Literature DB >> 24499385

Removal of particulate matter emitted from a subway tunnel using magnetic filters.

Youn-Suk Son1, Trieu-Vuong Dinh, Sang-Gwi Chung, Jai-Hyo Lee, Jo-Chun Kim.   

Abstract

We removed particulate matter (PM) emitted from a subway tunnel using magnetic filters. A magnetic filter system was installed on the top of a ventilation opening. Magnetic field density was increased by increasing the number of permanent magnet layers to determine PM removal characteristics. Moreover, the fan's frequency was adjusted from 30 to 60 Hz to investigate the effect of wind velocity on PM removal efficiency. As a result, PM removal efficiency increased as the number of magnetic filters or fan frequency increased. We obtained maximum removal efficiency of PM10 (52%), PM2.5 (46%), and PM1 (38%) at a 60 Hz fan frequency using double magnetic filters. We also found that the stability of the PM removal efficiency by the double filter (RSD, 3.2-5.8%) was higher than that by a single filter (10.9-24.5%) at all fan operating conditions.

Entities:  

Mesh:

Substances:

Year:  2014        PMID: 24499385     DOI: 10.1021/es404502x

Source DB:  PubMed          Journal:  Environ Sci Technol        ISSN: 0013-936X            Impact factor:   9.028


  1 in total

Review 1.  Environmental and Health Effects of Ventilation in Subway Stations: A Literature Review.

Authors:  Yueming Wen; Jiawei Leng; Xiaobing Shen; Gang Han; Lijun Sun; Fei Yu
Journal:  Int J Environ Res Public Health       Date:  2020-02-08       Impact factor: 3.390

  1 in total

北京卡尤迪生物科技股份有限公司 © 2022-2023.