Prolonged effect of two combined methods for Legionella disinfection in a hospital water system.

E Casari1, A Ferrario, A Montanelli.   

Abstract

This study was conducted in our 650 bed general hospital, which is situated on the southern outskirts of Milan (Italy). After a first nosocomial case of pneumonia (caused by Legionella pneumophila serogroup 1), we first used a conventional method (heat shock) without success. To solve the problem we then tried a copper-silver ionization system combined with a chlorine dioxide device. During the four years after the installation of these two systems we recorded a significant (p < or = 0.05) reduction in Legionella colonization, and no new cases of Legionnaires' disease were observed. Our results suggest that the Cu-Ag ionization system, combined with a chlorine dioxide device, is a highly promising method for the control of Legionella pneumophila in a hospital water distribution system.

Entities:  

Mesh:

Substances:

Year:  2007        PMID: 18376573

Source DB:  PubMed          Journal:  Ann Ig        ISSN: 1120-9135


  2 in total

1.  Longitudinal evaluation of the efficacy of heat treatment procedures against Legionella spp. in hospital water systems by using a flow cytometric assay.

Authors:  Severine Allegra; Florence Grattard; Françoise Girardot; Serge Riffard; Bruno Pozzetto; Philippe Berthelot
Journal:  Appl Environ Microbiol       Date:  2010-12-23       Impact factor: 4.792

Review 2.  The Use of Copper as an Antimicrobial Agent in Health Care, Including Obstetrics and Gynecology.

Authors:  Linda P Arendsen; Ranee Thakar; Abdul H Sultan
Journal:  Clin Microbiol Rev       Date:  2019-08-14       Impact factor: 26.132

  2 in total

北京卡尤迪生物科技股份有限公司 © 2022-2023.