[Community outbreak of pneumonia due to Legionella pneumophila: importance of monitoring hospital cooling towers].

Patricia García de Olalla1, José Gracia, Cristina Rius, Joan A Caylà, Helena Pañella, Joan R Villabí, Joan Guix, Teresa Pellicer, Dolors Ferrer, Meritxell Cusi, Carmen Pelaz, Miquel Sabrià.   

Abstract

OBJECTIVE: Description of an outbreak of legionnaires' disease originating in one of the cooling towers of a hospital. PATIENTS AND METHODS: This study included patients with confirmed pneumonia caused by Legionella pneumophila serogroup 1 and related to the Vallcarca neighborhood of Barcelona (Spain) in August 2004. Exposure was determined by a standardized questionnaire. An environmental investigation was carried out to identify the source of the outbreak. A descriptive analysis including incidence rates estimation was performed, as well as molecular study to document the genetic identity among human and environmental strains.
RESULTS: Thirty-three cases of L. pneumophila pneumonia were detected. Median age was 68 years and 70% of the affected patients were men. Incidence rate among residents in less than 200 meters of the source and older than 65 was 888.9 cases/100,000 inhabitants. Lethality rate was 6%. Four seasonal cooling towers that were not registered with the authorities were identified in a health care center. L. pneumophila was isolated from all four and at least one colony in each tower had the same genetic profile as the strains isolated from patients.
CONCLUSIONS: An association was demonstrated between a community outbreak of legionellosis and unregistered seasonal cooling towers located in a hospital. All risk facilities should be registered and inspected to ensure that they fulfill current legislation requirements.

Entities:  

Mesh:

Substances:

Year:  2008        PMID: 18208761

Source DB:  PubMed          Journal:  Enferm Infecc Microbiol Clin        ISSN: 0213-005X            Impact factor:   1.731


  3 in total

Review 1.  A review of back-calculation techniques and their potential to inform mitigation strategies with application to non-transmissible acute infectious diseases.

Authors:  Joseph R Egan; Ian M Hall
Journal:  J R Soc Interface       Date:  2015-05-06       Impact factor: 4.118

2.  Population structure of Environmental and Clinical Legionella pneumophila isolates in Catalonia.

Authors:  Sara Quero; Noemí Párraga-Niño; Irene Barrabeig; Maria Rosa Sala; M Luisa Pedro-Botet; Eduard Monsó; Mireia Jané; Miquel Sabrià; Marian Garcia-Núñez
Journal:  Sci Rep       Date:  2018-04-19       Impact factor: 4.379

3.  The impact of pipeline changes and temperature increase in a hospital historically colonised with Legionella.

Authors:  S Quero; N Párraga-Niño; M Garcia-Núñez; M L Pedro-Botet; L Gavaldà; L Mateu; M Sabrià; J M Mòdol
Journal:  Sci Rep       Date:  2021-01-21       Impact factor: 4.379

  3 in total

北京卡尤迪生物科技股份有限公司 © 2022-2023.