Uses of wastewater drives significant economic activity, supports countless livelihoods particularly those for developing countries. While using wastewater, the challenge is to identify practical, affordable safeguards that do not threaten the health of users. In Yanbu Al-Sinaiyah, treated sewage effluent (TSE) is used for landscape purposes. In the present study, the odour problem caused by TSE in community area has been addressed. Samples were collected and analysed for total coliform, odour, trihalomethanes (THMs), total organic carbon (TOC) and other physicochemical parameters. Results show that in distribution network, residual chlorine was below the detection limit, turbidity, THMs, TOC and total coliform concentration was much higher than point source, and concentration of these parameters was further increased in problematic areas. It was also observed that areas with odourous problem were at the tail of irrigation network. This indicates that odour problem was due to less residual chlorine high turbidity, high rate of coliform and TOC. In odourous water samples, carbon disulphide and dimethyl sulphide were also identified by GC/MS, while in other areas where there was no odour, both these compounds were not detected. Odour problem was successfully resolved by improving sand filtration system to minimise turbidity the main cause of odour, increasing the residual chlorine at the treatment plant and regularly flushing the distribution network.Entities: