| Literature DB >> 15109413 |
Paola Borella1, M Teresa Montagna, Vincenzo Romano-Spica, Serena Stampi, Giovanna Stancanelli, Maria Triassi, Rachele Neglia, Isabella Marchesi, Guglielmina Fantuzzi, Daniela Tatò, Christian Napoli, Gianluigi Quaranta, Patrizia Laurenti, Erica Leoni, Giovanna De Luca, Cristina Ossi, Matteo Moro, Gabriella Ribera D'Alcalà.
Abstract
We investigated Legionella and Pseudomonas contamination of hot water in a cross-sectional multicentric survey in Italy. Chemical parameters (hardness, free chlorine, and trace elements) were determined. Legionella spp. were detected in 33 (22.6%) and Pseudomonas spp. in 56 (38.4%) of 146 samples. Some factors associated with Legionella contamination were heater type, tank distance and capacity, water plant age, and mineral content. Pseudomonas presence was influenced by water source, hardness, free chlorine, and temperature. Legionella contamination was associated with a centralized heater, distance from the heater point >10 m, and a water plant >10 years old. Furthermore, zinc levels of <100 microg/L and copper levels of >50 microg/L appeared to be protective against Legionella colonization [corrected]. Legionella species and serogroups were differently distributed according to heater type, water temperature, and free chlorine, suggesting that Legionella strains may have a different sensibility and resistance to environmental factors and different ecologic niches.Entities:
Mesh:
Substances:
Year: 2004 PMID: 15109413 PMCID: PMC3322798 DOI: 10.3201/eid1003.020707
Source DB: PubMed Journal: Emerg Infect Dis ISSN: 1080-6040 Impact factor: 6.883
Characteristics of water supply and distribution systems in the examined buildings (N = 146)
| Characteristic | Frequency no. (%) |
|---|---|
| Type of water |
|
| Groundwater | 67 (46.2) |
| Mixture water | 79 (53.8) |
| Disinfection |
|
| Cl dioxide | 58 (39.7) |
| Na hypochlorite | 30 (20.6) |
| Cl dioxide + Na hypochlorite | 32 (22.2) |
| None | 26 (17.5) |
| Plumbing material |
|
| Metal | 131 (89.7) |
| Plastic | 15 (10.3) |
| Type of heater |
|
| Independent |
|
| Gas, tank | 30 (20.5) |
| Electric | 22 (15.1) |
| Gas, instant | 55 (37.7) |
| Central |
|
| House | 36 (24.7) |
| Neighborhood | 3 (2.1) |
| Softening system |
|
| Absent | 124 (84.9) |
| Present | 22 (15.1) |
| Hot water circulation |
|
| Absent | 117 (80.1) |
| Present | 29 (19.9) |
| Plant maintenance |
|
| Never/every 2 years | 26 (17.8) |
| Once/year | 100 (68.5) |
| Every 6 months | 20 (13.7) |
Chemical, physical, and microbiologic characteristics of the examined hot water samples
| Characteristic | Mean | SD | Minimum | Maximum | |
|---|---|---|---|---|---|
| Ca (mg/L) | 85.0 | 33.0 | 0.1 | 252.0 | |
| Mg (mg/L) | 17.6 | 10.6 | 0.1 | 90.1 | |
| Total hardness (°F) | 28.3 | 11.4 | 0.3 | 100.1 | |
| Sampling temperature (°C) | 41.9 | 12.4 | 17.0 | 65.0 | |
| Operating temperature (°C) | 52.9 | 10.0 | 20.0 | 90.0 | |
|
| Geometric mean | Median | 5th percentile | 95th percentile | |
| Fe (μg/L) | 15.0 | 21.0 | 0.1 | 171.5 | |
| Mn (μg/L) | 2.4 | 3.0 | 0.1 | 13.9 | |
| Cu (μg/L) | 11.5 | 14.2 | 0.1 | 87.5 | |
| Zn (μg/L) | 62.6 | 100.0 | 1 | 776.4 | |
| Free Cl (μg/L) | 9.2 | 26.4 | 0.0 | 250.0 | |
| Oxidizability (mg/L O2) | 0.63 | 0.64 | 0.24 | 1.70 | |
| 139.2 | 223.6 | 1.0 | 1.0 × 104 | ||
| Total count at 36°C (CFU/mL)a | 98.6 | 95.0 | 3.4 | 1.7 × 103 | |
| Total count at 22°C (CFU/mL)a | 50.4 | 30.0 | 4.0 | 3.9 × 103 | |
aPositive samples only.
Characteristics of Legionella contamination in the examined domestic hot water
| Characteristic | Other | |||
|---|---|---|---|---|
| Positive samples
n (%) | 33/146 (22.6) | 6/33 (18.2) | 19/33 (57.6) | 8/33 (24.2) |
| Count (CFU/L) | ||||
| Geometric mean | 1.17 × 103 | 0.96 × 103 | 0.94 × 103 | 2.30 × 103 |
| Median | 1.85 × 103 | 0.89 × 103 | 1.85 × 103 | 3.16 × 103 |
| 5th percentile | 54 | 100 | 25 | 100 |
| 95th percentile | 4.1 × 104 | 5 × 103 | 3 × 104 | 8.8 × 104 |
| Distribution n (%) | ||||
| 1–9.9×102 CFU/L | 15/33 (45.4) | 3/6 (50.0) | 9/19 (47.4) | 3/8 (37.5) |
| 103–9.9 × 103 CFU/L | 15/33 (45.4) | 3/6 (50.0) | 8/19 (42.1) | 4/8 (50.0) |
| 3/33 (9.2) | 0/6 (0.0) | 2/19 (10.5) | 1/8 (12.5) |
Univariate analysis of system and building characteristics associated with microbial contaminationa
| Characteristic | OR (95% CI) | |||
|---|---|---|---|---|
| Total count at 36°C high/low (62/84)b | Total count at 22°C high/low (35/111)b | |||
| Central heater | 9.24c (3.87 to 22.05) | 0.87 (0.40 to 1.85) | 0.92 (0.44 to 1.94) | 1.36 (0.59 to 3.12) |
| Distribution site distance >10 m | 8.10c (3.41 to 19.23) | 0.47* (0.22 to 1.00) | 1.08 (0.54 to 2.17) | 1.51 (0.69 to 3.32) |
| Tank capacity
>100 L | 5.21c (2.14 to 12.67) | 0.58 (0.24 to 1.43) | 0.58 (0.24 to 1.39) | 0.64 (0.22 to 1.83) |
| Age of heating plant
>10 y | 3.24d (1.38 to 7.59) | 1.85e (0.94 to 3.64) | 1.14 (0.59 to 2.19) | 1.58 (0.73 to 3.43) |
| House floor >3rd | 2.35e (1.04 to 5.30) | 1.38 (0.66 to 2.87) | 0.94 (0.45 to 1.96) | 1.24 (0.54 to 2.83) |
| Apartments >12/building | 2.26e (0.99 to 5.18) | 1.48 (0.75 to 2.91) | 1.00 (0.52 to 1.94) | 1.13 (0.53 to 2.44) |
| Sampling temperature >50°C | 0.62 (0.26 to 1.49) | 0.91 (0.24 to 3.40) | 1.16 (0.54 to 2.51) | 1.22 (0.54 to 2.75) |
| Operating temperature >50°C | 0.69 (0.29 to 1.67) | 0.32d (0.15 to 0.70) | 1.74 (0.80 to 3.76) | 0.57 (0.24 to 1.36) |
aOR, odds ratio; CI, confidence interval. bHigh >100 CFU/mL. cp < 0.001. dp < 0.01. ep < 0.05.
Univariate analysis of water chemical parameters associated with microbiologic dataa
| Chemical | Total count at 36°C (high/low)b | Total count at 22°C (high/low)b | |||
|---|---|---|---|---|---|
| OR (95% CI) | OR (95% CI) | OR (95% CI) | OR (95% CI) | ||
| Cu ≥50 μg/L | 0.14c (0.02 to 1.13) | 0.99 (0.38 to 2.56) | 0.64 (0.24 to 1.68) | 0.71 (0.22 to 2.28) | |
| Zn <100 μg/L | 0.33d (0.14 to 0.76) | 1,21 (0.62 to 2.35) | 0.38d (0.19 to 0.75) | 0.29d (0.13 to 0.67) | |
| Fe <20 μg/L | 0.37c (0.16 to 0.85) | 1.96c (1.00 to 3.86) | 050c (0.25 to 0.97) | 0.74 (0.34 to 1.58) | |
| Mn <3 μg/L | 0.42c (0.19 to 0.94) | 1.50 (0.76 to 2.94) | 0.23e (0.11 to 0.45) | 0.31d (0.14 to 0.70) | |
| Hardness >25°F | 0.41c (0.18 to 0.89) | 3.91e (1.80 to 8.52) | 1.92(0.96 to 3.86) | 1.03 (0.47 to 2.26) | |
| Oxidizability >0.5 mg/L O2 | 0.42c (0.18 to 0.95) | 1.12 (0.52 to 2.42) | 1.01 (0.49 to 2.07) | 0.29d (0.12 to 0.68) | |
| Free Cl present | 0.51 (0.23 to 1.15 ) | 0.35d (0.17 to 0.73) | 1.52 (0.73 to 3.13) | 0.49 (0.22 to 1.09) | |
aOR, odds ratio; CI, confidence interval. bHigh >100 CFU/mL. cp < 0.05. dp < 0.01. ep < 0.001.
Multiple logistic regression of system and water characteristics associated with Legionella contaminationa
| Variable | |
|---|---|
|
| OR (95% CI) |
| Central heater | 4.88 (1.61 to 14.76)b |
| Distribution site distance >10 m | 4.55 (1.55 to 13.33)c |
| Zn <100 μg/L | 0.22 (0.07 to 0.66)c |
| Heating system age >10 yr | 3.68 (1.25 to 10.82)d |
| Cu >50 μg/L | 0.08 (0.01 to 0.97)d |
aOR, odds ratio; CI, confidence interval. bp < 0.005. cp < 0.01. dp < 0.05.
Differences in some water parameters according to Legionella species
| Characteristic | F score (p) | |||
|---|---|---|---|---|
| Sampling temperature (°C) | 29.4 ± 11.8 | 48.9 ± 4.4a | 31.2 ± 15.5 | 15.17 (<0.001) |
| Operating temperature (°C) | 43.3 ± 12.1a | 53.7 ± 5.9 | 57.0 ± 4.4 | 6.91 (<0.005) |
|
| Geometric mean | Geometric mean | Geometric mean |
|
| Free chlorine (μg/L) | 78.0 | 2.6a | 32.3 | 7.86 (<0.002) |
| 0.4 | 19.1b | 0.6 | 3.31 (<0.05) |
ap < 0.05 versus the other two groups. bp < 0.05 versus Legionella other species.