Young Joong Kang1, Jungho Ahn1, Yang-In Hwang2.
Abstract
We report 2 cases of hepatotoxicity in cleanroom workers due to high retained chloroform air concentrations. The women, aged 34 and 41 years, who had been working in a medical endoscopic device manufacturer as cleanroom workers for approximately 40-45 days suffered severe liver damage. Two measured time-weighted averages of the chloroform concentration in the air in the cleanroom were 82.74 and 64.24 ppm, which are more than 6 times the legal occupational exposure limit in Korea. Only 7% of the cleanroom air was newly introduced from outside. The clinical courses of these cases and workplace inspection, led us to conclude that both cases of hepatotoxicity were caused by chloroform exposure.Entities:
Keywords: Chloroform; Cleanroom; Liver toxicity; Toxic hepatitis; Trichloromethane
Year: 2014 PMID: 25411642 PMCID: PMC4236418 DOI: 10.1186/s40557-014-0049-5
Source DB: PubMed Journal: Ann Occup Environ Med ISSN: 2052-4374
Liver enzymes
|
| |||||
|---|---|---|---|---|---|
| Case 1 | AST/ALT | 359/499 (0) | 295/436(1) | 179/309(3)* | 46/83 (11)† |
| Case 2 | AST/ALT | 767/1420(0) | 312/739(3) | 140/341(7)* | 40/98 (14)† |
*Last laboratory data during the course of hospitalization.
†Out Patient Department follow up visit.
Figure 1Cleanroom workers inside the cleanroom. a. Inside the cleanroom, workers are assembling with components of endoscopic devices with chloroform adhesives. b. The cleanroom is covered up tightly.
Concentrations of volatile organic compounds
|
|
|
| |
|---|---|---|---|
|
|
| ||
| Cleanroom | 337 | 82.74 | 160.61 |
| 337 | 64.24 | 98.71 | |
| Container workshop | 335 | 5.35 | 21.18 |
| 338 | 3.34 | 35.34 | |
| OEL* (TWA†) | 10 | 1,000 | |
* OEL, Occupational exposure limit.
† TWA, Time-weighted average.
Figure 2The percentage of outdoor air recirculated can be calculated by inputting the tracer values into this formula.
Carbon dioxide concentrations the cleanroom
|
|
| |
|---|---|---|
|
|
| |
| Supply air | 2,020 | 2,280 |
| Recirculation air | 2,140 | 2,400 |
| Outdoor air | 560 | 570 |