Literature DB >> 17050350

Evaluation of source model coupled computational fluid dynamics (CFD) simulation of the dispersion of airborne contaminants in a work environment.

S M Salim1, Shekar Viswanathan, Madhumita Bhowmick Ray.   

Abstract

Dispersion of airborne contaminants in indoor air was evaluated employing physical measurement, empirical models, and computer simulation methods. Field data collected from a tray of evaporating solvent in the laboratory were compared with computational fluid dynamics (CFD) simulations coupled with evaporation models. The results indicated that mathematical models of evaporation can be coupled with CFD simulations to produce reasonable qualitative predictions of airborne contaminant levels. The airflow pattern within a room is primarily determined by the room layout and the position of the air supply diffusers. Variations in ventilation rate did not alter the airflow pattern, thus generating a characteristic concentration profile of the airborne contaminants.

Entities:  

Mesh:

Substances:

Year:  2006        PMID: 17050350     DOI: 10.1080/15459620601011140

Source DB:  PubMed          Journal:  J Occup Environ Hyg        ISSN: 1545-9624            Impact factor:   2.155


  1 in total

Review 1.  Current and potential approaches on assessing airflow and particle dispersion in healthcare facilities: a systematic review.

Authors:  Huiyi Tan; Keng Yinn Wong; Mohd Hafiz Dzarfan Othman; Hong Yee Kek; Roswanira Abdul Wahab; Garry Kuan Pei Ern; Wen Tong Chong; Kee Quen Lee
Journal:  Environ Sci Pollut Res Int       Date:  2022-10-04       Impact factor: 5.190

  1 in total