Abstract
Due to water shortage, municipal reclaimed water rather than surface water was replenished into recycling cooling water system in power plants in some cities in China. In order to understand the effects of the measure on carbon steel corrosion, characteristics of two kinds of foulant produced in different systems were studied in the paper. Differences between municipal reclaimed water and surface water were analyzed firstly. Then, the weight and the morphology of two kinds of foulant were compared. Moreover, other characteristics including the total number of bacteria, sulfate reducing bacteria, iron bacteria, extracellular polymeric substance (EPS), protein (PN), and polysaccharide (PS) in foulant were analyzed. Based on results, it could be concluded that microbial and corrosive risk would be increased when the system replenished by municipal reclaimed water instead of surface water.Entities:
Year: 2015 PMID: 25893132 PMCID: PMC4393932 DOI: 10.1155/2015/746064
Source DB: PubMed Journal: J Anal Methods Chem ISSN: 2090-8873 Impact factor: 2.193
Figure 1Static reactor.
Analytical methods of water quality.
| Number | Test index | The test method or instrument |
|---|---|---|
| 1 | pH | Glass electrode method |
| 2 | Turbidity | WZS-180 turbidity meter |
| 3 | Conductivity | DDSJ-308A conductivity meter |
| 4 | TDS | DDSJ-308A conductivity meter |
| 5 | Cl− | The Mol method (GB/T 15453-95) |
| 6 | SO4 2− | Gravimetric method |
| 7 | Alkalinity | Acid-base indicator titration method (GB/T 15451-95) |
| 8 | Hardness | EDTA titrimetry (GB/T 15452-95) |
| 9 | HCO3 2− | Titrimetry |
| 10 | COD | Permanganate titration (GB/T 15456-95) |
| 11 | TP | Ammonium molybdate spectrophotometer method (B G76 002-90) |
| 12 | Orthophosphate | Ammonium molybdate spectrophotometer method (B G76 002-90) |
| 13 | TN | Potassium persulfate oxidation ultraviolet spectroscopy |
| 14 | NH4 +-N | Pay reagent luminosity law |
| 15 | DO | YSI 550A dissolved oxygen meters |
| 16 | Total Fe | O-Phenanthroline spectrophotometer method |
| 17 | Al | HI 93747 NANHA aluminum ion tester |
| 18 | Zn | HI 93731 NANHA zinc ion tester |
| 19 | Cu | HI 93747 NANHA copper ion tester |
| 20 | Me | HI 93748 NANHA manganese ion tester |
| 21 | Si | Molybdenum blue colorimetric method |
| 22 | Surfactant | Methylene blue spectrophotometer method |
Figure 2Protein standard curve.
Figure 3Polysaccharide standard curve.
Comparison of water quality of municipal reclaimed water and surface water.
| Number | Index | Unit | Municipal reclaimed water | Surface water |
|
| ||||
| 1 | Turbidity | NTU | 1.2~4.3 | 1.9~5.7 |
| 2 | pH | 7.22~7.91 | 7.05~8.57 | |
| 3 | Conductivity |
| 930~1101 | 566~753 |
| 4 | TDS | mg/mL | 540~587 | 283~356 |
| 5 | Cl− | mg/L | 109.53~125.29 | 26.30~48.45 |
| 6 | SO4 2− | mg/L | 100.15~122.25 | 84.76~103.29 |
| 7 | Total alkalinity (CaCO3) | mg/L | 138.57~143.24 | 150.25~168.78 |
| 8 | Total hardness (CaCO3) | mg/L | 286.36~296.56 | 268.77 |
| 9 | Calcium hardness (CaCO3) | mg/L | 176.5 | 122.8 |
| 10 | HCO3 2− | mmol/L | 3.464 | 3.572 |
| 11 | CODMn | mg/L | 4.2~6.8 | 2.24~3.5 |
| 12 | TP | mg/L | 0.21~0.39 | 0.13~0.17 |
| 13 | Soluble TP | mg/L | 0.15~0.21 | 0.10~0.15 |
| 14 | Orthophosphate | mg/L | 0.12~0.17 | 0.06~0.09 |
| 15 | TN | mg/L | 35.2 | 23.26 |
| 16 | Total Fe | mg/L | 0.075 | 0.061 |
| 17 | Al | mg/L | <0.04 | <0.04 |
| 18 | Zn | mg/L | <0.018 | 0.12 |
| 19 | Cu | mg/L | <0.010 | <0.010 |
| 20 | Mn | mg/L | <0.001 | 0.005 |
| 21 | Si | mg/L | 4.36 | 1.5 |
| 22 | Surfactant | mg/L | 0.14 | <0.05 |
| 23 | Total bacterial count | cfu/mL | (1.5~4.9) × 104 | 1.0 × 103 |
Figure 4Weights of foulant in recycling cooling water system makeup by municipal reclaimed water and surface water. Note: unit of weight of foulant was wet weight of foulant per unit area of coupon.
Figure 5Morphology of foulants in recycling cooling water system makeup by municipal reclaimed water and surface water by SEM.
Figure 6Corrosion morphology comparison in recycling cooling water system makeup by municipal reclaimed water and surface water.
Figure 7Comparison of EPS, PS, and PN in foulants in recycling cooling water system makeup by municipal reclaimed water and surface water.
Figure 8Microorganism comparisons of foulant in recycling cooling water system makeup by municipal reclaimed water and surface water. Note: the unit of the total number of bacteria was 106 cfu/g; unit of SRB and iron bacteria was 103 cfu/g.