Literature DB >> 23836796

Magnetic field measurements near stand-alone transformer stations.

Shaiela Kandel1, Ronen Hareuveny, Nir-Mordechay Yitzhak, Raphael Ruppin.   

Abstract

Extremely low-frequency (ELF) magnetic field (MF) measurements around and above three stand-alone 22/0.4-kV transformer stations have been performed. The low-voltage (LV) cables between the transformer and the LV switchgear were found to be the major source of strong ELF MFs of limited spatial extent. The strong fields measured above the transformer stations support the assessment method, to be used in future epidemiological studies, of classifying apartments located right above the transformer stations as highly exposed to MFs. The results of the MF measurements above the ground around the transformer stations provide a basis for the assessment of the option of implementing precautionary procedures.

Mesh:

Year:  2013        PMID: 23836796     DOI: 10.1093/rpd/nct170

Source DB:  PubMed          Journal:  Radiat Prot Dosimetry        ISSN: 0144-8420            Impact factor:   0.972


  1 in total

1.  Hazard zoning around electric substations of petrochemical industries by stimulation of extremely low-frequency magnetic fields.

Authors:  Monireh Hosseini; Mohammad Reza Monazzam; Laleh Farhang Matin; Hossein Khosroabadi
Journal:  Environ Monit Assess       Date:  2015-04-16       Impact factor: 2.513

  1 in total