers; Fungi; Mold; Occupational exposure; Ventilation system
Mesh:
Substances:
Year: 2017 PMID: 29209965 PMCID: PMC5846988 DOI: 10.1007/s11356-017-0830-4
Source DB: PubMed Journal: Environ Sci Pollut Res Int ISSN: 0944-1344 Impact factor: 4.223
Microclimatic parameters in the indoor air in buses, air in buses with and without air-conditioning system, and in outdoor air (external background) regarding to period of the operation of the system (N = 30)
| Type of buses | Period of system operationa (weeks) | Temperature (°C) | Relative humidity (%) | ||
|---|---|---|---|---|---|
| P1 | EB | P1 | EB | ||
| AM (SD) MIN-MAX | AM (SD) MIN-MAX | AM (SD) MIN-MAX | AM (SD) MIN-MAX | ||
| With air-conditioning system ( | 1 | 21.0 (5.6) | 21.1 (8.2) | 61.8 (16.6) | 57.8 (25.7) |
| 22 | 17.6 (3.3) | 18.2 (2.3) | 60.8 (8.8) | 55.0 (10.0) | |
| Without air-conditioning system ( | 1 | 22.5 (6.4) | 24.7 (7.6) | 55.1 (7.0) | 42.4 (5.9) |
| 22 | 14.5 (1.5) | 11.7b | 74.1 (6.6) | 75.5b | |
N samples number, P1 indoor air samples befor turning on air-conditioning system/ventilation system, EB external background (atmospheric air), M arithmetic mean, SD standard deviation, MIN minimum value, MAX maximum value
aFor the buses with air-conditioning system: period of operation form the last filter replacement and disinfection; for the buses without air-conditioning system: period of operation from the last filter replacement
bSingle sample microclimatic parameter in the outdoor air (the average value from the day of sampling)
Concentration of total molds in the indoor air in buses with and without air-conditioning system and in the outdoor air (external background) regarding to period of the operation of the system (N = 30)
| Type of buses | Period of system operation (weeks) | Total molds (cfu/m3) | ||
|---|---|---|---|---|
| P1 | P2 | EB | ||
| GM (GSD) | GM (GSD) | GM (GSD) | ||
| With air-conditioning system ( | 1 | 527.8 (1.8) | 127.6 (3.0) | 1229.5 (1.6) |
| 22 | 351.9 (2.2) | 113.3 (1.9) | 732.5 (1.4) | |
| Without air-conditioning system ( | 1 | 1053.0 (1.3) | 233.7 (2.1) | 2579.8 (1.0) |
| 22 | 1069.6 (1.5) | 324.9 (1.5) | 2121.0b | |
N samples number, P1 indoor air samples before turning on air-conditioning system/ventilation system, P2 indoor air samples after 6 min operation of the air-conditioning system/ventilation system, EB external background (atmospheric air), GM geometric mean, GSD geometric standard deviation, MIN minimum value, MAX maximum value
aFor the buses with air-conditioning system: period of operation form the last filter replacement and disinfection; for the buses without air-conditioning system: period of operation from the last filter replacement
bSingle sample microclimatic parameter in the outdoor air (the average value from the day of sampling)
Percentage ratio (P2/P1) indicated changes in concentrations of total molds in the indoor air of buses with and without air-conditioning system after 6 min operation of the air-conditioning system relative to the state before turning on regarding to the period of operation both systems (N = 30)
| Type of buses | P2/P1 (%) |
| |
|---|---|---|---|
| Period of system operationa (weeks) | |||
| 1 | 22 | ||
| GM | GM | ||
| With air-conditioning system ( | 24.2 | 32.2 | > 0.05 |
| Without air-conditioning system ( | 22.2 | 30.4 | > 0.05 |
|
| > 0.05 | > 0.05 | |
N samples number, P1 indoor air samples before turning on air-conditioning system/ventilation system, P2 indoor air samples after a 6-min operation of the air-conditioning system/ventilation system, EB external background (atmospheric air), GM geometric mean, GSD geometric standard deviation, MIN minimum value, MAX maximum value
p level of statistical significance (p < 0.05)
aFor the buses with air-conditioning system: period of operation form the last filter replacement and disinfection; for the buses without air-conditioning system: period of operation from the last filter replacement
Concentration of molds belonging to Aspergillus, Penicillium, Cladosporium, and Alernaria genera, and Fumigati section in the indoor air in the buses with and without air-conditions system regarding to period of operation both systemsa (N = 30)
| Type of buses | Period of system operationa (weeks) | Concentrations of molds (cfu/m3) | ||
|---|---|---|---|---|
| P1 | P2 | TZ | ||
| AM(SD) | AM(SD) | AM(SD) | ||
|
| ||||
| With air-conditioning system ( | 1 | 2.8 (6.0) | 1.2 (3.7) | 0.0 |
| 22 | 10.5 (15.6) | 0.5 (2.3) | 0.0 | |
| Without air-conditioning system ( | 1 | 5.4 (12.7) | 3.6 (7.8) | 16.5 (14.2) |
| 22 | 10.6 (14.0) | 2.5 (8.0) | 24.1b | |
|
| ||||
| With air-conditioning system ( | 1 | 0.9 (4,1) | 0.5 (2.3) | 0.0 |
| 22 | 1.3 (4.0) | 0.0 | 0.0 | |
| Without air-conditioning system ( | 1 | 5.4 (12.7) | 3.6 (7.8) | 16.5 (14.2) |
| 22 | 10.6 (14.0) | 0,0 | 24.1b | |
|
| ||||
| With air-conditioning system ( | 1 | 34.1 (35.6) | 7.5 (10.8) | 7.2 (12.7) |
| 22 | 34.1 (35.5) | 9.9 (22.0) | 12.8 (13.1) | |
| Without air-conditioning system ( | 1 | 47.6 (52.2) | 10.4 (18.2) | 44.4 (13,6) |
| 22 | 20.1 (21.1) | 4.9 (10.5) | 0.00b | |
|
| ||||
| With air-conditioning system ( | 1 | 262.2 (266.6) | 48.5 (39.1) | 875.0 (768.8) |
| 22 | 213.3 (224.9) | 59.1 (66.3) | 431.7 (220.1) | |
| Without air-conditioning system ( | 1 | 777.7 (222.6) | 201.7 (169.9) | 2176.8 (26.6) |
| 22 | 248.9 (200.1) | 49.9 (27.8) | 1132.8b | |
|
| ||||
| With air-conditioning system ( | 1 | 8.6 (11.6) | 0.0 | 34.2 (48.1) |
| 22 | 22.3 (35.5) | 4.3 (12,5) | 85.5 (61.5) | |
| Without air-conditioning system ( | 1 | 16.5 (19.5) | 18.7 (59.0) | 62.3 (44.9) |
| 22 | 1.4 (4.3) | 0.0 | 0.0b | |
N samples number, P1 indoor air samples before turning on air-conditioning system/ventilation system, P2 indoor air samples after a 6-min operation of the air-conditioning system/ventilation system, EB external background (atmospheric air), AM arithmetic mean, SD standard deviation, MIN minimum value, MAX maximum value
aFor the buses with air-conditioning system: period of operation form the last filter replacement and disinfection; for the buses without air-conditioning system: period of operation from the last filter replacement
bSingle sample microclimatic parameter in the outdoor air (the average value from the day of sampling)
The incidence of higher levels of molds belonging to Aspergillus, Penicillium, Cladosporium, and Alternaria genera and Fumigati section after a 6-min operation of the air-conditioning system relative to the state before turning on regarding to the period of operation both systems (N = 30)
| Type of buses | Period of system operationa (weeks) |
| |||
|---|---|---|---|---|---|
| 1 | 22 | ||||
|
| % |
| % | ||
|
| |||||
| With air-conditioning system ( | 2 | 10 | 0 | 0 | > 0.05 |
| Without air-conditioning system ( | 1 | 10 | 1 | 10 | > 0.05 |
| | > 0.05 | > 0.05 | |||
|
| |||||
| With air-conditioning system ( | 1 | 5 | 0 | 0 | > 0.05 |
| Without air-conditioning system ( | 1 | 10 | 0 | 0 | > 0.05 |
| | > 0.05 | > 0.05 | |||
|
| |||||
| With air-conditioning system ( | 3 | 15 | 3 | 15 | > 0.05 |
| Without air-conditioning system ( | 2 | 20 | 0 | 0 | > 0.05 |
| | > 0.05 | > 0.05 | |||
|
| |||||
| With air-conditioning system ( | 5 | 25 | 2 | 10 | > 0.05 |
| Without air-conditioning system ( | 0 | 0 | 0 | 0 | > 0.05 |
| | > 0.05 | > 0.05 | |||
|
| |||||
| With air-conditioning system ( | 0 | 0 | 2 | 10 | > 0.05 |
| Without air-conditioning system ( | 1 | 10 | 0 | 0 | > 0.05 |
| | > 0.05 | > 0.05 | |||
N samples number, n number of samples with increased concentration of molds after a 6-min operation of air-conditioning system/ventilation system relative to the state befor turning on both system, % percentage contribution of samples with increased concentration of molds after a 6-min operation of air-conditioning system/ventilation system relative to the state before turning on both system
p level of statistical significance (p < 0.05
aFor the buses with air-conditioning system: period of operation form the last filter replacement and disinfection; for the buses without air-conditioning system: period of operation from the last filter replacement