| Literature DB >> 20378114 |
Muhammad Rehan1, Abrar Ahmed, Naeem Iqbal.
Abstract
In this paper, a new framework for designing static and low order anti-windup compensator (AWC) for industrial cascade control systems with actuator saturation constraint is presented. Based on less conservative block diagonal quadratic Lyapunov function, sector boundedness, decoupled architecture, L(2) norm reduction and cascade loop compensation, linear matrix inequalities are developed which guarantee stability and suitable performance for overall closed-loop system. Static AWC parameters are obtained by comparing the full order AWC architecture with generalized architecture for cascade control system. Low order AWC is designed by sub-optimal approach in which AWC weights are tuned by designer. Anti-windup compensator is divided into inner and outer loop compensators which compensate the effect of saturation at each level. It is observed that the proposed methodology is less conservative than the traditional AWC schemes when applied to cascade control systems. The proposed scheme is successfully tested experimentally on a temperature-based process control system and results are outlined. 2010 ISA. Published by Elsevier Ltd. All rights reserved.Mesh:
Year: 2010 PMID: 20378114 DOI: 10.1016/j.isatra.2010.03.003
Source DB: PubMed Journal: ISA Trans ISSN: 0019-0578 Impact factor: 5.468