Emission modelling and validation of VOCs' source strengths in air-conditioned office premises.

K W Tham1, M S Zuraimi, S C Sekhar.   

Abstract

An emission model for indoor volatile organic compounds (VOCs) based on mass balance considerations has been presented and validated under steady state conditions. Comparison were made for the measured and predicted concentrations of 37 selected VOCs and TVOC through a case intervention study on the filters of the ventilation system in a new commercial air-conditioned office building. The intervention involved replacing media filters with electronic and carbon filtration. TVOC and 37 compounds selected for their health and comfort impact, representation of major chemical classes that occur in indoor air and their utility as markers of pollution sources were studied. The concentration levels predicted by the model were compared with actual measurements. Twenty-five target compounds and the TVOC were adequately described by the model where the measured concentrations were in agreement with the predicted concentrations. Modeling of the remaining 12 compounds was found to be affected by the emission rates that were occupant related.

Entities:  

Mesh:

Substances:

Year:  2004        PMID: 15337353     DOI: 10.1016/j.envint.2004.06.001

Source DB:  PubMed          Journal:  Environ Int        ISSN: 0160-4120            Impact factor:   9.621


  1 in total

1.  Temporal evolution of the main processes that control indoor pollution in an office microenvironment: a case study.

Authors:  Christos H Halios; Costas G Helmis
Journal:  Environ Monit Assess       Date:  2009-06-27       Impact factor: 2.513

  1 in total