Leena Korpinen1, Rauno Pääkkönen2.
Abstract
The aim was to investigate occupational exposure to electric and magnetic fields during tasks at ground or floor level at 110 kV substations in Finland and to compare the measured values to Directive 2013/35/EU. Altogether, 347 electric field measurements and 100 magnetic field measurements were performed. The average value of all electric fields was 2.3 kV/m (maximum 6.4 kV/m) and that of magnetic fields was 5.8 µT (maximum 51.0 µT). It can be concluded that the electric and magnetic field exposure at ground or floor level is typically below the low action levels of Directive 2013/35/EU. The transposition of the directive will not create new needs to modify the work practice of the evaluated tasks, which can continue to be performed as before. However, for workers with medical implants, the exposure may be high enough to cause interference.Entities:
Keywords: electric fields; exposure; magnetic fields; substations
Mesh:
Year: 2016 PMID: 27075421 PMCID: PMC4960502 DOI: 10.1080/10803548.2016.1153858
Source DB: PubMed Journal: Int J Occup Saf Ergon ISSN: 1080-3548
Figure 1. Example of electric field measurement at a 110 kV substation.
Figure 2. Example of magnetic field measurement at a 110 kV substation.
Figure 3. Histogram of measured electric field values at tasks A, B and C.
Figure 4. Histogram of measured magnetic field values at tasks B and C.
Maximum values, M and SD of measured electric fields at work tasks A, B and C at 110 kV substations.
| Task ( | Code of substation | Electric field (kV/m), max | Electric field (kV/m), | Electric field (kV/m), | Electric field (kV/m), geometric mean | Height of sensor above ground (m) |
|---|---|---|---|---|---|---|
| A (4) | S8 | 0.8 | 0.8 | 0.1 | 0.7 | 1.7 |
| A (1) | S12 | 2.1 | 2.1 | 0.0 | 2.1 | 1.7 |
| A (4) | S17 | 1.5 | 1.1 | 0.4 | 1.0 | 1.7 |
| A (23) | S19 | 5.3 | 3.1 | 0.9 | 2.9 | 1.7 or 1.8 |
| B (32) | S1 | 6.1 | 4.0 | 1.1 | 3.8 | 1.7 or 1.8 or 2.0 |
| B (8) | S2 | 2.1 | 1.5 | 0.4 | 1.4 | 1.0 or 1.7 |
| B (12) | S3 | 3.7 | 1.1 | 0.9 | 0.7 | 1.7 |
| B (2) | S4 | 2.2 | 1.4 | 1.1 | 1.1 | 1.7 |
| B (1) | S5 | 1.7 | 1.7 | – | 1.7 | 1.7 |
| B (1) | S6 | 0.004 | 0.004 | – | 0.004 | 1.7 |
| B (38) | S7 | 4.8 | 2.6 | 0.9 | 2.5 | 1.7 or 1.8 or 2.0 |
| B (13) | S8 | 4.8 | 2.5 | 1.1 | 2.3 | 1.7 |
| B (2) | S9 | 1.1 | 0.9 | 0.4 | 0.8 | 1.7 |
| B (11) | S11 | 5.6 | 4.1 | 0.9 | 4.0 | 1.7 |
| B (1) | S13 | 2.8 | 2.8 | – | 2.8 | 1.7 |
| B (1) | S14 | 4.7 | 4.7 | – | 4.7 | 1.7 |
| B (6) | S16 | 4.6 | 3.6 | 0.7 | 3.5 | 1.7 or 1.8 |
| B (2) | S17 | 1.4 | 0.9 | 0.8 | 0.6 | 1.7 |
| B (45) | S19 | 4.0 | 3.0 | 0.6 | 2.9 | 1.7 |
| C (9) | S7 | 1.8 | 1.5 | 0.3 | 1.5 | 1.7 |
| C (3) | S11 | 6.4 | 5.2 | 1.7 | 4.9 | 1.7 or 1.8 |
| C (2) | S15 | 3.2 | 2.7 | 0.8 | 2.6 | 1.7 or 2.1 |
| C (12) | S16 | 2.8 | 1.8 | 0.7 | 1.7 | 1.7 |
| C (54) | S17 | 3.0 | 1.6 | 0.6 | 1.4 | 1.7 or 2.0 |
| C (60) | S19 | 2.4 | 1.1 | 0.6 | 0.9 | 1.7 |
Note: Task A = maintenance of an operating device of a circuit breaker at ground level; task B = walking in a 110 kV substation; task C = maintenance of an operating device of disconnector at ground or floor level; – denotes a single measurement where standard deviation cannot be calculated.
Maximum values, M and SD of measured magnetic fields at different work tasks B and C at 110 kV substations.
| Tasks ( | Code of substation | Magnetic field (µT), max | Magnetic field (µT), | Magnetic field (µT), | Magnetic field (µT), geometric mean | Height of sensor above ground (m) |
|---|---|---|---|---|---|---|
| B (5) | S1 | 12.9 | 10.2 | 3.6 | 9.5 | 1.7 |
| B (6) | S2 | 4.1 | 2.6 | 0.9 | 2.4 | 1.7 |
| B (6) | S3 | 2.2 | 1.3 | 0.8 | 1.0 | 1.7 |
| B (1) | S4 | 16.0 | 16.0 | – | 16.0 | 1.7 |
| B (2) | S5 | 12.2 | 11.6 | 0.7 | 11.5 | 1.7 |
| B (2) | S6 | 4.4 | 3.1 | 1.9 | 2.7 | 1.7 |
| B (3) | S7 | 23.5 | 19.5 | 4.3 | 19.2 | 1.7 |
| B (2) | S8 | 28.0 | 25.0 | 4.2 | 24.8 | 1.7 |
| B (2) | S10 | 18.5 | 12.8 | 8.1 | 11.4 | 1.7 |
| B (2) | S11 | 5.4 | 3.7 | 2.4 | 3.3 | 1.7 |
| B (1) | S14 | 4.5 | 4.5 | – | 4.5 | 1.7 |
| B (3) | S15 | 3.5 | 2.3 | 1.3 | 2.0 | 1.7 |
| B (2) | S16 | 13.7 | 12.4 | 1.9 | 12.3 | 1.7 |
| B (5) | S18 | 11.0 | 7.5 | 3.5 | 6.7 | 1.7 |
| B (3) | S19 | 51.0 | 42.5 | 7.4 | 42.1 | 1.7 |
| C (1) | S4 | 1.8 | 1.8 | – | 1.8 | 1.7 |
| C (54) | S17 | 7.1 | 2.2 | 1.7 | 1.6 | 1.7 |
Note: Task B = walking in a 110 kV substation; task C = maintenance of an operating device of disconnector at ground or floor level; – denotes a single measurement where standard deviation cannot be calculated.