Uniformity of stratum-ventilated thermal environment and thermal sensation.

Y Cheng1, M L Fong, T Yao, Z Lin, K F Fong.   

Abstract

Three human test series were conducted to evaluate the uniformity of the thermal environments in a stratum-ventilated chamber with dimensions of 8.8 m (L) × 5.1 m (W) × 2.4 m (H). In all, nineteen conditions were generated by adjusting the room temperature, supply airflow rate, and supply terminal type. An air diffuser performance index (ADPI) of at least 80% was achieved for most cases. This result shows that the air velocity and temperature in the occupied zone are reasonably uniform. Subjective assessments using the ASHRAE 7-point scale indicate that the thermal sensations of the subjects in stratum ventilation are also uniform. This study examines the applicability of the predicted mean vote (PMV) model for evaluating stratum ventilation. When compared to the actual mean thermal sensation votes (ATS), the PMV values are acceptable. The PMV results at a height of 1.1 m above the floor show better agreement with the ATS than at a height of 0.1 m.
© 2014 John Wiley & Sons A/S. Published by John Wiley & Sons Ltd.

Entities:  

Keywords:  Air diffusion performance index; Effective draft temperature; Stratum ventilation; Thermal sensation; Uniformity

Mesh:

Year:  2014        PMID: 24438214     DOI: 10.1111/ina.12097