Chin-Chi Cheng1, Dasheng Lee2.
Abstract
The study investigates the development of sensors, in particular the use of thermo-fluidic sensors and occupancy detectors, to achieve smart operation of air conditioning systems. Smart operation refers to the operation of air conditioners by the reinforcement of interaction to achieve both thermal comfort and energy efficiency. Sensors related to thermal comfort include those of temperature, humidity, and pressure and wind velocity anemometers. Improvements in their performance in the past years have been studied by a literature survey. Traditional occupancy detection using passive infra-red (PIR) sensors and novel methodologies using smartphones and wearable sensors are both discussed. Referring to the case studies summarized in this study, air conditioning energy savings are evaluated quantitatively. Results show that energy savings of air conditioners before 2000 was 11%, and 30% after 2000 by the integration of thermo-fluidic sensors and occupancy detectors. By utilizing wearable sensing to detect the human motions, metabolic rates and related information, the energy savings can reach up to 46.3% and keep the minimum change of predicted mean vote (∆PMV→0), which means there is no compromise in thermal comfort. This enables smart air conditioning to compensate for the large variations from person to person in terms of physiological and psychological satisfaction, and find an optimal temperature for everyone in a given space. However, this tendency should be evidenced by more experimental results in the future.Entities:
Keywords: energy saving; occupancy detector; smart air conditioning; thermal comfort; thermo-fluidic sensors
Year: 2016 PMID: 27916906 PMCID: PMC5191009 DOI: 10.3390/s16122028
Source DB: PubMed Journal: Sensors (Basel) ISSN: 1424-8220 Impact factor: 3.576
Sensors employed by traditional air conditioning system and achieved air conditioning temperature control.
| Product | Sensor Type | Range | Accuracy |
|---|---|---|---|
| H-brand temperature control (USA) | IC sensor | 5~30 °C | 0.5 °C |
| NI-209 temperature control (Taiwan) | IC sensor | −40~50 °C | 1 °C |
| S-brand temperature control (Japan) | 1000 Ω Platinum | −20~70 °C | 0.5 °C |
| S-brand temperature control (Germany) | IC sensor | 0~50 °C | 1 °C |
Figure 1A brief history of the development of air conditioners, thermo-fluidic sensors and occupancy technology illustrating smart air conditioning and smart sensor development qualitatively.
Sensors employed by novel air conditioning system and achieved smart control.
| Year | Air Conditioning Case | Equipped Sensors | Achieved Smart Control | ||
|---|---|---|---|---|---|
| Thermo-Fluidic | Occupancy Detection | Others | |||
| 1982–1983 | EMS for Heating/ventilating/air conditioning equipment: Case study of USA [ | Thermocouples + Multiplexor + Minicomputer system | X | X | Using a computer for supervisory control allows the equipment to be operated in a more efficient manner through temperature sensor feedback controls |
| 1985 | Energy management for air conditioning system in Kuwait [ | RTDs with accuracy to 0.1 °C temperature sensing | X | Water flow rate sensor | Energy management and economic analysis based on occupancy periods and the present values of life-cycle costs |
| 1986 | Computerized energy management system installed in the small to large industries and campus type facilities [ | RTDs + Micro- and minicomputers with 4–10 floating per unit | PIR sensor + hardware digital equipment | X | Hardware digital equipment with occupancy detection function for start/stop of equipment and stand-alone demand controller |
| 1986 | Thermostat management for reducing household energy [ | Thermostat based on thermistor | Home ownership investigation | X | Self-reported winter and summer thermostat settings and control strategies according to sensor data and occupancy status |
| 1992 | Users’ decisions about when and how to operate room air conditioners [ | Thermostat based on thermistor + Wind velocity indicator | X | X | By user education, resident can operate air conditioner by non-thermostatic mode. |
| 1993 | Energy management for multi-zone air conditioning systems in Canada [ | Thermistors with accuracy to 0.5 °C temperature sensing | X | Disturbance input | Multi-zone control based temperature sensor and disturbance signal |
| 1994 | A two zone variable air volume system [ | Supply, return, entering and leaving air condition sensors include air density, velocity, temperature and humidity | Input data related to occupied period | X | A reduced model for variable air volume system to account mass, momentum and energy balance for saving energy |
| 1994 | Comfort control for short term occupancy at hotel [ | Thermostat based on thermistor | PIR sensor integrated in a prototype ‘comfortstat’ | X | Interactive set-point adjustment with immediate response to thermal requests |
| 1996 | Optimization of thermal processes in a variable air volume system [ | Thermistors with accuracy to 0.5 °C temperature sensing + Humidity sensor | Thermal load prediction | X | Optimized thermal processes to achieve thermal comfort by both zone temperature and humidity ratio |
| 1999 | On-line control strategies for air conditioning system [ | RTDs with accuracy to 0.1 °C temperature sensing + Air flow rate sensor + Pressure sensor | Investigating number of occupants | CO2 sensor | Optimizing pressure set-point of variable air volume system to achieve thermal comfort and improve air quality |
| 2001 | Air conditioning control to ensure comfort [ | RTDs with accuracy to 0.01 °C temperature sensing | CO2 detection for improved start-stop time control | Integrated IAQ sensor | Air bypass, CO2 control, setback and improved start-stop time |
| 2005 | Personalized ventilation for air conditioning in a hot and humid climate [ | Thermistors with accuracy to 0.5 °C temperature sensing + Air flow rate sensor with resolution to 0.01 L/s | Investigating number of occupants and detailed data includes sex, age, height and weight | X | Personalized ventilation to improve the immediate breathing zones of occupants in the built environment |
| 2006 | Optimal set point strategy to achieve energy efficient operation of air conditioning system [ | Thermistors with accuracy to 0.5 °C temperature sensing | Occupied time adaptive controller based year-month-day function | X | Occupied time adaptive control and energy efficiency through optimal set point |
| 2008 | Energy saving and improved comfort by increased air movement [ | RTDs with accuracy to 0.1 °C temperature sensing + wind velocity sensor with resolution <0.2 m/s | X | X | Elevating air speed which can offset the impact of increased room air temperature on occupants’ comfort |
| 2008 | Enthalpy estimation for thermal comfort and energy saving in air conditioning system [ | Thermistors with accuracy to 0.5 °C temperature sensing + Humidity sensor for estimation Enthalpy | Optimum operative temperature for people during light, primarily sedentary activity | X | The least enthalpy estimator combines the concept of human thermal comfort with the theory enthalpy |
| 2010 | Task ambient conditioning system [ | Thermo-camera with accuracy to 1 °C temperature sensing + wind velocity sensor with resolution to 0.5 m/s | Infra-Red images | X | A special air conditioning system heats only the feet and hands, and cools only the hands and face, to provide thermal comfort |
| 2010 | Air conditioning system of an AHU dedicated to the personalized ventilation system and an overhead fan-coil dedicated to control the room air temperature [ | Thermistors with accuracy to 0.5 °C temperature sensing + Air flow rate sensor with resolution to 0.1 m3/s | X | X | Microclimate control by an individually controlled air distribution system aimed at improving the quality of inhaled air and thermal comfort off each occupant |
| 2010 | Campus air conditioning system managed by control center on internet [ | RTDs with accuracy to 0.01 °C temperature sensing | Scheduled time-of-day | X | Scheduled control for energy saving |
| 2010 | Ceiling mounted personalized ventilation system [ | Thermistors with accuracy to 0.5 °C temperature sensing + Air flow rate sensor with resolution to 1 L/s | PIR sensor | X | Using desk fans for providing convection cooling to each occupant in rooms |
| 2011 | Air conditioning system in conveniences stores in Taiwan [ | IC type temperature sensor + embedded system for constructing a WSN | Digital camera | Digital power meter | WSN provides feedback of distributed thermal comfort index and controls environment |
| 2011 | Chilled ceiling and displacement ventilation aided with personalized evaporative cooler [ | Thermistors with accuracy to 0.5 °C temperature sensing + Air flow rate sensor with resolution to 0.1 L/s + Humidity sensor | Personal location service | X | Personalized air conditioning directly towards the occupant trunk and face |
| 2011 | Air conditioning system strategies for energy conservation in commercial buildings in Saudi Abraia [ | Thermostat based on thermistor | Specified schedules | X | Air conditioning model verification, investigation of energy savings and thermal comfort |
| 2013 | Personalized air condition and desk fan control for the convection flow around occupants [ | Temperature sensor with accuracy to 0.01 °C + Thermal radiation sensor + wind velocity sensor with resolution to 0.1 m/s | Skin and core temperature; Sensible and latent heat; Clothing properties; Human metabolic | X | Building three models: CFD model; Thermal comfort model; Multi-segmental bio-heat model |
| 2013 | A versatile energy management system for large integrated cooling systems [ | Thermistors with accuracy to 0.5 °C temperature sensing + Ambient property sensor | X | Level sensor | Versatile energy management platform for energy saving control of four large cooling systems |
| 2013 | A low-mixing ceiling mounted personalized air conditioning system [ | Thermistors with accuracy to 0.5 °C temperature sensing + Air flow rate sensor with resolution to 0.1 L/s | Location based service | CO2 sensor | CFD, bio-heat, and comfort model coupling |
| 2014 | Variable air volume air conditioning system for buildings with large number of zones [ | Thermostat based on thermistor | Calendar for occupancy prediction | X | Model predictive control |
| 2014 | Smart sensors enabled smart air condition control [ | IC type temperature sensor | PIR detector, mobile phone and wearable device | X | Wearable sensing for smart control |
| 2015 | Supervisory control methodology for air condition system of commercial buildings [ | Thermistors with accuracy to 0.5 °C temperature sensing | X | Electricity frequency detector | Air conditioning control to electricity grid integration |
| 2016 | Indoor air quality and energy management through real-time sensing in commercial buildings [ | Thermistors with accuracy to 0.5 °C temperature sensing + Humidity sensor | Occupancy/movement detecting system through Wifi, GSM or Bluetooth signals, or through volume recognition with depth sensors (Ultrasound sensor) | Digital power meter | CFD, bio-heat, and comfort model coupling |
| 2016 | Multi-evaporator system integrated with networked control systems in large spatially distributed plants [ | IC type temperature sensor + Embedded system for constructing a WSAN (Wireless sensor and actuators network) | Evaporator assembled near crowds in many places | X | Completing a detailed analysis of the end-to-end real-time flows over WSAN and a real-time kernel with an earliest deadline first (EDF) scheduler |
Figure 2The qualitative analysis of the developed sensor technologies and achieved smart controls of the selected case studies in Table 2.
Figure 3Energy savings (%) achieved by smart air conditioning researches, enabled by sensor and occupancy detection technology from 1982 to 2016.
Figure 4The aforementioned experimental data and the estimated data of energy savings of air conditioner through the development of fluidic sensors with occupancy detection technology from 2008 to 2016.