| Literature DB >> 27035575 |
Ali M Humada1,2, Mojgan Hojabri1, Mohd Herwan Bin Sulaiman1, Hussein M Hamada3, Mushtaq N Ahmed1.
Abstract
A grid-connected photovoltaic (PV) system operates under fluctuated weather condition has been modeled and characterized based on specific test bed. A mathematical model of a small-scale PV system has been developed mainly for residential usage, and the potential results have been simulated. The proposed PV model based on three PV parameters, which are the photocurrent, IL, the reverse diode saturation current, Io, the ideality factor of diode, n. Accuracy of the proposed model and its parameters evaluated based on different benchmarks. The results showed that the proposed model fitting the experimental results with high accuracy compare to the other models, as well as the I-V characteristic curve. The results of this study can be considered valuable in terms of the installation of a grid-connected PV system in fluctuated climatic conditions.Entities:
Mesh:
Year: 2016 PMID: 27035575 PMCID: PMC4817980 DOI: 10.1371/journal.pone.0152766
Source DB: PubMed Journal: PLoS One ISSN: 1932-6203 Impact factor: 3.240
Fig 1Schematic diagram of the PV system installed under Malaysia weather condition.
Specifications of the proposed system.
| Parameter | Value and Units |
|---|---|
| Number of PV modules | 42 |
| Maximum Power (PMP) | 120 W |
| Maximum Voltage (VMP) | 16.9 V |
| Maximum Current (IMP) | 7.10 A |
| Open-Circuit Voltage (VOC) | 21.5 V |
| Short-Circuit Current (ISC) | 7.45 A |
Values of C1–C6.
| Coefficient | Value |
|---|---|
| 0.0062 | |
| 0.0048 | |
| 6.745×10−6 | |
| 3.237×10−8 | |
| 2.677×10−4 | |
| 6399 |
Fig 2A comparison between the proposed equation for the parameter a and the experimental results with other models.
Fig 4A comparison between the proposed equation for the reverse diode current, I and the experimental results with other models.
Evaluation criteria of the proposed model.
| Evaluation Criteria | Parameter | Parameter | Parameter |
|---|---|---|---|
| MAPE | 3.12% | 6% | 10.3% |
| SSE | 2.198×10−16 | 2.7281×10−15 | 7.216×10−14 |
| R-squared | 0.9998 | 0.998 | 0.997 |
| SSR | 1.09878×10−12 | 1.36132×10−12 | 2.39812×10−11 |
| SST | 1.099×10−12 | 1.364×10−12 | 2.405×10−11 |
Fig 5Influence of changing parameter “a” on the I–V characteristic curve, and comparing with experimental results and other models.
Fig 7Influence of changing I on the I–V characteristic curve, and comparing with experimental results and other models.
Fig 8Inverter’s power and efficiency with respect to PV power.