Occupational exposure to electric fields and induced currents associated with 400 kV substation tasks from different service platforms.

Leena H Korpinen1, Jarmo A Elovaara, Harri A Kuisti.   

Abstract

The aim of the study was to investigate the occupational exposure to electric fields, average current densities, and average total contact currents at 400 kV substation tasks from different service platforms (main transformer inspection, maintenance of operating device of disconnector, maintenance of operating device of circuit breaker). The average values are calculated over measured periods (about 2.5 min). In many work tasks, the maximum electric field strengths exceeded the action values proposed in the EU Directive 2004/40/EC, but the average electric fields (0.2-24.5 kV/m) were at least 40% lower than the maximum values. The average current densities were 0.1-2.3 mA/m² and the average total contact currents 2.0-143.2 µA, that is, clearly less than the limit values of the EU Directive. The average values of the currents in head and contact currents were 16-68% lower than the maximum values when we compared the average value from all cases in the same substation. In the future it is important to pay attention to the fact that the action and limit values of the EU Directive differ significantly. It is also important to take into account that generally, the workers' exposure to the electric fields, current densities, and total contact currents are obviously lower if we use the average values from a certain measured time period (e.g., 2.5 min) than in the case where exposure is defined with only the help of the maximum values.
© 2010 Wiley-Liss, Inc.

Mesh:

Year:  2011        PMID: 20925064     DOI: 10.1002/bem.20612

Source DB:  PubMed          Journal:  Bioelectromagnetics        ISSN: 0197-8462            Impact factor:   2.010


  2 in total

1.  An In Situ and In Silico Evaluation of Biophysical Effects of 27 MHz Electromagnetic Whole Body Humans Exposure Expressed by the Limb Current.

Authors:  Jolanta Karpowicz; Patryk Zradziński; Jarosław Kieliszek; Krzysztof Gryz; Jaromir Sobiech; Wiesław Leszko
Journal:  Biomed Res Int       Date:  2017-07-05       Impact factor: 3.411

2.  The Possibility of Decreasing 50-Hz Electric Field Exposure near 400-kV Power Lines with Arc Flash Personal Protective Equipment.

Authors:  Leena Korpinen; Herkko Pirkkalainen; Timo Heiskanen; Rauno Pääkkönen
Journal:  Int J Environ Res Public Health       Date:  2016-09-23       Impact factor: 3.390