Literature DB >> 24005820

Susceptibility of Legionella strains to the chlorinated biocide, monochloramine.

Delphine Jakubek1, Carole Guillaume, Marie Binet, Gérard Leblon, Michael DuBow, Matthieu Le Brun.   

Abstract

Members of the Legionella genus find suitable conditions for their growth and survival in nuclear power plant cooling circuits. To limit the proliferation of Legionella pathogenic bacteria in nuclear power plant cooling circuits, and ensure that levels remain below regulatory thresholds, monochloramine treatment can be used. Although the treatment is highly effective, i.e. it reduces Legionella numbers by over 99%, Legionella bacteria can still be detected at low concentrations and rapid re-colonisation of circuits can occur after the treatment has ceased. The aim of this study was to develop an in vitro methodology for determining the intrinsic susceptibility of L. pneumophila strains, collected from various nuclear power plant cooling circuits subjected to different treatment conditions. The methodology was developed by using an original approach based on response surface methodology (RSM) combined with a multifactorial experimental design. The susceptibility was evaluated by the Ct factor. The susceptibility of environmental strains varies widely and is, for some strains, greater than that of known tolerant species; however, strain susceptibility was not related to treatment conditions. Selection pressure induced by monochloramine use did not result in the selection of more tolerant Legionella strains and did not explain the detection of Legionella during treatment or the rapid re-colonisation of cooling circuits after disinfection has ceased.

Entities:  

Mesh:

Substances:

Year:  2013        PMID: 24005820      PMCID: PMC4070956          DOI: 10.1264/jsme2.me12205

Source DB:  PubMed          Journal:  Microbes Environ        ISSN: 1342-6311            Impact factor:   2.912


Legionella pneumophila is the causative agent of Legionnaires’ disease and L. pneumophila serogroup 1 is responsible for more than 98% of legionellosis cases in France (9). Bacteria of the genus Legionella are hydrotelluric and are found in natural as well as in artificial aquatic environments. The most frequently identified sources of legionellosis cases are hot water system networks, air conditioning systems and cooling towers (9). Bacteria in nuclear power plant cooling circuits can find suitable conditions for their survival and growth. Although circuit design is not conducive to the development of Legionella (due to water velocity, little backwater, etc.), the presence of nutrients (from suspended solids, organic matter, etc.), favourable growth temperatures (30 to 50°C for hot parts and 18 to 38°C for cold parts), the presence of oxygen, and the presence of biofilms and protozoa can provide a suitable environment for the development of these bacteria. Even if the cooling towers in nuclear power plants in France have never been implicated in legionellosis cases, regulatory monitoring of Legionella concentrations in cooling circuit water was established in France in 2004. This involves counting culturable Legionella spp. and L. pneumophila using the French Standard methodology (3) followed by serogroup determination (1 or 2 to 14) by latex agglutination (16, 18). If the concentrations are above the regulatory thresholds, corrective actions, such as disinfection procedures, are required. Thus, in some cooling circuits, chemical treatment with monochloramine is used to limit Legionella proliferation and ensure that the concentration is maintained below the authorised thresholds. Oxidising biocides are characterised by their non-selective attack on microorganisms and by a common chemical feature: production of hydroxyl radicals (•OH), which are able to oxidise and mineralise almost any organic molecule, yielding CO2 and inorganic ions (25). Killing by active chlorine compounds proceeds in three steps: (i) formation of a chlorine cover (i.e. covalent N-Cl bonds) on the surface of the microbes, which affects virulence but not viability; (ii) penetration through cell barriers and (iii) destruction of important cell components, such as proteins responsible for bacterial transport, respiration and substrate dehydrogenation (2, 20). The rate of penetration can vary to a large degree for the same agent, mainly depending on the cell wall structure of bacteria. Gram-negative bacteria have higher susceptibility to monochloramine than Gram-positive bacteria, as demonstrated by Arnitz et al. (2); however, the specific mode of action of monochloramine on bacterial cells is not well known. Laboratory studies have shown that monochloramine does not severely damage the cell envelope or affect nucleic acid function; it reacts rapidly with only four amino acids (cysteine, cystine, methionine and tryptophan) and very slowly with DNA or RNA (20). In addition to the reactivity of the oxidant, the physiological state of the bacteria can influence the efficiency of bacterial inactivation by the oxidant (27). Monochloramine treatment is effective in reducing Legionella colonisation in water systems (16), such as in nuclear power plant cooling circuits (unpublished data). In these systems, monochloramine treatment is able to reduce culturable Legionella concentrations to below the enumeration method’s detection limit (500 CFU L−1). However, during disinfection, Legionella bacteria can still be detected at low concentrations and rapid re-colonisation in cooling circuits, as in other man-made water systems, can be observed after treatment has ceased (12, 18). The survival of Legionella bacteria in water systems during treatment could be linked, in part, to the presence of protozoa (1, 8, 31). Their interaction allows Legionella to persist for long periods of time in the presence of biocide (1, 31). Thomas et al. (31) suggested that amoebae act as reservoirs for L. pneumophila and allow the rapid re-colonisation of water systems once treatment is interrupted. Biofilms are suspected to be the primary source of microorganisms in drinking water distribution systems. It has been shown that disinfection with biocides, such as chlorine dioxide and chlorite, can reduce the concentrations of planktonic bacteria, but has little or no effect on the concentrations of biofilm bacteria (17). Cooper et al. (12) showed that L. pneumophila biofilms were able to survive for 28 days when exposed to chlorine treatment at a concentration of 50 mg L−1. Another study performed on a pilot-scale water distribution system found that monochloramine did not deter L. pneumophila from accumulating in biofilms (22). However, monochloramine, and its low reactivity with biofilm polymers, has a better penetration into biofilms than free chlorine and is therefore more effective in eradicating Legionella in biofilm (23). Other studies have suggested that disinfection efficacy could be affected by microbial community diversity and, in turn, that the disinfection strategy could influence microbial diversity (8). For example, Pryor et al. (26) performed a study on biofilms from a water distribution system and showed that the use of monochloramine induces a larger decrease in Legionella diversity than free chlorine, confirming the high efficiency of monochloramine against Legionella in biofilm. Another hypothesis that could explain the persistence of Legionella in cooling circuits during treatment is the selection, by monochloramine, of Legionella strains that are more tolerant to this biocide (18). Although the consensus view is that chlorinated biocide usage does not induce bacterial resistance, the selection of intrinsically-tolerant strains by monochloramine cannot be excluded. Thus, it is necessary to determine the intrinsic susceptibility of Legionella strains isolated from cooling circuits, and to compare the susceptibility of strains isolated from non-treated cooling circuits with those from treated systems. To achieve this objective, an in vitro approach, based on the Chick and Watson model (11, 33), was developed to determine Ct99.9% values, the product of monochloramine concentration and the contact time necessary to observe a 3-log reduction in bacterial concentration. Ct values are directly proportional to bacterial inactivation rates. They represent the susceptibility of bacteria to the biocide under defined experimental conditions. The inactivation rates of bacteria with biocide, and the Ct values, are influenced by experimental parameters. An original approach, using response surface methodology (RSM) combined with a multifactorial experimental design, which is a mathematical method for designing experiments, building models, evaluating the effects of variables and searching optimum conditions of variables to predict responses, was used to obtain the optimum inactivation conditions in terms of temperature, pH, initial bacteria and biocide concentrations. Treating each factor separately would be very time-consuming. Furthermore, if several factors were to play a role, their interactions would not be discernible even if they were dominant. Hence, the application of an adequate experimental design is the optimal strategy to obtain maximum information with a minimum number of experiments. Moreover, RSM can provide an empirical model of the disinfection kinetics, based on the diverse variables of interest. With the aim of determining the intrinsic susceptibility of Legionella strains, the disinfection kinetics of monochloramine on Legionella bacteria isolated from various treated or non-treated cooling circuits was investigated. Their susceptibilities were compared with those of bacteria taken from reference collections (Legionella and non-Legionella strains).

Materials and Methods

Bacterial strains and culture conditions

A set of 39 L. pneumophila strains was used to evaluate their susceptibilities to monochloramine (Table 1). These strains originated from water or biofilms and were isolated from a river, upstream or downstream from a nuclear power plant, or directly from various cooling circuits in nuclear power plants located in France. These cooling circuits were either non-treated or treated with monochloramine. L. pneumophila strains from the treated circuits were isolated over the course of the treatment and beyond or between two disinfection stages.
Table 1

Strains selected (non-Legionella bacteria, Legionella species, and environmental L pneumophila strains) for the determination of their susceptibility to monochloramine.

StrainSerogroupIRS-PCRYear of samplingLocationOriginal matrixNH2Cl
Non-Legionella bacteria

Escherichia coliATCC 10536
Staphylococcus aureusATCC 6538
Lactobacillus brevisCIP 103474
Corynebacterium glutamicumATCC 13032
Pseudomonas fluorescens*

Legionella bacteria

Reference strains

Legionella pneumophilaATCC 331527L1
Legionella pneumophilaATCC 338231R1
Legionella feeleiiATCC 35849BJ1
Legionella longbeachaeATCC 334842V1
Legionella jordanisATCC 33623AM1
Legionella birminghamensisATCC 43702AN1
Legionella hackeliaeATCC 35250AC1
Legionella londiniensisATCC 49505AG1
Legionella erythraATCC 35303AR1
Legionella cincinnatiensisATCC 43753AP1
Legionella israelensisATCC 43119AO1
Legionella tusconensisATCC 49180AD1
Legionella maceacherniiATCC 35300AE1
Legionella bozemanaeATCC 355452N1

Environmental L. pneumophila strains

 Qee 400Lp1Q22005Cooling circuitWater
 Qee 403Lp1Q32005Cooling circuitWater
 Qee 527Lp1AB102005Cooling circuitWater
 Qee 529Lp1A42005Cooling circuitWater
 Qee 531Lp2 to 14A42005Cooling circuitWater
 Qee 532Lp2 to 14AB102005Cooling circuitWater
 Qee 533Lp2 to 14Q22005Cooling circuitWater
 Qee 534Lp2 to 14Q32005Cooling circuitWater
 Qee 766Lp1Y22008Cooling circuitWater
 Qee 773Lp1Y22008Cooling circuitBiofilm
 Qee 1825Lp2 to 14G22009Cooling circuitBiofilm
 Qee 1837Lp2 to 14G22009Cooling circuitBiofilm
 Qee 1885Lp1A32009Cooling circuitWater
 Qee 2343Lp1AB82009Cooling circuitWater+
 Qee 4195Lp2 to 14G22009Cooling circuitWater
 Qee 4595Lp2 to 14J22005Cooling circuitWater+/−
 Qee 4596Lp1AW62005Cooling circuitWater+/−
 Qee 5008Lp1AB82006Cooling circuitWater+
 Qee 5354Lp2 to 14J52007Cooling circuitWater
 Qee 5869Lp2 to 14G22010Cooling circuitWater
 Qee 5874Lp1G22010Cooling circuitWater
 Qee 6048Lp1AW52010Cooling circuitWater+
 Qee 6054Lp2 to 14AW52010Cooling circuitWater+
 Qee 6750Lp1G22010Cooling circuitWater
 Qee 6905Lp2 to 14AB132010Cooling circuitWater
 Qee 6918Lp1AB132010Cooling circuitWater
 Qee 7591Lp2 to 14U12010Cooling circuitWater+/−
 Qee 7592Lp2 to 14AK12010Cooling circuitWater+/−
 Qee 7604Lp2 to 14U12010Cooling circuitWater+/−
 Qee 7605Lp1U12010Cooling circuitWater+/−
 Qee 7614Lp2 to 14AW152010Cooling circuitWater+/−
 Qee 7615Lp2 to 14AB82010Cooling circuitWater+/−
 Qee 7748Lp2 to 14S12010UpstreamWater
 Qee 7830Lp2 to 14AW62010DownstreamWater+
 Qee 7831Lp2 to 14AW62010Cooling circuitWater+
 Qee 7841Lp2 to 14Q72010UpstreamWater
 Qee 7842Lp2 to 14Q72010DownstreamWater+
 Qee 10246Lp1G22011Cooling circuitWater
 Qee 10420Lp2 to 14G22011Cooling circuitWater

− Strain isolated from a non-treated cooling circuit

+ Strain isolated from a cooling circuit treated continuously with monochloramine

+/− Strain isolated from a cooling circuit treated sequentially with monochloramine and between two treatment phases

Environmental origin

To compare the susceptibility of L. pneumophila with that of other Legionella species, 14 strains of Legionella non-pneumophila from reference collections (the American Type Culture Collection, ATCC, and the French Pasteur Institute Collection, CIP) were used (see Table 1). Susceptibilities of bacteria belonging to the genus Legionella were also compared with those of other bacteria belonging to non-Legionella genera. These non-Legionella strains belonged to Gram-negative and Gram-positive groups and were used to screen a wide range of susceptibilities. All the strains were precultured in the laboratory before their use in inactivation studies. To limit the variability in the physiological state of bacteria, the incubation time necessary to attain the stationary state was observed depending on species. Legionella spp. strains were cultured on BCYE media supplemented with l-cysteine, and L. pneumophila on GVPC (Oxoid Microbiology Products, Cambridge, England), for four days at 37±2°C. Escherichia coli, Pseudomonas fluorescens and Corynebacterium glutamicum were cultured on R2A, Cetrimide medium and blood agar, respectively (Oxoid Microbiology Products), at 30±2°C for two days. Staphylococcus aureus and Lactobacillus brevis were cultured on Baird Parker and MRS media (Oxoid Microbiology Products, Thermo Fisher Scientific, Waltham, Massachusetts, USA) respectively, for two days at 37±2°C. After culture, colonies were suspended in sterile phosphate buffer (100 mM, pH 7.5) before disinfection treatment. The concentration was adjusted by A595 measurement at 595 nm (one A595nm unit = 109 cells mL−1). Legionella strains isolated from the environment were subjected to comprehensive identification. Their genera, species and serogroups were identified using culture methods and latex agglutination in accordance with the AFNOR Standard method (3). The mip gene was sequenced to confirm the species identification (28) and a molecular typing method, the Infrequent-Restriction-Site PCR (IRS-PCR), was used to discriminate among L. pneumophila sub-populations (21).

Monochloramine disinfection assays

Monochloramine was prepared by combining a predetermined volume of sodium hypochlorite to ammonia solution with a chlorine to nitrogen mass ratio of 4.8 and pH 8.3. Stock solutions of monochloramine at 1 g L−1 were stored at 4°C. Monochloramine concentrations were determined at the beginning and end of each assay using the DPD (N,N’-diethyl-p-phenylenediamine) (HACH Company, Loveland, Colorado, USA) colorimetric method in accordance with the manufacturer’s procedures. Disinfection assays were performed by inoculating 108 to 1011 bacteria per liter and 0.7 to 1 ppm monochloramine in sterile phosphate buffer (100 mM, pH 7.5). Samples were incubated at a controlled temperature (25°C–35°C) and pH (7.5–8.5) and were continuously agitated by magnetic stirring. The survival of the bacteria was analysed after 0, 5, 10, 15, 20, 25, 30, 45 and 60 min of treatment. Longer treatment was performed (90 to 120 min) on less susceptible strains. Samples were then treated with sterile sodium thiosulfate (20 mg L−1) to quench the monochloramine residual. Ten-fold serial dilutions were plated on the appropriate medium. The detection limit of the culture was 104 CFU L−1. Bacterial concentrations were determined after a five-day culture for non-Legionella bacteria and after a ten-day culture for Legionella bacteria at the appropriate temperature. Disinfection assays were performed in triplicate for non-Legionella bacteria and only once for Legionella bacteria as the coefficient of variation of the method was determined for this genus (19%). For each experiment, a disinfectant consumption control without microorganisms and a bacterial survival control without biocide were performed to evaluate the stability of the biocide and the natural survival of the bacteria. Experimental parameters, including temperature, pH, initial biocide and bacterial concentrations, were determined using a factorial design experiment combined with the RSM.

Ct determination

Ct values were determined according to the Chick and Watson expression (11, 33), , where N is the initialnumber of culturable cells, N is the number of culturable cells after time t of disinfection exposure, k is the rate constant for a specific microorganism and set of conditions, C is the disinfectant concentration and n is the coefficient of biocide activity depending on the type of biocide and experimental variables. Microorganism susceptibility was quantified by Ct (in mg·min−1 L−1). As frequently used in the literature, Ct values were calculated in our study for 3-log inactivation (Ct99.9%) (2, 15). The time necessary to inactivate 99.9% (t99.9%) of the bacteria was calculated by linear regression of the curve . The Ct value was the mathematical product of t99.9% and the initial concentration of monochloramine.

Development and optimisation of the method using the multifactorial experimental design and RSM

A multifactorial experimental design, combined with an RSM, was used to validate the microorganism susceptibility determination method. Two criteria, also called responses of the multifactorial experimental design, were chosen: (i) a significant reduction of the bacterial concentration (3-log bacterial reduction minimum) in approximately 30 min (Y1=t99.9%=30 min) and (ii) to ensure a minimal effect of the experimental variables on the effectiveness of the monochloramine, i.e. Y2=n=1. Four factors affecting the two responses, which would be easily controllable in the laboratory, were selected: temperature (X1), pH (X2), initial monochloramine concentration (X3) and initial bacterial concentration (X4). The four process parameters were added at two levels: low (−1) and high (+1). The low and high levels were chosen based on knowledge of the physicochemical characteristics of cooling waters with regard to temperature and pH, and the ability to obtain a rapid and detectable decay for monochloramine and bacterial concentration (Table 2). The central values (zero level) chosen were: T°=30°C, pH=8.0, [NH2Cl]=0.85 ppm and [bacteria]=3×109 cells L−1. To develop the regression equation, the test variables were coded according to the following equation: where Xi is the coded value for the independent variable, x is the real value of the independent variable, χ̄ is the real value of the independent variable at the centre point and Δx is the value of the step change. The response variables were fitted using a first order model in order to correlate response variables to the independent variables. The general form of the equation is:
Table 2

Multifactorial experimental design matrix and measured responses for optimisation of experimental conditions (temperature, pH, [NH2Cl], [bacteria]).

Run orderExperimental conditionsMeasured responses


X1X2X3X4Y1Y2





Temperature °CpH[NH2Cl] ppm[bacteria] t0 cells mL−1t99.9% minn
1+ 135+ 18.5+ 11+ 1101197.71−2.22
2+ 135+ 18.5+ 11−110823.751.1134
3+ 135+ 18.5−10.7+ 1101144.18−2.22
4+ 135+ 18.5−10.7−110835.331.1134
5+ 135−17.5+ 11+ 1101158.64.81
6+ 135−17.5+ 11−110818.60.81
7+ 135−17.5−10.7+ 11011326.14.81
8+ 135−17.5−10.7−110824.80.81
9−125+ 18.5+ 11+ 110113750−6.9
10−125+ 18.5+ 11−1108198.67−1.81
11−125+ 18.5−10.7+ 11011319.15−6.9
12−125+ 18.5−10.7−1108104.16−1.81
13−125−17.5+ 11+ 1101129.12−0.06
14−125−17.5+ 11−110812.941.1
15−125−17.5−10.7+ 1101128.5−0.06
16−125−17.5−10.7−110819.21.1

17030−17.5+11−0.3310935.631.51
18030−17.5−0.330.8−0.3310949.921.51
where Y refers to the measured response, X, X, X and X to the independent coded variables, b to the offset term, b, b, b and bl to the linear effects and b, b and b to the interaction terms, and n corresponds to the number of studied factors. The multifactorial experimental design for four independent variables, each at two levels, consisted of 16 experiments, which permitted the determination of the b terms. Two additional experiments enabled model validation (Table 2). For each experiment, Y1=t99.9% was measured as described in the previous section and Y2=n was calculated from the t99.9% measured by pair tests where only the monochloramine concentration varied as below: After modelling the responses, the RSM used a graphical representation to visualise the relationship between the response and the experimental levels of each variable to deduce the optimum conditions. Three-dimensional graphs were generated for the pairwise combination of two factors, while the other two were maintained at the extreme level (−1 or +1). The combination of optimum values reported for each interaction allowed us to determine the optimal experimental values for the method. To validate the defined protocol, a reproducibility study was performed by independently testing the reference L. pneumophila strain ATCC 33152 eleven times. Method reproducibility was high, as the coefficient of variation determining the method error was 19% (data not shown).

Results

Protocol development using the multifactorial experimental design and RSM

The multifactorial experimental design was used to determine the optimum conditions, including temperature (X1), pH (X2), monochloramine (X3) and bacterial (X4) concentrations, to observe a 3-log bacterial reduction in approximately 30 min (Y1) and to optimise monochloramine activity (Y2). Sixteen experiments (runs n° 1 to 16) were then performed using the reference L. pneumophila strain ATCC 33152 and responses were experimentally determined (Table 2). Models were constructed to evaluate the effects of the parameters on responses: To ensure their predictions, these models were tested under various experimental conditions, as shown in Table 2 (runs 17 and 18). Responses Y1 and Y2 were defined according to developed models (predicted responses) and experimental results (measured responses). For experimental conditions 17 and 18, predicted responses Y1 were 25.71 and 58.21 min, respectively, while measured responses Y1 were 35.63 and 49.92 min, respectively. For the pair of conditions 17 and 18, the predicted response Y2 was 1.43, whereas the measured response was 1.51. The residuals between predictive and real response values were low (less than 10 min for Y1 and less than 0.1 for Y2), meaning that the models could be validated. The models developed in our study showed that all four variables, and their interactions, affect the contact time required to inactivate 99.9% of the bacteria (Fig. 1A), whereas only the temperature, pH and bacterial concentration, and their interactions, affect monochloramine efficiency (Fig. 1B). All experimental parameters had an impact on the t99.9% with the same order of magnitude but, interestingly, the greatest effect on the response was not associated with any of the parameters tested, meaning that unmeasured experimental factors have a significant impact on the t99.9%. Temperature has a systematic negative effect on the response, whereas others parameters positively influence the t99.9%. Although almost all are equivalent, among the measured parameters, the combination of pH and temperature has the greatest influence on the time required to inactivate 3-log units of bacterial concentration. The efficiency of monochloramine is mostly influenced by pH and temperature, but in a converse manner, as pH affects monochloramine activity negatively and temperature affects it positively.
Fig. 1

Bar graphs showing the standardised estimated effects of the variables tested against the time needed to inactivate 3-log units of bacteria (A) and the activity of monochloramine represented by the n factor (B) during disinfection assays with monochloramine. The variables tested were temperature, pH, initial monochloramine and bacterial concentrations. Standardised estimated effects correspond to the proportion of each estimated effect (absolute value) relative to the sum of all estimated effects.

RSM was applied to define the optimal conditions for monochloramine inactivation of bacteria. Optimum levels of temperature, pH, monochloramine and bacterial concentrations were determined by plotting response surface profiles against any two independent parameters, while keeping the other two at the extreme level (“−1” and “+1”). Thus, for one response, eight profiles were used within all possible combinations, to determine the optimal values of the four variables. Fig. 2 illustrates four profiles for the Y1 response surface plot in the optimisation of variables X1 and X2. For each profile, the optimal region was determined through visual inspection of the response surface plot. Optimal regions for Y1=30 min were combined to determine the solution interval of each variable. The solution intervals of each variable for Y2=1 were determined using the same methodology. The optimal values of temperature (X1), pH (X2), biocide (X3) and bacterial (X4) concentrations were then selected within the common interval of the two optimal regions computed for Y1=30 min and Y2=1. All of the curves used to optimise the variables are available as supplementary material. Indeed, the X1 level (temperature) needed to be between [−0.6; −0.2] or [0.8; +1], equivalent to [27; 29°C] or [34; 35°C]. The pH level (X2) was between 7.5 and 7.55. The initial concentration of monochloramine (X3) needed to be between 0.82 and 1.00 mg L−1. The initial bacterial concentration (X4) was between 2×108 and 8×108 CFU L−1. Our experimental conditions were then arbitrarily chosen from within the optimal intervals: T°=28°C, pH=7.5, [NH2Cl]0=0.9 mg L−1 and N0=5×108 CFU L−1. The predicted and measured responses with these values were in agreement (data not shown).
Fig. 2

Response surface plots and contour plots of interactions between temperature and pH, while the other two variables (bacterial and biocide concentrations) are maintained at extreme levels, against the time necessary to inactivate 3-log units of bacteria, Y1=t99.9%.

Susceptibilities of selected bacteria to monochloramine biocide

The aim of this study was to determine the susceptibilities of Legionella strains isolated from nuclear power plant cooling circuits under different disinfection conditions, and to compare these susceptibilities with those of reference strains, whether or not they belonged to the genus Legionella. The Ct99.9% was measured, using the protocol defined by the multifactorial experimental design and the RSM, for non-Legionella bacteria and for L. pneumophila strains from the reference collections. Among the non-Legionella bacteria, E. coli was the most sensitive strain with a Ct99.9% value of 10.3±1.67 mg·min L−1 followed by C. glutamicum (Ct99.9%=16.84±1.18 mg·min L−1), P. fluorescens (Ct99.9%=22.19±3.04 mg·min L−1), L. brevis (Ct99.9%=48.67±1.43 mg·min L−1) and S. aureus, which presented the lowest sensitivity with a Ct99.9% value of 54.06±9.21 mg·min L−1 (Fig. 3A).
Fig. 3

Reduction of non-Legionella bacteria (A) and Legionella pneumophila ATCC 33152 and ATCC 33823 (B) culturability after monochloramine treatments. Bars represent standard errors of the means of the three independent experiments.

The two L. pneumophila reference strains, ATCC 33823 and ATCC 33152, showed the same inactivation kinetics and presented equivalent sensitivity against monochloramine (Fig. 3B). With Ct99.9% values of 22.24±4.22 mg·min L−1 for the strain ATCC 33152 and 24.08±4.57 mg·min L−1 for strain ATCC 33823, the L. pneumophila species presented moderate sensitivity compared to other Legionella species and other non-Legionella strains (Fig. 4). Interestingly, the sensitivity of strains belonging to the genus Legionella extended to the widest range. Indeed, L. tusconensis was the most susceptible species (Ct99.9%=9.17±1.74 mg·min L−1) and was about seven times more susceptible than L. cincinnatiensis (Ct99.9%= 68.15±0.67 mg·min L−1).
Fig. 4

Ct99.9% values after monochloramine treatment of non-Legionella and Legionella strains from the reference collections. Bars represent standard errors of the method (19%), except for non-Legionella bacteria and L. hackeliae and L. cincinnatiensis, for which bars represent standard errors of the mean of three independent experiments.

The Ct99.9% values of the environmental L. pneumophila strains ranged between 16.14±3.07 mg·min L−1 and 64.88±19.07 mg·min L−1 (Fig. 5). The susceptibilities of the environmental strains matched the susceptibilities of the non-Legionella bacteria, situated between the susceptibilities of L. tusconensis and L. cincinnatiensis. As shown in Fig. 5, a ranking of strains based on their Ct99.9% values did not reveal characteristics that would be able to explain their susceptibilities. Indeed, it appeared that the susceptibilities of the environmental L. pneumophila strains were not linked to either their geographical origin (geographical location of the plant and their location upstream, inside or downstream from the plant) or to their initial matrix (water or biofilm) or serogroup identification (1 or 2 to 14). Moreover, the treatment phase (with, without or between two monochloramine treatment phases) did not have any impact on Legionella susceptibility, meaning that the use of monochloramine in the cooling circuit would not select monochloramine-tolerant strains.
Fig. 5

Ct99.9% values after monochloramine treatment of environmental Legionella pneumophila strains isolated during various treatment conditions (− without treatment, + during treatment, +/− between two treatment phases) and identified by the IRS PCR method. Strains were collected from water or biofilm; upstream, inside or downstream from the cooling circuits. Tags represent the treatment condition during strains isolation.

Interestingly, Ct99.9% values followed a normal distribution except for the three most tolerant strains. These three strains presented high Ct99.9% values (61.74±11.73; 62.09±10.72 and 64.88±19.07 mg·min L−1) and were statistically more tolerant than the other environmental L. pneumophila strains (Grubbs test, α=0.05). Their susceptibilities were higher than those of the non-Legionella bacteria, S. aureus (54.06±9.21 mg·min L−1) and L. brevis (48.67±1.43 mg·min L−1), but lower than that of L. cincinnatiensis (68.15±0.67 mg·min L−1). Interestingly, these three strains belonged to IRS-PCR type G2 and were isolated from various matrices and power plants that were not treated with monochloramine biocide. These three strains were subject to SBT typing (28) and were not identical according to their sequence types (data not shown). Other strains belonging to the IRS-PCR type G2 were tested but they presented moderate Ct99.9% values, between 26.31±1.18 and 31.46±7.08 mg·min L−1; indicating that tolerance to monochloramine is not a characteristic of the entire G2 type. Moreover, no other links between L. pneumophila identification (serogroups and IRS-PCR types) and their monochloramine susceptibilities were observed during this study.

Discussion

This study was performed to define the intrinsic susceptibility of L. pneumophila strains isolated from cooling circuits during different disinfection processes, and to determine whether biocide usage in artificial systems could select biocide-tolerant Legionella. To define bacterial monochloramine susceptibility, an in vitro method to determine Ct99.9% values was developed. Ct99.9% values are defined as the mathematical product of the biocide concentration (mg L−1) and time (minutes) required to inactivate 3-log units of bacterial concentration. The Ct parameter reflects the natural susceptibility of bacteria to the biocide (11, 33), although it is highly sensitive to experimental conditions (29). To develop a robust and reproducible method, optimum laboratory conditions, in terms of the temperature, pH, monochloramine and bacterial concentrations, were established based on a multifactorial experimental design combined with RSM. The parameters were optimised to meet two method validation criteria: (i) to observe a 3-log unit decay of Legionella in approximately 30 minutes and (ii) to retain significant monochloramine activity. This original approach appears to be ideal for obtaining a maximum of information with a minimum number of experiments. The temperature, pH and initial bacterial concentration appeared to have a significant effect on Legionella susceptibility to monochloramine. The temperature and pH, when combined, had a greater effect on the inactivation speed than when observed individually. In both cases, the effects of these two parameters were the reverse. Increasing the temperature had a negative effect on the 99.9% inactivation time and a positive effect on monochloramine activity, whereas increasing the pH presented a positive effect on the 99.9% inactivation time and a negative effect on monochloramine activity. Although experimental condition effects are generally measured based on Ct values, these results were in agreement with those observed in past studies. Thus, studies on Cryptosporidium parvum inactivated with monochloramine, at a constant concentration, have shown that pH has a positive effect on Ct values, whereas temperature presents a negative effect (14, 29). Modelling of the experimental outcomes showed that the 99.9% inactivation time was dependent on other unmeasured parameters. The effect of these unknown factors seemed to be significant and should be studied more thoroughly in order to identify factors that could modulate monochloramine efficiency under laboratory conditions (physiological status of bacteria, free chlorine and other chloramine residuals). The protocol defined by the multifactorial experimental design and RSM was used to determine the intrinsic susceptibility of L. pneumophila strains isolated from various nuclear power plant cooling circuits during different treatment processes. The Ct99.9% values of these strains were compared with those of non-Legionella and Legionella species from the reference collections. For non-Legionella bacteria, monochloramine susceptibility was ordered as follows (from the most to the least susceptible strain): E. coli < C. glutamicum < P. fluorescens < L. brevis < S. aureus. Thus, except for C. glutamicum, it appeared that monochloramine susceptibility was linked to Gram stain characteristics. Gram-negative bacteria presented lower Ct99.9% values than Gram-positive bacteria. This is consistent with previous studies, which have shown that Gram-negative bacteria are generally more susceptible than Gram-positive bacteria. This is a result of the better penetration of monochloramine in Gram-negative bacteria than in Gram-positive bacteria (2, 32). C. glutamicum, a Gram-positive bacterium, exhibited a Ct99.9% value between those for Gram-negative bacteria. This bacterium belongs to the suborder Corynebacterineae, in which Mycobacterium and Norcardia genera are also present. These three genera are known to produce a particular and complex cell envelope, containing various lipid species, as well as mycolic acid residues covalently linked to arabinogalactan which, in turn, is linked to peptidoglycan (4). Interestingly, in the literature, studies of the effectiveness of monochloramine on other Corynebacterineae have revealed a strong inter-species variability of susceptibility as M. avium revealed high resistance to monochloramine, whereas M. terrae appeared very sensitive (7, 24, 30). This inter-species variability of monochloramine susceptibility was also observed among Legionella species. Indeed, among selected strains from the reference collections, L. tusconensis was the most susceptible strain, whereas L. cincinnatiensis was the least susceptible. While all species of Legionella exhibited Ct99.9% values within the same range as other Gram-negative bacteria, surprisingly, L. cincinnatiensis presented a Ct99.9% value higher than that of the Gram-positive S. aureus strain. L. pneumophila strains isolated from the environment also showed a high degree of variability in terms of their monochloramine susceptibilities. These strains were more susceptible than Gram-positive bacteria, except for three strains which were less susceptible than Gram-positive bacteria but more than L. cincinnatiensis. These three strains belonged to IRS-PCR type G2 but were not identical according to their SBT profiles. Other G2 strains showed moderate monochloramine susceptibilities, suggesting that the observed monochloramine tolerance might be a characteristic of a subgroup of the whole G2 type. Bacterial susceptibility and tolerance to monochloramine could be explained by different membrane compositions (13) or cell responses to biocide exposure (6). To investigate these hypotheses, first it would be useful to better characterise the mode of action of monochloramine on bacterial cells and to determine which sites in the cell are the most affected by the biocide. Membrane characterisation of susceptible and tolerant L. pneumophila strains could be very informative on biocide susceptibility. Secondly, a study investigating the cellular response of bacterial cells to the presence of monochloramine would allow a better understanding of the mechanisms involved in bacterial tolerance. Such a study could be performed by analysing and comparing the transcriptomic responses of susceptible and tolerant strains. Berry et al. (6) have defined, by performing a comparative transcriptomic analysis of the response of E. coli to monochloramine, a core set of genes responsible for increased tolerance to stresses, known as the “stressome”. Identifying and comparing the gene expression involved in bacterial tolerance between susceptible and non-susceptible strains would aid our understanding of susceptibility variations within the same bacterial species, as in the case of L. pneumophila species isolated from cooling circuits. Although environmental L. pneumophila biocide susceptibility was found to cover a wide range of Ct99.9% values, the results from this study suggest that monochloramine usage in nuclear power plant cooling circuits does not select more tolerant strains. Indeed, their susceptibilities were not ranked according to the treatment conditions during their isolation. These results are in agreement with those of Garcia et al. (18), who performed a long-term environmental monitoring study of Legionella persistence in chlorinated systems. The authors showed, by measuring the minimum inhibitory and bactericidal concentrations (MIC and MBC), that biocide usage in water systems does not increase the tolerance of Legionella strains. Moreover, despite the higher tolerance of some strains, considering the concentration of monochloramine used during the cooling circuit disinfection process (0.25±0.05 mg L−1), under these conditions, the theoretical time required to inactivate 99.9% of Legionella is approximately four hours. Given that the minimum residence time of bacteria in cooling circuits is approximately six hours, this shows that the disinfection process used to eradicate Legionella bacteria in nuclear power plant cooling circuits is efficient. Thus, the detection of Legionella bacteria during monochloramine treatment, and the rapid re-colonisation of nuclear power plant cooling circuits after a disinfection process, cannot be explained by the selection of strains that are naturally more biocide-tolerant. These phenomena could be explained by the presence of viable but not culturable Legionella in water systems, or the protection by biofilm location or by higher organisms (such as amoebae) (1, 31). L. pneumophila could persist in the VBNC state after biocide treatment (1, 5). This low metabolic activity state could be responsible for the failure to culture viable L. pneumophila from treated circuits. Under favourable conditions, VBNC bacteria can recover their culturability and their ability to grow in cooling circuits. Also, Legionella bacteria can be internalised into higher organisms, such as amoebae, wherein they are protected from the action of biocide (1, 31). Legionella hosts probably act as reservoirs for L. pneumophila, allowing rapid re-colonisation of the water system once the treatments are interrupted. Another possible explanation is protection based on biofilm location. Biofilms are known to reduce biocide efficiency by acting as a physical barrier to biocide penetration (12, 17, 22). The salting-out of biofilm bacteria in the water phase could explain the detection of Legionella during treatment and the rapid re-colonisation of cooling circuits. Moreover, post-amoebic and sessile Legionella exhibit a different phenotype than planktonic Legionella, enhancing their tolerance to biocide through the synthesis of proteins involved in oxidative stress (10, 19). In conclusion, this study showed that monochloramine usage in nuclear power plant cooling circuits does not induce selection pressure leading to the persistence of tolerant Legionella bacteria. Although Legionella are sometimes still detectable at low concentrations during the treatment process, and although the cooling circuits are often rapidly re-colonised after treatment has ceased, disinfecting these water systems with monochloramine is effective and is not related to re-colonisation. The origin of these phenomena remains unclear and they may be caused by environmental factors such as biofilm location and protozoa protection.
  28 in total

Review 1.  Cellular impermeability and uptake of biocides and antibiotics in Gram-negative bacteria.

Authors:  S P Denyer; J-Y Maillard
Journal:  J Appl Microbiol       Date:  2002       Impact factor: 3.772

2.  Investigation of opportunistic pathogens in municipal drinking water under different supply and treatment regimes.

Authors:  M Pryor; S Springthorpe; S Riffard; T Brooks; Y Huo; G Davis; S A Sattar
Journal:  Water Sci Technol       Date:  2004       Impact factor: 1.915

3.  A Note on the Variation of the Rate of Disinfection with Change in the Concentration of the Disinfectant.

Authors:  H E Watson
Journal:  J Hyg (Lond)       Date:  1908-09

4.  Detection of viable Legionella pneumophila in water by polymerase chain reaction and gene probe methods.

Authors:  A K Bej; M H Mahbubani; R M Atlas
Journal:  Appl Environ Microbiol       Date:  1991-02       Impact factor: 4.792

5.  Role of disinfectant concentration and pH in the inactivation kinetics of Cryptosporidium parvum oocysts with ozone and monochloramine.

Authors:  J L Rennecker; J H Kim; B Corona-Vasquez; B J Mariñas
Journal:  Environ Sci Technol       Date:  2001-07-01       Impact factor: 9.028

6.  Kinetics of membrane damage to high (HNA) and low (LNA) nucleic acid bacterial clusters in drinking water by ozone, chlorine, chlorine dioxide, monochloramine, ferrate(VI), and permanganate.

Authors:  Maaike K Ramseier; Urs von Gunten; Pietro Freihofer; Frederik Hammes
Journal:  Water Res       Date:  2010-11-18       Impact factor: 11.236

7.  Sequence-based classification scheme for the genus Legionella targeting the mip gene.

Authors:  R M Ratcliff; J A Lanser; P A Manning; M W Heuzenroeder
Journal:  J Clin Microbiol       Date:  1998-06       Impact factor: 5.948

8.  Microbicidal activity of monochloramine and chloramine T compared.

Authors:  R Arnitz; M Nagl; W Gottardi
Journal:  J Hosp Infect       Date:  2009-08-31       Impact factor: 3.926

9.  Amoebae in domestic water systems: resistance to disinfection treatments and implication in Legionella persistence.

Authors:  V Thomas; T Bouchez; V Nicolas; S Robert; J F Loret; Y Lévi
Journal:  J Appl Microbiol       Date:  2004       Impact factor: 3.772

10.  Validation of IRS PCR, a molecular typing method, for the study of the diversity and population dynamics of Legionella in industrial cooling circuits.

Authors:  D Jakubek; M Le Brun; G Leblon; M Dubow; M Binet
Journal:  Lett Appl Microbiol       Date:  2012-12-03       Impact factor: 2.858

View more
  5 in total

1.  Legionella: A Promising Supplementary Indicator of Microbial Drinking Water Quality in Municipal Engineered Water Systems.

Authors:  Chiqian Zhang; Jingrang Lu
Journal:  Front Environ Sci       Date:  2021-11-10

2.  Hospital water and opportunities for infection prevention.

Authors:  Brooke K Decker; Tara N Palmore
Journal:  Curr Infect Dis Rep       Date:  2014-10       Impact factor: 3.725

3.  Survivability of Microbes in Natural Environments and Their Ecological Impacts.

Authors:  Shin Haruta; Nanako Kanno
Journal:  Microbes Environ       Date:  2015       Impact factor: 2.912

4.  A comprehensive evaluation of monochloramine disinfection on water quality, Legionella and other important microorganisms in a hospital.

Authors:  Darren A Lytle; Stacy Pfaller; Christy Muhlen; Ian Struewing; Simoni Triantafyllidou; Colin White; Sam Hayes; Dawn King; Jingrang Lu
Journal:  Water Res       Date:  2020-11-18       Impact factor: 11.236

5.  Rediscovery of the microbial world in microbial ecology.

Authors:  Shin Haruta
Journal:  Microbes Environ       Date:  2013       Impact factor: 2.912

  5 in total

北京卡尤迪生物科技股份有限公司 © 2022-2023.