Literature DB >> 17870669

Hospital-acquired legionellosis originating from a cooling tower during a period of thermal inversion.

Steffen Engelhart1, Stefan Pleischl, Christian Lück, Günter Marklein, Edith Fischnaller, Sybille Martin, Arne Simon, Martin Exner.   

Abstract

A case of hospital-acquired legionellosis occurred in a 75-year-old male patient who underwent surgery due to malignant melanoma. Legionellosis was proven by culture of Legionella pneumophila serogroup 1 from bronchoalveolar lavage (BAL) fluid. Being a chronic smoker the patient used to visit the sickroom balcony that was located about 90 m to the west of a hospital cooling tower. Routine cooling tower water samples drawn during the presumed incubation period revealed 1.0x10(4) CFU/100 ml (L. pneumophila serogroup 1). One of three isolates from the cooling tower water matched the patient's isolate by monoclonal antibody (mab)- and genotyping (sequence-based typing). Horizontal transport of cooling tower aerosols probably was favoured by meteorological conditions with thermal inversion. The case report stresses the importance of routine maintenance and microbiological control of hospital cooling towers.

Entities:  

Mesh:

Substances:

Year:  2007        PMID: 17870669     DOI: 10.1016/j.ijheh.2007.07.022

Source DB:  PubMed          Journal:  Int J Hyg Environ Health        ISSN: 1438-4639            Impact factor:   5.840


  4 in total

Review 1.  Occurrence and Control of Legionella in Recycled Water Systems.

Authors:  Patrick K Jjemba; William Johnson; Zia Bukhari; Mark W LeChevallier
Journal:  Pathogens       Date:  2015-07-01

2.  Industrial Cooling Tower Disinfection Treatment to Prevent Legionella spp.

Authors:  Matteo Iervolino; Benedetta Mancini; Sandra Cristino
Journal:  Int J Environ Res Public Health       Date:  2017-09-26       Impact factor: 3.390

Review 3.  Outbreaks of Legionnaires' Disease and Pontiac Fever 2006-2017.

Authors:  K A Hamilton; A J Prussin; W Ahmed; C N Haas
Journal:  Curr Environ Health Rep       Date:  2018-06

4.  Effect of pollutant source location on air pollutant dispersion around a high-rise building.

Authors:  Erfan Keshavarzian; Ruizhi Jin; Kejun Dong; Kenny C S Kwok; Yu Zhang; Ming Zhao
Journal:  Appl Math Model       Date:  2020-01-15       Impact factor: 5.129

  4 in total

北京卡尤迪生物科技股份有限公司 © 2022-2023.