The intracellular multiplication of Legionella pneumophila in protozoa from hospital plumbing systems.

K Nahapetian1, O Challemel, D Beurtin, S Dubrou, P Gounon, F Squinazi.   

Abstract

Between October 1987 and March 1989, we tested 144 water samples obtained from the plumbing and cooling tower systems of 5 Paris hospitals for the presence of legionellae and amoebae. Of the samples tested for Legionella, 67 out of 144 (46.5%) were positive, and 82 out of 116 tested for amoebae (70.7%) were positive. The ability of protozoa to support the multiplication of legionella was shown by incubating samples at 35.5 degrees C for 7-15 days. Prior to determining the presence of legionellae and amoebae, 51 of the 144 samples were incubated. After incubation, 22 out of 25 (88%) samples which were positive for the presence of both Legionella and amoebae showed multiplication of Legionella. In 3 out of the 25 (12%) samples containing Legionella and amoebae, Legionella failed to multiply. Six out of the 51 (11.8%) samples which were negative in direct culture for Legionella but positive for amoebae, became positive after incubation. Legionella did not multiply in samples negative for amoebae, nor was there proliferation in samples after filtration through a 1.2-microns membrane followed by incubation for the same period and temperature. Strains of Legionella pneumophila serogroup 1 and serogroup 6 (SG1 and SG6), including 3 patient isolates and 2 environmental isolates, were cocultured with 2 strains of amoebae and Tetrahymena pyriformis. Plate counts, Gimenez staining and electron microscopy demonstrated that intracellular legionellae proliferation occurred.

Entities:  

Mesh:

Year:  1991        PMID: 1961979     DOI: 10.1016/0923-2508(91)90081-k

Source DB:  PubMed          Journal:  Res Microbiol        ISSN: 0923-2508            Impact factor:   3.992


  5 in total

1.  Comparison of free-living amoebae in hot water systems of hospitals with isolates from moist sanitary areas by identifying genera and determining temperature tolerance.

Authors:  U Rohr; S Weber; R Michel; F Selenka; M Wilhelm
Journal:  Appl Environ Microbiol       Date:  1998-05       Impact factor: 4.792

2.  Influence of Acanthamoeba castellanii on intracellular growth of different Legionella species in human monocytes.

Authors:  B Neumeister; G Reiff; M Faigle; K Dietz; H Northoff; F Lang
Journal:  Appl Environ Microbiol       Date:  2000-03       Impact factor: 4.792

3.  Draft Genome Sequence of Legionella jamestowniensis Isolated from a Patient with Chronic Respiratory Disease.

Authors:  Birgit Prochazka; Alexander Indra; Petra Hasenberger; Marion Blaschitz; Laura Wagner; Günther Wewalka; Sieglinde Sorschag; Daniela Schmid; Werner Ruppitsch
Journal:  Genome Announc       Date:  2016-09-15

Review 4.  From Many Hosts, One Accidental Pathogen: The Diverse Protozoan Hosts of Legionella.

Authors:  David K Boamah; Guangqi Zhou; Alexander W Ensminger; Tamara J O'Connor
Journal:  Front Cell Infect Microbiol       Date:  2017-11-30       Impact factor: 5.293

Review 5.  Legionella pneumophila and Protozoan Hosts: Implications for the Control of Hospital and Potable Water Systems.

Authors:  Muhammad Atif Nisar; Kirstin E Ross; Melissa H Brown; Richard Bentham; Harriet Whiley
Journal:  Pathogens       Date:  2020-04-15
  5 in total

北京卡尤迪生物科技股份有限公司 © 2022-2023.