| Literature DB >> 29047880 |
Axel Kramer, Daniel Over, Patrick Stoller, Thomas A Paul.
Abstract
Novel dielectric insulation gases used as alternatives to sulfur hexafluoride in gas-insulated switchgear (GIS) include several mixtures containing fluorinated organic compounds. We developed a fiber-optic analyzer enabling concentration measurement of fluoroketones used in medium- and high-voltage switchgear applications by ABB, with concurrent compensation of disturbing effects caused by dust and dirt. The sensor enables measurements in GIS and even in operating high-voltage circuit breakers. The online availability of concentration readings of fluoroketones is important for development tests, but can also be applied for monitoring or diagnostics of field installations.Entities:
Year: 2017 PMID: 29047880 DOI: 10.1364/AO.56.004505
Source DB: PubMed Journal: Appl Opt ISSN: 1559-128X Impact factor: 1.980