Prevalence and distribution of Legionella spp in potable water systems in Germany, risk factors associated with contamination, and effectiveness of thermal disinfection.

Eva-Brigitta Kruse1, Arno Wehner2, Hilmar Wisplinghoff3.   

Abstract

BACKGROUND: Worldwide, Legionella spp are a common cause of community-acquired pneumonia. Potable water systems are a main reservoir; however, exposure in the community is unknown.
METHODS: Water samples from 718 buildings in Germany were collected. Possible risk factors were prospectively recorded. All samples were tested for Legionella spp using cultural microbiologic methods. Samples were assigned to 1 of 5 levels of contamination. Statistical analysis was performed to determine the influence of risk factors for contamination and, in a subgroup of buildings, for unsuccessful thermal disinfection.
RESULTS: In total, 4,482 water samples from 718 different water supply systems were analyzed. In 233 buildings (32.7%), Legionella spp were identified, 148 (63.5%) of which had a medium or higher level of contamination. The most common species was Legionella pneumophila (94%). Contamination was strongly associated with temperature in the circulation, but not with the size of the building, time of the year, or transport time to the laboratory. Thermal disinfection was successful in fewer than half of the buildings.
CONCLUSIONS: There is relevant exposure to Legionella spp in the community. Water systems are not always up to current technical standards. Although microbiological risk assessment remains a challenge, there is a case for monitoring for Legionella spp outside of hospitals.
Copyright © 2016 Association for Professionals in Infection Control and Epidemiology, Inc. Published by Elsevier Inc. All rights reserved.

Entities:  

Keywords:  Microbiological monitoring; Technical assessment; Water-related infection risks

Mesh:

Substances:

Year:  2016        PMID: 26775932     DOI: 10.1016/j.ajic.2015.10.025

Source DB:  PubMed          Journal:  Am J Infect Control        ISSN: 0196-6553            Impact factor:   2.918


  5 in total

1.  Ten Questions Concerning the Aerosolization and Transmission of Legionella in the Built Environment.

Authors:  Aaron J Prussin; David Otto Schwake; Linsey C Marr
Journal:  Build Environ       Date:  2017-06-13       Impact factor: 6.456

2.  Co-Occurrence of Free-Living Amoeba and Legionella in Drinking Water Supply Systems.

Authors:  Olga Valciņa; Daina Pūle; Artjoms Mališevs; Jūlija Trofimova; Svetlana Makarova; Genadijs Konvisers; Aivars Bērziņš; Angelika Krūmiņa
Journal:  Medicina (Kaunas)       Date:  2019-08-15       Impact factor: 2.430

3.  Low Efficacy of Periodical Thermal Shock for Long-Term Control of Legionella spp. in Hot Water System of Hotels.

Authors:  Jhon J Molina; Magdalena Bennassar; Edwin Palacio; Sebastian Crespi
Journal:  Pathogens       Date:  2022-01-25

Review 4.  Confirming the Presence of Legionella pneumophila in Your Water System: A Review of Current Legionella Testing Methods.

Authors:  James T Walker; Paul J McDermott
Journal:  J AOAC Int       Date:  2021-08-20       Impact factor: 1.913

5.  Variable Legionella Response to Building Occupancy Patterns and Precautionary Flushing.

Authors:  William J Rhoads; Meril Sindelar; Céline Margot; Nadine Graf; Frederik Hammes
Journal:  Microorganisms       Date:  2022-03-03
  5 in total

北京卡尤迪生物科技股份有限公司 © 2022-2023.