Contaminant levels, source strengths, and ventilation rates in California retail stores.

W R Chan1, S Cohn1, M Sidheswaran1, D P Sullivan1, W J Fisk1.   

Abstract

UNLABELLED: This field study measured ventilation rates and indoor air quality in 21 visits to retail stores in California. Three types of stores, such as grocery, furniture/hardware stores, and apparel, were sampled. Ventilation rates measured using a tracer gas decay method exceeded the minimum requirement of California's Title 24 Standard in all but one store. Concentrations of volatile organic compounds (VOCs), ozone, and carbon dioxide measured indoors and outdoors were analyzed. Even though there was adequate ventilation according to standard, concentrations of formaldehyde and acetaldehyde exceeded the most stringent chronic health guidelines in many of the sampled stores. The whole-building emission rates of VOCs were estimated from the measured ventilation rates and the concentrations measured indoor and outdoor. Estimated formaldehyde emission rates suggest that retail stores would need to ventilate at levels far exceeding the current Title 24 requirement to lower indoor concentrations below California's stringent formaldehyde reference level. Given the high costs of providing ventilation, effective source control is an attractive alternative. PRACTICAL IMPLICATIONS: Field measurements suggest that California retail stores were well ventilated relative to the minimum ventilation rate requirement specified in the Building Energy Efficiency Standards Title 24. Concentrations of formaldehyde found in retail stores were low relative to levels found in homes but exceeded the most stringent chronic health guideline. Looking ahead, California is mandating zero energy commercial buildings by 2030. To reduce the energy use from building ventilation while maintaining or even lowering formaldehyde in retail stores, effective formaldehyde source control measures are vitally important. Published 2014. This article is a U.S. Government work and is in the public domain in the USA.

Entities:  

Keywords:  Building energy efficiency standards; Formaldehyde; Ozone; Ventilation; Volatile organic compounds

Mesh:

Substances:

Year:  2014        PMID: 25155526     DOI: 10.1111/ina.12152

Source DB:  PubMed          Journal:  Indoor Air        ISSN: 0905-6947            Impact factor:   5.770


  2 in total

1.  Variability of Total Volatile Organic Compounds (TVOC) in the Indoor Air of Retail Stores.

Authors:  Chunrong Jia; Kevin Cao; Riya Valaulikar; Xianqiang Fu; Anna Bess Sorin
Journal:  Int J Environ Res Public Health       Date:  2019-11-21       Impact factor: 3.390

2.  Presumed Exposure to Chemical Pollutants and Experienced Health Impacts among Warehouse Workers at Logistics Companies: A Cross-Sectional Survey.

Authors:  Szabolcs Lovas; Károly Nagy; János Sándor; Balázs Ádám
Journal:  Int J Environ Res Public Health       Date:  2021-07-01       Impact factor: 3.390

  2 in total

北京卡尤迪生物科技股份有限公司 © 2022-2023.