Literature DB >> 24279292

Fumigation of a laboratory-scale HVAC system with hydrogen peroxide for decontamination following a biological contamination incident.

K M Meyer1, M W Calfee, J P Wood, L Mickelsen, B Attwood, M Clayton, A Touati, R Delafield.   

Abstract

AIMS: To evaluate hydrogen peroxide vapour (H2 O2 ) for its ability to inactivate Bacillus spores within a laboratory-scale heating, ventilation and air-conditioning (HVAC) duct system. METHODS AND
RESULTS: Experiments were conducted in a closed-loop duct system, constructed of either internally lined or unlined galvanized metal. Bacterial spores were aerosol-deposited onto 18-mm-diameter test material coupons and strategically placed at several locations within the duct environment. Various concentrations of H2 O2 and exposure times were evaluated to determine the sporicidal efficacy and minimum exposure needed for decontamination. For the unlined duct, high variability was observed in the recovery of spores between sample locations, likely due to complex, unpredictable flow patterns within the ducts. In comparison, the lined duct exhibited a significant desorption of the H2 O2 following the fumigant dwell period and thus resulted in complete decontamination at all sampling locations.
CONCLUSIONS: These findings suggest that decontamination of Bacillus spore-contaminated unlined HVAC ducts by hydrogen peroxide fumigation may require more stringent conditions (higher concentrations, longer dwell duration) than internally insulated ductwork. SIGNIFICANCE AND IMPACT OF THE STUDY: These data may help emergency responders when developing remediation plans during building decontamination.
© 2013 The Society for Applied Microbiology This article has been contributed to by US Government employees and their work is in the public domain in the USA.

Entities:  

Keywords:  Bacillus anthracis; anthrax; biological agent; decontamination; fumigation; heating, ventilation and air conditioning; hydrogen peroxide

Mesh:

Substances:

Year:  2013        PMID: 24279292     DOI: 10.1111/jam.12404

Source DB:  PubMed          Journal:  J Appl Microbiol        ISSN: 1364-5072            Impact factor:   3.772


  5 in total

1.  Improvement of Vivarium Biodecontamination through Data-acquisition Systems and Automation.

Authors:  Shakthi Rk Devan; Suresh Vasu; Yogesha Mallikarjuna; Ramkumar Ponraj; Gireesh Kamath; Suresh Poosala
Journal:  J Am Assoc Lab Anim Sci       Date:  2018-03-01       Impact factor: 1.232

Review 2.  Review of Decontamination Techniques for the Inactivation of Bacillus anthracis and Other Spore-Forming Bacteria Associated with Building or Outdoor Materials.

Authors:  Joseph P Wood; Alden Charles Adrion
Journal:  Environ Sci Technol       Date:  2019-04-02       Impact factor: 9.028

3.  A simple decontamination approach using hydrogen peroxide vapour for Bacillus anthracis spore inactivation.

Authors:  J P Wood; M W Calfee; M Clayton; N Griffin-Gatchalian; A Touati; S Ryan; L Mickelsen; L Smith; V Rastogi
Journal:  J Appl Microbiol       Date:  2016-10-23       Impact factor: 3.772

4.  Low-concentration hydrogen peroxide decontamination for Bacillus spore contamination in buildings.

Authors:  Ronald Leroy Mickelse; Joseph Wood; Michael Worth Calfee; Shannon Serre; Shawn Ryan; Abderrahmane Touati; Francis Robbins Delafield; Lola Denise Aslett
Journal:  Remediation (N Y)       Date:  2019-12-03

5.  Air Disinfection-From Medical Areas to Vehicle.

Authors:  Anna Bukłaha; Anna Wieczorek; Ewelina Kruszewska; Piotr Majewski; Dominika Iwaniuk; Paweł Sacha; Elzbieta Tryniszewska; Piotr Wieczorek
Journal:  Front Public Health       Date:  2022-02-24
  5 in total