Effect of flow rate and lead/copper pipe sequence on lead release from service lines.

Clément Cartier1, Roger B Arnold, Simoni Triantafyllidou, Michèle Prévost, Marc Edwards.   

Abstract

A pilot experiment examined lead leaching from four representative configurations of service lines including: (1) 100% lead (Pb), (2) 100% copper (Cu), (3) 50% Pb upstream of 50% Cu, and (4) 50% Pb-downstream of 50% Cu using a range of flow rates. The cumulative mass of lead release indicated that a typical partial replacement configuration (50% lead downstream of copper) did not provide a net reduction in lead when compared to 100% lead pipe (85 mg for 50% Pb-downstream versus 83 mg for 100%-Pb) due to galvanic and deposition corrosion. The partially replaced service line configuration also had a much greater likelihood of producing water with "spikes" of lead particulates at higher flow rates, while tending to produce lower levels of lead at very low flow rates. After the first 214 days the galvanic current between copper and lead was only reduced by 34%, proving that galvanic impacts can be highly persistent even in water with optimized corrosion control by dosing of zinc orthophosphate. Finally, this experiment raises concern about the low flow rates used during some prior home sampling events, which may underestimate exposure to lead during normal water use, especially when galvanic Pb:Cu connections are present.
Copyright © 2012 Elsevier Ltd. All rights reserved.

Entities:  

Mesh:

Substances:

Year:  2012        PMID: 22677500     DOI: 10.1016/j.watres.2012.05.010

Source DB:  PubMed          Journal:  Water Res        ISSN: 0043-1354            Impact factor:   11.236


  5 in total

1.  Distribution system water age can create premise plumbing corrosion hotspots.

Authors:  Sheldon Masters; Jeffrey Parks; Amrou Atassi; Marc A Edwards
Journal:  Environ Monit Assess       Date:  2015-08-07       Impact factor: 2.513

2.  Inherent variability in lead and copper collected during standardized sampling.

Authors:  Sheldon Masters; Jeffrey Parks; Amrou Atassi; Marc A Edwards
Journal:  Environ Monit Assess       Date:  2016-02-20       Impact factor: 2.513

3.  Mineralogical Evidence of Galvanic Corrosion in Drinking Water Lead Pipe Joints.

Authors:  Michael K DeSantis; Simoni Triantafyllidou; Michael R Schock; Darren A Lytle
Journal:  Environ Sci Technol       Date:  2018-02-28       Impact factor: 9.028

4.  Long-Term Behavior of Simulated Partial Lead Service Line Replacements.

Authors:  Justin St Clair; Clement Cartier; Simoni Triantafyllidou; Brandi Clark; Marc Edwards
Journal:  Environ Eng Sci       Date:  2016-01-01       Impact factor: 1.907

5.  Tracking reduction of water lead levels in two homes during the Flint Federal Emergency.

Authors:  Anurag Mantha; Min Tang; Kelsey J Pieper; Jeffrey L Parks; Marc A Edwards
Journal:  Water Res X       Date:  2020-03-03
  5 in total

北京卡尤迪生物科技股份有限公司 © 2022-2023.