Zhigao Wang1, Xinghai Zhang1, Fangqiang Wang1, Xinsheng Lan1, Yiqian Zhou1.
Abstract
In order to analyze the cracking and aging reason of the silicone rubber current transformer (CT) insulation bushing used for 8 years from a 500 kV alternating current substation, characteristics including Fourier transform infrared (FTIR) spectroscopy, mechanical properties analysis, hardness, and thermo gravimetric analysis have been carried out. The FTIR results indicated that the external surface of the silicone rubber CT insulation bushing suffered from more serious aging than the internal part, fracture of side chain Si-C bond was much more than the backbone. Mechanical properties and thermal stability results illustrated that the main aging reasons were the breakage of side chain Si-C bond and the excessive cross-linking reaction of the backbone. This study can provide valuable basis for evaluating degradation mechanism and aging state of the silicone rubber insulation bushing in electric power field.Entities:
Keywords: Aging analysis; Characterization; External insulation; Polymers; Silicone rubber
Year: 2016 PMID: 27390631 PMCID: PMC4916109 DOI: 10.1186/s40064-016-2549-y
Source DB: PubMed Journal: Springerplus ISSN: 2193-1801
Fig. 1Picture of 500 kV CT composite insulators out of service
Fig. 2Cracking on the surface part (left) and intact inner part (right) of the CT insulation bushing
Fig. 3FTIR spectra of the silicone rubber CT insulation bushing samples: a S1 and S2, b S3 and S4, c S5 and S6
Mechanical properties test results of the silicone rubber CT insulation bushing samples
| Sample | Tensile strength (MPa) | Elongation at break (%) |
|---|---|---|
| S1 | 1.87 | 217 |
| S2 | 2.88 | 267 |
| S3 | 2.08 | 261 |
| S4 | 2.55 | 256 |
| S5 | 2.60 | 243 |
| S6 | 2.66 | 236 |
Shore A hardness of the silicone rubber CT insulation bushing samples
| Sample | S1 | S2 | S3 | S4 | S5 | S6 |
|---|---|---|---|---|---|---|
| Shore hardness (HA) | 33 | 25 | 26 | 26 | 27 | 26 |
Fig. 4TG curves of the silicone rubber CT insulation bushing samples: a S1 and S2, b S3 and S4, c S5 and S6
Thermo gravimetric analysis data of the silicone rubber CT insulation bushing samples
| Sample | Tonset (°C) | Tmax (°C) | Residue at 800 °C (%) |
|---|---|---|---|
| S1 | 375.1 | 425.2 | 83.80 |
| S2 | 427.2 | 665.2 | 72.70 |
| S3 | 375.3 | 438.1 | 83.40 |
| S4 | 427.6 | 664.1 | 73.47 |
| S5 | 375.6 | 436.1 | 84.85 |
| S6 | 428.1 | 664.4 | 77.89 |