Literature DB >> 17601635

Disconnecting central hot water and using electric showers to avoid colonization of the water system by Legionella pneumophila: an 11-year study.

M S Oliveira1, F R Maximino, R D Lobo, S Gobara, S I Sinto, L E Ianhez, C L Warschauer, A S S Levin.   

Abstract

Legionella spp. can be difficult to control in hospitals. The objective of this study was to describe an 11-year experience with the use of electric showers in the control of Legionella pneumophila. From June 1989 to March 1990 there was an outbreak of pneumonia caused by L. pneumophila in a 20-bed renal transplant unit in a university-associated tertiary-care hospital. Control measures included hyperchlorination, heating and flushing of the water system with limited results. In November 1993 the central hot water was disconnected and water for bathing was heated using electric showers. From January 1992 to June 1995 water was collected from showers and water faucets and cultured for L. pneumophila every two weeks. Surveillance cultures were then collected every month until May 1999. During this seven-year surveillance period, 1115 samples of water were cultured. Water cultures were positive on 24 of 429 occasions (without cases of legionellosis) during the pre-shower period (22 months). In the post-shower period (67 months) only one of 686 cultures was positive. Subsequently there have been no new cases of nosocomial pneumonia by L. pneumophila although surveillance continues. In conclusion, disconnecting the central hot water was effective in avoiding colonization of the water system by L. pneumophila. Heating was possible by using electric showers, which are effective, easy to maintain and cheap.

Entities:  

Mesh:

Year:  2007        PMID: 17601635     DOI: 10.1016/j.jhin.2007.04.020

Source DB:  PubMed          Journal:  J Hosp Infect        ISSN: 0195-6701            Impact factor:   3.926


  3 in total

Review 1.  The role of water in healthcare-associated infections.

Authors:  Brooke K Decker; Tara N Palmore
Journal:  Curr Opin Infect Dis       Date:  2013-08       Impact factor: 4.915

Review 2.  Plumbing of hospital premises is a reservoir for opportunistically pathogenic microorganisms: a review.

Authors:  Margaret M Williams; Catherine R Armbruster; Matthew J Arduino
Journal:  Biofouling       Date:  2013       Impact factor: 3.797

3.  Risk Exposure to Legionella pneumophila during Showering: The Difference between a Classical and a Water Saving Shower System.

Authors:  Hélène Niculita-Hirzel; Audrey S Vanhove; Lara Leclerc; Françoise Girardot; Jérémie Pourchez; Séverine Allegra
Journal:  Int J Environ Res Public Health       Date:  2022-03-10       Impact factor: 3.390

  3 in total